MECHANICAL

Contract/PO No.: Document No.: Total Pages:


4650013432 20-01-BRGA-MEC-TBE-0005 XX

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15 MMSCFD


BERINGIN A
ASSET 2 FIELD PRABUMULIH

TBE FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)

A 22-Jun-20 Issued for Information DPO/DAW API THP YHN ES


BY CHK APP CHK APP
REV DATE DESCRIPTION
PT ELNUSA TBK PERTAMINA EP

TOTAL OR PARTIAL REPRODUCTION AND/OR UTILIZATION OF THIS DOCUMENT ARE


FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
TOTAL OR PARTIAL REPRODUCTION AND/OR UTILIZATION OF THIS DOCUMENT ARE
FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page 2

Table of Revision

REVISION REVISION REVISION


PAGE PAGE ATTC REMARK
A B C 0 1 A B C 0 1 A B C 0 1
1 X 31 1
2 X 32 2
3 X 33 3
4 X 34 4
5 X 35 5
6 36
7 37
8 38
9 39
10 40
11 41
12 42
13 43
14 44
15 45
16 46
17 47
18 48
19 49
20 50
21 51
22 52
23 53
24 54
25 55
26 56
27 57
28 58
29 59
30 60
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page 3

Revision Log Register

Revision had been performed on following pages:

Rev Page Date Revision


A All 1-Apr-20 First Issueance
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page 4

Table of Content

1 Cover 1
2 Table of Revision 2
3 Revision Log Register 3
4 Table of Content 4
5 Summary 5
6 Detail TBE 6
7 Attachment 1 - Deviation List
8 Attachment 2 - Bidders Un-Priced Quotation
9 Attachment 3 - Email Correspondences / Clariffications (if any)
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page 5

Summary

1 General
Evaluation Process shall refer to project requirement, scope of work & supply, standard quality
and performances.
Further clarifications should be required from the respected Bidder that was sought through the
technical bid clarification. The recommendation in section 5 below was made based purely on the
result of this technical evaluation.

2 Reference Project Documents & Drawings


RFQ for TEG Dedydration Package 20-01-BRGA-MEC-RFQ-0007 and its attachments.
3 Bidders Proposal

Manufacturer of Main Delivery Time


No Bidder Quotation No
Equipment (ARO)

4 Technical Evaluation Result


Bidder 1 PT. ABC
PT. ABC is technically acceptable with the following remarks:
1
2
Bidder 2 PT. ABC
PT. ABC is technically not acceptable with the following remarks:
1
2
Bidder 3 PT. ABC
PT. ABC is technically acceptable with the following remarks:
1
2

5 Recommendations
Based on Technical Evaluation Result, the following Bidder proposal is technically acceptable
and can be proceed to the next stage (Commercial evaluation):
1
2
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
1 GENERAL
1 Manufacture As Per PML
2 Country of Origin As Per PML
3 Delivery Time
4 Delivery Terms FOT Factory/Warehouse

The Vendor shall guarantee the


performance and workmanship of the
equipment supplied along with quality of
material, manufacture and assembly.
5 Warranty
The guarantee shall be valid for a period
of twelve (12) months after first start or
eighteen (18) months after delivery at
site whichever comes first.

6 Compliance / deviation list Provided


7 Migas Certification Required
8 Hazardous Area Classification (Indoor) Safe Area
9 Hazardous Area Classification (Outdoor) Class 1 Div.2 Gr D, Temp Class T3

2 DOCUMENTATIONS
1 Quotation, including best possible delivery time Provided
2 Company Profile and Experience List similar project/supplies Provided
3 Supporting Letter from Manufacturer Provided
4 Product Catalog Provided
Planning: Delivery Schedule of studies, sub-orders, fabrication (time and
5 Provided
point), including supporting letter from sub vendor
6 Material Take Off and List of Sub - Equipment Provided
7 Statement of Guarantee Provided
8 List of spare parts and consumable for installation and commissioning, start up Provided
9 Recommended spare parts list for two years operation including price list Provided
10 Spare part 10 years availability statement from manufacturer Provided
11 List of special tools for installation and maintenance Provided
12 List of special tools for calibration and test Provided
13 Coordination scheme / project organization Provided
14 General arrangement and outline drawing (external & internal) Provided
15 Architecture drawing and interconnection drawing Provided
16 Panel Arrangement and Accessories Equipment List Provided
17 Dimensional outline and mounting details, with weight Provided
18 Document s per VDRL Provided
19 MIGAS document for SKPP Provided

3 PROCESS PERFORMANCE GUARANTEE


1 GLYCOL VOLUME RATE 2.46 Usgpm (0.56 m³/h) (VTC)
2 GLYCOL CIRCULATION RATE 46.57 lb TEG/ lb water (VTC)
3 TEMPERATURE (NORMAL /MAXIMUM) 110 °F (43 °C) / 120 °F (49 °C)
4 PRESSURE (NORMAL) 820 psig (56.5 barg)
5 WATER CONTENT AT GAS OUTLET STREAM < 7 lb/MMSCF
6 GAS FLOWRATE (NORMAL) 14.372 MMSCFD
7 GLYCOL CONCENTRATION 99.5 %wt
8 IMPURITIES:
9 H2S 50 ppmv
10 RSH 10 ppmv
11 CO2 10% mole

4 MECHANICAL
1 TEG Contactor (BRA-C-3001) 1 unit 1 unit
2 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
3 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
4 DESIGN DATA
5 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) 200 / 110 / 120 °F
6 PRESSURE (DESIGN / OPERATING) 1020 / 828 psig
7 LIQUID Glycol
8 VOLUME RATE 2.46 gpm
9 VISCOSITY 13.38 cp
10 VAPOUR
11 STD GAS FLOWRATE 3.639 MMscfd
12 OLECULAR WEIGHT 22.19
13 INLET WATER CONTENT 142 lb/MMSCF
14 OUTLET WATER CONTENT 7 lb/MMSCF
15 GLYCOL CIRCULATION RATE VTA lb TEG / lb water
16 VESSEL SIZE :
17 DIA (ID) 1000 (VTC) mm
18 LENGTH (T/T) 7700 (VTC) mm
19 VESSEL THICKNESS: mm
20 SHELL THK VTA mm
21 HEAD THK VTA
22 CONSTRUCTION MATERIAL
23 SHELL SA-516 Gr. 70
24 HEADS SA-516 Gr. 70
25 SKIRT SA-516 Gr. 70
26 INTERNALS SS 316
27 INTERNAL ATTACHMENTS SS 316
28 EXTERNAL ATTACHMENTS SA-516 Gr. 70
29 FITTINGS SA-234 GR. WPB
30 EARTHING LUGS SS 316
31 LIFTING LUGS & TAILING LUGS SA-516 Gr. 70
32 FLANGES SA-105
33 NOZZLE NECK (PIPE) SA-106 GR. B
34 REINFORCING PADS SA-516 Gr. 70
35 EXTERNAL BOLTS SA-193 Gr. B7
36 EXTERNAL NUTS SA-194 Gr. 2H
37 INTERNAL BOLTS SS 316
38 INTERNAL NUTS SS 316
39 VORTEX BREAKER SA-516 Gr. 70
40 INTERNAL LADDER RUNG SA-106 GR. B
41 MANHOLE DAVIT SA-516 Gr. 70
42 BASE PLATE SA-36
43 GASKETS SS 316 with graphite filler
44 NAME PLATE SS 316
45 PLATFORM / LADDER / HANDRAIL SA-36
46 FOUNDATION BOLTS / NUTS SA-307 GR. B or EQUIVALENT
47 CONSTRUCTION
48 TYPE OF HEADS Required
49 TYPE OF SUPPORT Required
50 PLATFORM, LADDER, HANDRAIL & CLIP Required
51 MANHOLE DAVIT Required
52 EARTHING LUGS Required
53 LIFTING LUGS / EYES Required
54 NAMEPLATE Required
55 WELD JOINT EFFICIENCIES:
56 SHELL 1
57 HEAD 1
58 CORROSION ALLOWANCE 3 mm
59 NON DESTRUCTIVE TESTING:
60 RADIOGRAPHY YES, AS PER SPEC & CODE
61 ULTRASONIC YES, AS PER SPEC & CODE
62 MAGNETIC PARTICLE YES, AS PER SPEC & CODE
63 DYE PENETRANT YES, AS PER SPEC & CODE
64 PAINTING (INTERNASL & EXTERNAL) AS PER 20-01-BRGA-MEC-SPE-0001
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
65 TRANSPORTATION LOAD AS PER DESIGN BASIS
66 WIND LOAD 58,67 ft / s
67 SEISMIC LOAD SKBI-1.3.53.1987, ZONE 4
68 MDMT VTA
69 ESTIMATED WEIGHTS
70 EMPTY VTA kg
71 SHIPPING VTA kg
72 OPERATING VTA kg
73 FIELD TEST VTA kg
74
75 LEAN TEG / DRY GAS EXCHANGER (BRA-HE-3001) 1 unit 1 unit
76 DESIGN CODE ASME, TEMA R
77 DESIGN DATA
78 TEMPERATURE (DESIGN / OPERATING) 200 / 120 °F
79 PRESSURE (DESIGN / OPERATING) 1020 / 851 psig
80 PERFORMANCE OF ONE UNIT
81 Fluid name TEG
82 Total fluid entering VTA lb/h
83 Fluid vaporized or condensed VTA lb/h
84 Pressure drop : allow. / calc. VTA psi
85 Fouling resistance 22.19 ft² x hr x ºF/Btu
86 Min. Corrosion Allowance 142 in
87 Number of passes per shell 7
88 Total Area VTA ft²
89 LMTD VTA
90 Corrected MTD VTA
91 Transfer rate:
92 Clean VTA Btu/hr.ft².ºF
93 Service VTA Btu/hr.ft².ºF
94 NOZZLE SCHEDULE
95 SHELL SIDE NOZZLES
96 Inlet 6"/RFWN/600#
97 Outlet 6"/RFWN/600#
98 TUBESIDE NOZZLES
99 Inlet 2"/RFWN/600#
100 Outlet 2"/RFWN/600#
101 SHELL DETAILS
102 Shell O.D ft-in
103 Shell thickness in
104 Head (Location/type) VTA
105 Head thickness in
106 Baffles crosspasses VTA
107 No. Baffles / type VTA
108 Baffle/ support spacing VTA
109 Baffle cut (diam / area) VTA
110 Longitudinal baffle (seal type) VTA
111 Expansion joint (type) VTA
112 Impingement plate VTA
113 Tube to tubesheet joint VTA
114 Tube holes VTA
115 Face joint @ tubesheet VTA
116 Pass lane seal rods VTA
117 Tie rod holes VTA
118 TUBE DETAILS
119 No. Tubes/Shell VTA
120 OD x Length VTA
121 Tube thickness VTA
122 Tube type VTA
123 Tube pitch VTA
124 Tube arrangement VTA
125 By pass seal (seal bar) VTA
126 Support at U-bend VTA
127 Tubesheet thickness VTA
128 Removable tube bundle Yes
129 Radiography /Joint efficiency: FULL (shell & tube side)
130 Joint Efficiency 1 (shell & tube side)
131 CONSTRUCTION MATERIAL
132 Shell / Head SA 106 Gr.B / ASTM A 516 Gr.70
133 Shell Nozzle Necks SA 106 Gr.B
134 Shell Nozzle Flanges SA 105
135 Channel Cover A 515 Gr. 70
136 Channel Flanges SA 105
137 Channel Nozzle Necks SA 106 Gr.B
138 Channel Nozzle Flanges SA 105
139 Tubesheets A 515 Gr. 70
140 Nameplate SS 304
141 Tubes SA 214
142 Baffles / Support Plates / Weir Plate A 283 Gr.C
143 Partition Plate A 283 Gr.C
144 Spacers / Dummy Tubes -
145 Saddle Wrapper Plates -
146 External Stud Bolts A 193 Gr. B7
147 External Nuts A 194 Gr. 2H
148 Gaskets Shell Side SPIRAL WOUND LOW STRESS 316SS
149 Gaskets Tube Side SPIRAL WOUND LOW STRESS 316SS
150 Saddle Parts A 515 Gr. 70
151 Internal Bolts / Nuts A 193 Gr. B8M / A 194 Gr. 8M
152 Surface Preparation As per BRGA-00-N2-SP-001,
153 Fire Proofing No
154 Insulation, (Type / Thk.) Yes (VTA)
155 Size (OD x OAL) ft-in
156 Orientation VERTICAL (VTC)
157 ESTIMATED WEIGHTS
158 Weight empty VTA kg
159 Tube bundle weight VTA kg
160 Weight - insulation VTA kg
161 Weight - operating VTA kg
162 Weight - full of water VTA kg
163
164 TEG FLASH DRUM (TAG. NO. TBA) 1 unit 1 unit
165 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
166 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
HORIZONTAL, 3-PHASE SEPARATOR
167 TYPE
(VTA)
168 DESIGN DATA
169 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) VTA °F
170 PRESSURE (DESIGN / OPERATING) VTA psig
171 FLUID RICH TEG + HC (VTA)
172 TOTAL CAPACITY VTA gpm
173 VESSEL SIZE :
174 DIA (ID) VTA mm
175 LENGTH (T/T) VTA mm
176 VESSEL THICKNESS: mm
177 SHELL THK VTA mm
178 HEAD THK VTA
179 TYPE OF HEAD 2:1 ELLIPTICAL
180 CORROSION ALLOWANCE 3 mm
181 SUPPORT TYPE SADDLES
182 INSULATION No
183 PERSONAL PROTECTION No
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
184 FIREPROOFING No
SKIMMING, WEIR, STRUCTURED
185 INTERNALS PACKING, INLET IMPACTOR,
VORTEX BREAKER (VTA)
186 CONSTRUCTION MATERIAL
187 Pressure plates SA-516 Gr. 70
188 Non-pressure plates SA 36 / SA 283 Gr. C
189 Skid / structure SA 36 / SA 283 Gr. C
190 Flanges SA-105
191 Nozzle neck / pipe SA 106 / API 5L Gr. B
192 Internals (Wet CO2) SS 316L
193 Internals (Others) SS 316L
SA 516 Gr. 70 (except attachment on
194 Internal and external attachments
the cladding surface)
SA 193 Gr. B7 & SA 194 Gr. 2H (hot dip
195 External bolts & nuts
galvanized)
196 ESTIMATED WEIGHTS
197 WEIGHT (REMOVABLE INTERNALS) VTA kg
198 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
199
200 TEG REBOILER (TAG NO. TBA ) & HEATER (TAG NO. TBA)
201 TYPE FLUE U-TUBE (VTA)
202 DESIGN DATA
203 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) VTA °F
204 PRESSURE (DESIGN / OPERATING) VTA psig
205 FLUID RICH TEG (VTA)
206 TOTAL CAPACITY VTA gpm
207 VESSEL SIZE :
208 DIA (ID) VTA mm
209 LENGTH (T/T) VTA mm
210 VESSEL THICKNESS: mm
211 SHELL THK VTA mm
212 HEAD THK VTA
213 TYPE OF HEAD 2:1 ELLIPTICAL
214 CORROSION ALLOWANCE 3 mm
215 SUPPORT TYPE SADDLES
216 INSULATION Yes
217 PERSONAL PROTECTION Yes
218 FIREPROOFING No

CORRUGATED FIRE TUBE, RETURN


219 INTERNALS PIPE, RETURN BOX, GAS BOX, COIL,
INTERNAL SUPPORT (VTA)

220 CONSTRUCTION MATERIAL


SA-516 Gr. 70 WITH A MINIMUM
221 Pressure plates
WALL THICKNESS 5/16" (VTA)
222 Non-pressure plates SA 36 / SA 283 Gr. C
223 Skid / structure SA 36 / SA 283 Gr. C
224 Flanges SA-105
225 Nozzle neck / pipe SA 106 / API 5L Gr. B
226 Internals (Wet CO2) SS 316L
227 Internals (Others) SS 316L
SA 516 Gr. 70 (except attachment on
228 Internal and external attachments
the cladding surface)
SA 193 Gr. B7 & SA 194 Gr. 2H (hot dip
229 External bolts & nuts
galvanized)
230 ESTIMATED WEIGHTS
231 WEIGHT (REMOVABLE INTERNALS) VTA kg
232 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
233 BURNER CHARACTERISTICS:
234 TYPE FORCED DRAFT BURNER (VTC)
235 MANUFACTURER VTA
236 PILOT TYPE INTERMITTENT (VTC)
237 IGNITER TYPE (PORTABLE, FIXED, RETRACTABLE) & NUMBER FIXED / 1 (VTC)
238 FLAME DETECTOR TYPES & NUMBERS UV / 1 PER BURNER (VTC)
239 SIGHT GLASS YES (VTC)
240 IGNITOR TYPE & NUMBER SPARK PULSE GENERATOR (VTA)
241 AIR BLOWER:
242 TEMPERATURE (MIN. /MAX.) (VTA)
243 STATIC PRESSURE (AT FAN INLET / AT FAN OUTLET) (VTA)
244 VELOCITY (AT SUCTION / AT DISCHARGE) (VTA)
245 REVOLUTIONS PER MINUTE (VTA)
246 ABSORBED POWER / INSTALLED POWER (VTA)
247 EFFICIENCY (VTA)
248 MODE OF OPERATION (VTA)
249 ROTATION (FACING N.D.E) (VTA)
250 DRIVER VTA
251 DUTY (VTA)
252 FAN TYPE CENTRIFUGAL (VTA)
(CARBON STEEL / CARBON STEEL /
253 MATERIALS (CASING / FRAME / FANS IMPELLER)
SS) (VTA)
254 FUEL GAS FILTER To be provided
THE BURNER ASSEMBLY SHALL HAVE DUAL FLAME FAILURE
255 Required
DETECTION AND DUAL FLAME BURNER FOR EACH FIRE TUBE
256 FLAME ARRESTOR FOR THE FIRE BOX AND THE FLUE STACK Required
BMS (BURNER MANAGEMENT SYSTEM) SHALL BE FURNISHED WITH
257 Required
LOCAL CONTROL PANEL (LCP)
258
259 TEG STILL COLUMN (TAG NO. TBA )
260 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
261 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
262 TYPE PACKED COLUMN
263 DESIGN DATA
264 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) VTA °F
265 PRESSURE (DESIGN / OPERATING) VTA psig
266 FLUID RICH TEG + HC (VTA)
267 TOTAL CAPACITY VTA gpm
268 VESSEL SIZE :
269 DIA (ID) VTA mm
270 LENGTH (T/T) VTA mm
271 VESSEL THICKNESS: mm
272 SHELL THK VTA mm
273 HEAD THK VTA
274 TYPE OF HEAD VTA
275 CORROSION ALLOWANCE 3 mm
276 SUPPORT TYPE FLANGE ON REBOILER
277 INSULATION INSULATION SUPPORT
278 PERSONAL PROTECTION No
279 FIREPROOFING No
280 INTERNALS SS 316L
281 CONSTRUCTION MATERIAL
282 Pressure plates SA-516 Gr. 70
283 Non-pressure plates SA 36 / SA 283 Gr. C
284 Skid / structure SA 36 / SA 283 Gr. C
285 Flanges SA-105
286 Nozzle neck / pipe SA 106 / API 5L Gr. B
287 Internals (Wet CO2) SS 316L
288 Internals (Others) SS 316L
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
SA 516 Gr. 70 (except attachment on
289 Internal and external attachments
the cladding surface)
SA 193 Gr. B7 & SA 194 Gr. 2H (hot dip
290 External bolts & nuts
galvanized)
291 ESTIMATED WEIGHTS
292 WEIGHT (REMOVABLE INTERNALS) VTA kg
293 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
REMOVABLE FIRE TUBES SIZED FOR THE MAXIMUM ALLOWABLE HEAT
294 Required
FLUX AS SPECIFIED IN THE API STANDARDS.
295 PACKED WITH 3/4 INCH S/S 316 PALL RING OR EQUAL PACKING Required
296
297 TEG REFLUX CONDENSER (TAG NO. TBA)
298 TYPE COIL TYPE (VTA)
299 FLUID CIRCULATED RICH TEG + VAPOR (VTA)
300 TOTAL CAPACITY VTA m³
301 REFLUX RATIO VTA %
302 DESIGN RATED OF DUTY (INCLUDING 10% MARGIN) VTA kW
303 OPERATING DUTY VTA kW
304 VESSEL
305 OUTSIDE DIAMETER (OD) VTA mm
306 LENGTH VTA mm
307 THICKNESS (SHELL / HEAD) VTA mm
308 SUPPORT TYPE FLANGE ON REBOILER
309 TYPE OF HEAD ELLIPTICAL 2:1
310 CORROSION ALLOWANCE (SHELL / HEAD / NOZZLES / COIL) 3 / 3 / 3 / 3+1
311 INSULATION No
312 PERSONAL PROTECTION No
313 FIREPROOFING No
314 MATERIAL OF CONSTRUCTION- SHELL VTA
315 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
316 CONDENSER COIL
317 SURFACE AREA / HEAT LOAD VTA mm² / kW
318 NO OF COILS / COIL DIA. / TUBE O.D VTA / mm / mm
319 TEMPERATURE IN / OUT VTA °C
320 PRESSURE (DESIGN /OP.) VTA barg
321 TEMPERATURE (DESIGN/OP.) VTA °C
322 MATERIAL OF CONSTRUCTION - COIL SS 316L
323 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
324
325 TEG SURGE DRUM (TAG NO. TBA)
326 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
327 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
HORIZONTAL, 3-PHASE SEPARATOR
328 TYPE
(VTA)
329 DESIGN DATA
330 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) VTA °F
331 PRESSURE (DESIGN / OPERATING) VTA psig
332 FLUID LEAN TEG (VTA)
333 TOTAL CAPACITY VTA gpm
334 VESSEL SIZE :
335 DIA (ID) VTA mm
336 LENGTH (T/T) VTA mm
337 VESSEL THICKNESS: mm
338 SHELL THK VTA mm
339 HEAD THK VTA
340 TYPE OF HEAD 2:1 ELLIPTICAL
341 CORROSION ALLOWANCE 3 mm
342 SUPPORT TYPE SADDLES
343 INSULATION No
344 PERSONAL PROTECTION Yes
345 FIREPROOFING No
SUPPORT GRID, INTERNAL PIPE,
346 INTERNALS STRUCTURED PACKING,
DISTRIBUTOR TRAY (VTA)
347 CONSTRUCTION MATERIAL
348 Pressure plates SA-516 Gr. 70
349 Non-pressure plates SA 36 / SA 283 Gr. C
350 Skid / structure SA 36 / SA 283 Gr. C
351 Flanges SA-105
352 Nozzle neck / pipe SA 106 / API 5L Gr. B
353 Internals (Wet CO2) SS 316L
354 Internals (Others) SS 316L
SA 516 Gr. 70 (except attachment on
355 Internal and external attachments
the cladding surface)
SA 193 Gr. B7 & SA 194 Gr. 2H (hot dip
356 External bolts & nuts
galvanized)
357 ESTIMATED WEIGHTS
358 WEIGHT (REMOVABLE INTERNALS) VTA kg
359 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
360
361 STRIPPING COLUMN (TAG NO. TBA )
362 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
363 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
VERTICAL, INTEGRAL TO THE
364 TYPE
ACCUMULATOR VESSEL (VTA)
365 DESIGN DATA
366 TEMPERATURE (DESIGN / OPERATING (NORMAL / MAX)) VTA °F
367 PRESSURE (DESIGN / OPERATING) VTA psig
368 FLUID RICH TEG (VTA)
369 TOTAL CAPACITY VTA gpm
370 VESSEL SIZE :
371 DIA (ID) VTA mm
372 LENGTH (T/T) VTA mm
373 VESSEL THICKNESS: mm
374 SHELL THK VTA mm
375 HEAD THK VTA
376 TYPE OF HEAD 2:1 ELLIPTICAL
377 CORROSION ALLOWANCE 3 mm
378 SUPPORT TYPE BRACKET / LEGS
379 INSULATION Yes
380 PERSONAL PROTECTION Yes
381 FIREPROOFING No
SUPPORT GRID, INTERNAL PIPE,
382 INTERNALS STRUCTURED PACKING,
DISTRIBUTOR TRAY (VTA)
383 CONSTRUCTION MATERIAL
384 Pressure plates SA-516 Gr. 70
385 Non-pressure plates SA 36 / SA 283 Gr. C
386 Skid / structure SA 36 / SA 283 Gr. C
387 Flanges SA-105
388 Nozzle neck / pipe SA 106 / API 5L Gr. B
389 Internals (Wet CO2) SS 316L
390 Internals (Others) SS 316L
SA 516 Gr. 70 (except attachment on
391 Internal and external attachments
the cladding surface)
SA 193 Gr. B7 & SA 194 Gr. 2H (hot dip
392 External bolts & nuts
galvanized)
393 ESTIMATED WEIGHTS
394 WEIGHT (REMOVABLE INTERNALS) VTA kg
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
395 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
396 PACKED WITH RASCHIG RING OR EQUAL PACKING Required
397 EXPANDED METAL PERSONNEL PROTECTION Required
398
399 LEAN / RICH GLYCOL HEAT EXCHANGER (TAG NO. TBA)
SHELL & TUBE / DOUBLE PIPE / OR
400 TYPE
WELDED TYPE PLATE (VTA)
401 DUTY VTA MBTU/hr
402 PRESSURE DROP VTA bar
RICH (TUBE SIDE): (VTA), LEAN
403 PRESSURE (DESIGN /OP.) barg
(SHELL SIDE): (VTA)
404 TEMPERATURE (DESIGN) VTA °C
405 PROCESS OP. TEMPERATURE ( INLET/OUTLET) VTA °C
406 SERVICE OP. TEMPERATURE ( INLET/OUTLET) VTA °C
407 CORROSION ALLOWANCE 3 mm
408 MATERIAL OF CONSTRUCTION (PLATE / FRAME) SA 240 TP 316L / SA 516 GR.70 (VTA)
409 PANEL GASKET MATERIAL VTA
410 SIZE ( L X W X H ) VTA mm
411 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
412
413 TEG CIRCULATION PUMPS (TAG NO. TBA )
414 APPLICABLE CODE API 674
POSITIVE DISPLACEMENT PUMP / 2
415 TYPE / QUANTITY
X 100 % (1 DUTY 1 STANDBY)
416 FLUID HANDLED GLYCOL (VTA)
417 OPERATING CAPACITY VTA m³ / hr
418 RATED DESIGN CAPACITY (INCLUDING 25% MARGIN) VTA m³ / hr
419 SUCTION PRESSURE VTA barg
420 DISCHARGE PRESSURE VTA barg
421 DESIGN TEMPERATURE VTA °C
422 RPM VTA rpm
423 POWER VTA kW
424 NPSHR VTA m
425 VOLT / PHASE / CYCLES 400 V, 3 Ph, 50 Hz (VTA)
426 CONNECTION:
427 SUCTION (SIZE / RATING / FACING) VTA
428 DISCHARGE (SIZE / RATING / FACING) VTA
429 AUXILIARY EQUIPMENT
430 BASE PLATE YES (VTA)
431 PULSATION DAMPER RESID. PULSATION YES (VTA)
432 BELT TYPE V-BELT (VTA)
433 Y-TYPE SUCTION STRAINERS. Required
COMMON BY-PASS LINE WITH GLOBE VALVE TO ACCUMULATOR TO
434 Required
ALLOW FLOW CONTROL
A 216 GR WCB / A 182 GR F 316L
435 MATERIAL OF CONSTRUCTION - CASING / WETTED PARTS
(VTA)
436 SIZE (L x W x H)) VTA mm
437 PUMP WEIGHT VTA kg
438 DRIVER WEIGHT VTA kg
439 TOTAL WEIGHT VTA kg
440
441 TEG CATRIDGE FILTERS (TAG NO. TBA )
442 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
443 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
444 TYPE / QTY (VTA) / 2 X 100 % CARTRIDGE TYPE
445 FLUID HANDLED RICH TEG (VTA)
446 TOTAL CAPACITY VTA m³
447 DESIGN FLOW RATE VTA USGPM
448 DIFFERENTIAL PRESSURE (CLEAN / DIRTY) VTA bar
449 FILTRATION AREA VTA mm²/ mm³
99% OF PARTICLES 5 MICRONS AND
450 FILTRATION EFFICIENCY
LARGER
451 PRESSURE (DESIGN /OP.) VTA barg
452 TEMPERATURE (DESIGN/OP.) VTA °C
453 INSIDE DIAMETER (ID) VTA mm
454 LENGTH VTA mm
455 THICKNESS (SHELL / HEAD) VTA mm
456 SUPPORT TYPE LEGS
457 TYPE OF HEAD ELLIPTICAL 2:1 (BOTTOM)
458 CORROSION ALLOWANCE (SHELL / HEAD / NOZZLES) 3 mm
459 INSULATION NO
460 PERSONAL PROTECTION NO
461 FIREPROOFING NO
CATRIDGES, PALL CARTRIDGE
462 INTERNALS
FILTERS OR EQUAL. (VTA)
463 MATERIAL OF CONSTRUCTION SA 516 GR. 70 (VTA)
464 MATERIAL OF REMOVABLE INTERNALS SS 316L (VTA)
465 WEIGHT (REMOVABLE INTERNALS) VTA kg
466 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
467 SPARE FILTER ELEMENTS FOR TWENTY CHANGE-OUTS. Required
QUICK OPENING TYPE (SWING BOLT OR CLAMP) AND ACCESS
468 Required
PLATFORM TO FACILITATE FILTER REPLACEMENT.
469
470 TEG CARBON FILTER (TAG NO. TBA )
471 DESIGN CODE ASME Sec VIII Div. 1 Latest Ed.
472 DESIGN SPECIFICATION 20-01-BRGA-MEC-SPE-0002
473 TYPE / QTY GRANULATED CHARCOAL BED / 1
474 FLUID HANDLED RICH GLYCOL (VTA)
475 TOTAL CAPACITY VTA m³
476 DESIGN FLOW RATE VTA USGPM
477 DIFFERENTIAL PRESSURE (CLEAN / DIRTY) VTA bar
478 FILTER SIZE 10 MESH GRANULATED CHARCOAL
479 CHARCOAL VOLUME VTA mm³
480 PRESSURE (DESIGN /OP.) VTA barg
481 TEMPERATURE (DESIGN/OP.) VTA °C
482 INSIDE DIAMETER (ID) VTA mm
483 LENGTH VTA mm
484 THICKNESS (SHELL / HEAD) VTA mm
485 SUPPORT TYPE LEGS
486 TYPE OF HEAD ELLIPTICAL 2:1 (BOTTOM)
487 CORROSION ALLOWANCE (SHELL / HEAD / NOZZLES) 3 mm
488 INSULATION NO
489 PERSONAL PROTECTION YES
490 FIREPROOFING NO
ACTIVATED CARBON FILTER
491 INTERNALS
ELEMENT (VTA)
492 MATERIAL OF CONSTRUCTION SA 516 GR. 70 (VTA)
493 MATERIAL OF REMOVABLE INTERNALS SS 316L (VTA)
494 WEIGHT (REMOVABLE INTERNALS) VTA kg
495 WEIGHT (EMPTY, OPERATING, FULL OF WATER) VTA kg
DIFFERENTIAL PRESSURE GAUGE (C/W REMOTE MONITORING
496 DEVICE) AND SHALL HAVE INLET ISOLATION, OUTLET ISOLATION AND Required
BYPASS VALVE.
SUPPORT GRID SHALL HAVE A MINIMUM OF TWO LAYERS OF 20 MESH
497 Required
STAINLESS STEEL SCREEN.
498 QUICK OPENING TYPE (SWING BOLT OR CLAMP). Required
499
TEG SUMP DRUM AND PUMP (DRUM TAG NO. BRA-D-3003 & PUMP TAG
500
NO. BRA-P-3002 )
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
501 FLUID LEAN TEG (VTA)
502 PUMP
503 TYPE / QTY PNEUMATIC / 1
504 CAPACITY (NORMAL / MINIMUM / MAXIMUM / DESIGN) VTA LPH
505 SUCTION PRESSURE VTA barg
506 DISCHARGE PRESSURE VTA barg
507 DESIGN TEMPERATURE VTA °C
508 POWER AIR OPERATED
509 CONNECTION:
510 SUCTION (SIZE / RATING / FACING) VTA
511 DISCHARGE (SIZE / RATING / FACING) VTA
512 AUXILIARY EQUIPMENT
513 BASE PLATE YES (VTA)
514 PULSATION DAMPER RESID. PULSATION, IF APPLICABLE (VTA)
515 MATERIAL OF CONSTRUCTION - CASING / WETTED PARTS VTA
516 SIZE (L x W x H)) VTA mm
517 PUMP WEIGHT VTA kg
518 DRIVER WEIGHT VTA kg
519 TOTAL WEIGHT VTA kg
520 TANK
521 DIMENSION (W x L x H OR ID x H) VTA mm
522 TANK VOLUME VTA mm³
523 TANK WEIGHT VTA kg
524 MATERIAL OF CONSTRUCTION VTA
525
TEG STORAGE / MAKE UP TANK AND PUMP (TANK TAG NO. TBA &
526
PUMP TAG NO. TBA )
527 FLUID LEAN TEG (VTA)
528 PUMP
529 TYPE / QTY PNEUMATIC / 1
530 CAPACITY (NORMAL / MINIMUM / MAXIMUM / DESIGN) VTA LPH
531 SUCTION PRESSURE VTA barg
532 DISCHARGE PRESSURE VTA barg
533 DESIGN TEMPERATURE VTA °C
534 POWER AIR OPERATED
535 CONNECTION:
536 SUCTION (SIZE / RATING / FACING) VTA
537 DISCHARGE (SIZE / RATING / FACING) VTA
538 AUXILIARY EQUIPMENT
539 BASE PLATE YES (VTA)
540 PULSATION DAMPER RESID. PULSATION, IF APPLICABLE (VTA)
541 MATERIAL OF CONSTRUCTION - CASING / WETTED PARTS VTA
542 SIZE (L x W x H)) VTA mm
543 PUMP WEIGHT VTA kg
544 DRIVER WEIGHT VTA kg
545 TOTAL WEIGHT VTA kg
546 TANK
547 DIMENSION (W x L x H OR ID x H) VTA mm
548 TANK VOLUME VTA mm³
549 TANK WEIGHT VTA kg
550 MATERIAL OF CONSTRUCTION VTA
551
4 INSTRUMENTATION
1 UNIT CONTROL PANEL
2 TYPE PLC
3 QTY 1 (ONE) UNIT CONTROL PANEL
4 MANUFACTURER AS PER PML
5 LOCATION ON SKID / PANEL SHELTER
6 SEQUENTIAL PANEL REQUIRED YES
IP 65 (OUTDOOR) RATED AS
MINIMUM) / EXPLOSION PROOF &
7 IP RATING & ENCLOSURE SUITABLE FOR AREA
CLASSIFICATION: ZONE 2, GAS
GROUP IIA, TEMP. CLASS T3.
8 COMMUNICATION TYPE DHT; Ethernet
9 OPERATOR WORK STATION (OWS) DESKTOP PC Required
10 LAPTOP COMPLETE WITH ALL SOFTWARES Required
All instruments and electrical cable in the dehydration system shall be armored
11 Required
type and complete with SS 316 cable tray.

5 OTHERS
CERTIFIED LIFTING TOOLS OR HANDLING DEVICES AND
1 Required
RECOMMENDED SPECIAL TOOLS
All metalic material shall be provided with inspection certificates in accordance
2 with EN 10204, 2004 edition. Pressure parts type 3.1 certification and non- Required
pressure parts type 2.2 certification
All NDE include radiography (before and after PWHT, if any) shall be
3 Required
conducted in accordance with
CLASS 1, ZONE 2, GAS GROUP IIA,
4 AREA CLASSIFICATION
TEMP. CLASS T3
5 HEATER CONTROL PANEL (C/W ANTI CONDENSATION HEATER) Required
6 LIFTING LUGS Required
7 PLATFORM / LADDERS Required
8 WIRING AND CABLE TRAYS WITHIN THE SKID Required
9 SKID EDGE JUNCTION BOXES Required
10 SKID INTERFACE PIPING TERMINATION WITH ASME B 16.5 FLANGES
11 REGENERATION SKID WEIGHT (ERECTED/OPERATED) VTA kg
12 REGENERATION SKID SIZE ( L X W X H ) VTA kg

6 DESIGN CODES / STANDARDS


1 PRESSURE VESSELS/FILTERS / HEAT EXCHANGERS ASME VIII DIV.1 WITH CODE STAMPED + MIGAS
2 PLATE HEAT EXCHANGERS API-662 (VTA)
3 SHELL & TUBE HEAT EXCHANGER API-660 + TEMA (VTA)
4 GLYCOL CIRCULATION PUMP API-674
5 FLANGES ASME B 16.5
6 PIPING (INSIDE SKID) ASME B 31.3

5 SCOPE OF WORK - INSPECTION AND TESTING REQUIREMENTS


1 Design Engineering Required
2 Manual for QA / QC, FAT, SAT procedures Required
3 Factory Acceptance Test (FAT) Required
4 Integration Factory Acceptance Test (IFAT) Required
5 Packing & preparation for shipment Required
6 Start-up Commisionning Engineering Phase Required
7 Mobilize personel for construction, pre-commisionning and commisionning to sit Required
8 Site System Integration Test (SSIT) Required
9 Site Acceptance Test (SAT) Required
10 Inspection test plan for the manufacturing and assembly Required
11 Witness of wet test by MIGAS, including specification Required
12 Training and socialization for Operator (2 batches) Required

TECHNICAL EVALUATION SUMMARY ACCEPTABLE NOT ACCEPTABLE


1 1 1
2 2 2
REMARK
Document No.: 20-01-BRGA-MEC-TBE-0005

EPC PEMBANGUNAN STASIUN PENGUMPUL GAS 15


MMSCFD
BERINGIN A
ASSET 2 FIELD PRABUMULIH REVISION PREPARED CHECKED APPROVED CHECKED APPROVED
A DPO/DAW API THP YHN ES

TECHNICAL BID EVALUATION FOR MAIN POWER GENERATOR (BRA-GEG-5001 A/B)


PT ELNUSA TBK PT. PERTAMINA EP
BIDDERS
NO. REQUIREMENT QUANTITY UNIT
BIDDER -1 RESULT REMARK BIDDER -2 RESULT REMARK BIDDER-3 RESULT REMARK
REMARK 3 3 3

NOTE :
VTA : Vendor to Adivce
C : Comply
NC : Not Comply
AA : Alternative and Acceptable
NS : Not Specified
I : Information
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page Attachment 1

Attachment 1
Deviation List
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page Attachment

Deviation List

We are PT. ………………………………………………..., hereby declare:

We confirm complete compliance of this requisition and all applicable documents.

We take the following exceptions and deviations to this requisition and all applicable
documents refer to below table.
Please thick one of above box.

Deviation List

Reference Original Bidder's CTR's CPY's


No Deviation
Documents Requirement Justification Assessment Repsonse

Jakarta, …………………………2020

Note:
1. This page can be duplicated and extended. Each single page shall be signed by authorized
personnel of this bidding and stamped.
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page Attachment 2

Attachment 2
Bidders Un-Priced Quotation
MECHANICAL

Rev A
Document Title:
Document No.:
TBE FOR MAIN POWER Date 22-Jun-20
20-01-BRGA-MEC-TBE-0005
GENERATOR (BRA-GEG-5001 A/B)
Page Attachment 3

Attachment 3
Email Correspondences /
Clarifications (if any)