SIEMENS Rapid MetroRail Gurgoan

Doc no. TTD0200000560 Rev-A


CABLE NUMBERING & DESIGNATION FOR RMGL PROJECT

Cable numbering and designation was made by 5 checker columns as mentioned below :

C1 C2 C3 C4 C5

Station Number Voltage level Designation FROM Designation TO Sr.No of Cables


+1ST0X X AA AA XX

A - Alphabetical reference
X - Numerical reference
+1ST0 - Constant (station code)

Hence the overall cable numbering & designation is categorized into 8 digits alpha numeric code.

Column 1 (C1) : STATION NUMBER

Station Name Station No


Sikanderpur +1ST01
DLF Phase 2 +1ST02
Belvedere Tower +1ST03
Gateway Tower +1ST04
Mall of India +1ST05
DLF Phase 3 +1ST06
Depot +1ST07
Receiving substation1 +RSS01
Receiving substation2 +RSS02
Trackside loop +TSLP

Column 2 (C2) : VOLTAGE LEVEL

Voltage Levels Designation


750V DC Positive Feeder cables 1
DC Negative Return cables 2
11KV(AC) 3
1.1KV (AC) power cables 4
Control cables (DC) 5
Control cables (AC) 6
Fibre Optic cables 7
Earthing cables 8
BLS cables 9

Column 3 & 4 (C3 & C4) : Designation From and Designation To

Equipment Designation
DC SwitchGear Panels MC
AC SwitchGear Panels KO
Control & Protection Panels JA
Rectifier MG
Metering Panels ME
Return Line Panels MD
Short Circuit Device Panels MF
Stinger Panels MQ
Line Section (Third Rail) LS
Station Control Panels UW
LT Side Panels LT
Remote Terminal Unit RT
Station Control Room SR
Auxiliary/Station Transformer TA
Rectifier Transformer TR
AC Distribution Board NA
DC Distribution Board ND
Battery Charger NN
Battery Bank NL
UPS(ControlSystem) NU
Emergency Trip Box ET
Platform&Station Blue Light Station BL
Running Rail RR
Structure Earthing MS
Miscellaneous AA

Column 5 (C5) : Sr.No of CABLES

Numeric Cable Numbers Designation


Sr.No of Cables 00-99

1of1