SineWaveTM
20 - 480 A
Autotransformer
for 208 volt
mains
Installation manual
e
Wav
Sine
D E R
O V I
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
T E
I N
U N
T H E
51027358EN/AD - Page 1
To the user
We would like to thank you for choosing the SineWave™ active harmonics conditioner and welcome you to the ever increasing
world-wide family of satisfied MGE UPS SYSTEMS product users.
This manual has been written to provide you with all the information necessary to install and operate your SineWave™ active
conditioner.
We remain at your entire disposal should you require any further details.
Danger
Hazardous voltages are ◗ do not obstruct the air vents;
present inside the
autotransformer. ◗do not place the autotransformer in
Work on this equipment direct sunlight or near sources of
should only be carried out heat;
by qualified personnel. ◗if the autotransformer is to be
◗the autotransformer must be stored before use, it must be kept in
earthed; a dry, dust-free location.
Pictograms
Page 2 - 51027358EN/AD
Contents
Presentation ........................................................................................................ 4
Installation of the SineWave™ active harmonics conditioner, its autotransformer for a 208 volt mains,
checking of its operation and certain repairs should only be carried out by qualified personnel trained to deal
with electrical hazards.
Other operations may be carried out by any other persons with the help of this manual.
All SineWave™ range products are protected by patents; they implement original technology which cannot
be used by any competitor of MGE UPS SYSTEMS.
Copies of this document- may be made with the approval of MGE UPS SYSTEMS and must bear the title:
"MGE UPS SYSTEMS SineWave™ autotransformer for 208 volt mains installation manual n° 51027403XT".
51027358EN/AD - Page 3
Autotransformer for 208 volt mains
installation manual
Presentation
This document is complementary to the
SineWave™ installation and operation
manual. It provides additional
information required for the installation
and connection of the autotransformer
for adaptation to a 208 volt mains.
Typical diagram
The autotransformer must be Case of a single 20, 30, 45 or 60 A SineWave™ conditioner unit
connected between the mains and the
SineWave™ active harmonics
low voltage distribution
conditioner. switchboard
harmonic
autotransformer compensating SineWave™
208 V 400 V fuses active
currents
harmonics
conditioner
harmonic
fuses compensating
currents
Page 4 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
◗ each power circuit remains Case of a two 20, 30, 45 or 60 A SineWave™ conditioner units in parallel
independent and has is own protective
device (not supplied);
low voltage distribution
◗ it is possible to connect up to 4 switchboard
conditioners in parallel to compensate a
given load or group of loads.
208 V mains
supply current
sensor harmonic current
circuit breaker to be compensated
load to be
compensated
harmonic
autotransformer compensating SineWave™
208 V 400 V fuses current active
harmonics
conditioner
harmonic
autotransformer compensating
208 V 400 V fuses current SineWave™
active
harmonics
conditioner
208 V mains
supply current
sensor
harmonic current
circuit breaker to be compensated
load to be
compensated
autotransformer SineWave™
compensateur
208 V 400 V fuses active
actif
harmonics
d'harmoniques
conditioner
SineWave™
fuses
harmonic
autotransformer compensating SineWave™
208 V 400 V fuses current active
harmonics
conditioner
harmonic
compensating
fuses current
51027358EN/AD - Page 5
Autotransformer for 208 volt mains
installation manual (continued)
4 mounting
holes ØD
E1 E2
L I
Power connections
Terminal block Top view of autotransformer terminal block
Key:
autotransformer primary and secondary
a-b-c : secondary 400 V
a connections:
A3-B3-C3 : primary 208 V
A2-B2-C2 : primary 220 V A1 Rating A-B-C a-b-c
A1-B1-C1 : primary 240 V A2 20 - 30 A M6 terminals
45 - 60 A AI 15x3 ø7 terminals
A3
90 - 120 A AI 20x5 ø9 terminals
b
B1
connection of the exposed conductive
B2
parts and the neutral common to the
B3 primary and secondary:
c
Rating N Exposed
C1 conductive
parts
C2
20 - 30A M6 terminals M6 terminals
C3 45 - 60 A AI terminals M8 terminals
N 15x3 ø7
90 - 120 A AI terminals M10 terminals
20x5 ø 9
Page 6 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
51027358EN/AD - Page 7
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 20 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
IT system IT system
32 A UR 208 V A3 50 A 25 A a 32 A UR
208 V A3 50 A 25 A a 1 1
B3 b B3 b 2
2
C3 c C3 c
3 3
N 25 A 135 A 65 A N
N
N
TT system TT system
208 V A3 50 A 25 A a 32 A UR 208 V A3 50 A 25 A a 32 A UR
1 1
B3 b 2 B3 b 2
C3 c C3 c
3 3
N 25 A 135 A 65 A N
N
N
TNC system
208 V A3 50 A 25 A a 32 A UR
1
B3 b 2
C3 c
3
N
PEN 135 A N 65 A
208V / 400V
C60 3x50 A curve D
autotransformer
TNS system
208 V A3 50 A 25 A a 32 A UR
1
B3 b 2
C3 c
3
135 A 65 A N
N PE
Page 8 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 30 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
IT system IT system
208 V A3 75 A 35 A a 40 A UR 40 A UR
1 208 V A3 75 A 35 A a 1
B3 b 2 B3 b 2
C3 c C3 c
3 3
N 35 A 220 A 100 A N
N
N
TT system TT system
208 V A3 75 A 35 A a 40 A UR 208 V A3 75 A 35 A a 40 A UR
1 1
B3 b B3 b 2
2
C3 c C3 c
3 3
N 35 A 220 A 100 A N
N
N
TNC system
208 V A3 75 A 35 A a 40 A UR
1
B3 b 2
C3 c
3
N
PEN 220 A N 100 A
208V / 400V
NC100H 3x80 A curve D
autotransformer
TNS system
208 V A3 75 A 35 A a 40 A UR
1
B3 b 2
C3 c
3
220 A 100 A N
N PE
51027358EN/AD - Page 9
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 45 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
IT system IT system
208 V A3 105 A 50 A a 63 A UR 208 V A3 105 A 50 A a 63 A UR
1 1
B3 b 2 B3 b 2
C3 c C3 c
3 3
N 50 A 310 A 150 A N
N
N
TT system TT system
208 V A3 105 A 50 A a 63 A UR 208 V A3 105 A 50 A a 63 A UR
1 1
B3 b 2 B3 b 2
C3 c C3 c
3 3
N 50 A 310 A 150 A N
N
N
TNC system
208 V A3 105 A 50 A a 63 A UR
1
B3 b 2
C3 c
3
N
PEN 310 A N 150 A
208V / 400V
autotransformer NC100H 3x100 A curve D
TNS system
208 V A3 105 A 50 A a 63 A UR
1
B3 b 2
C3 c
3
310 A 150 A N
N PE
Page 10 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 60 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
IT system IT system
208 V A3 135 A 65 A a 80 A UR 208 V A3 135 A 65 A a 80 A UR
1 1
B3 b B3 b 2
2
C3 c C3 c
3 3
N 65 A 400 A 200 A N
N
N
TT system TT system
80 A UR 208 V A3 135 A 65 A a 80 A UR
208 V A3 135 A 65 A a 1 1
B3 b B3 b 2
2
C3 c C3 c
3 3
N 65 A 400 A 200 A N
N
N
TNC system
208 V A3 135 A 65 A a 80 A UR
1
B3 b 2
C3 c
3
N
PEN 400 A N 200 A
208V / 400V
autotransformer NS160 STR22ME 150 A 3p3d
TNS system
208 V A3 135 A 65 A a 80 A UR
1
B3 b 2
C3 c
3
400 A 200 A N
N PE
51027358EN/AD - Page 11
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 90 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
Non-distributed neutral
IT system
63 A UR
208 V A3 205 A 100 A a 50 A 1
B3 b 2
C3 c
3
100 A N 50 A N
63 A UR
50 A 1
2
3
50 A N
TT system
63 A UR
208 V A3 205 A 100 A a 50 A 1
B3 b 2
C3 c 3
100 A N 50 A N
63 A UR
208V / 400V 50 A 1
autotransformer 2
3
50 A N
Page 12 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
Distributed neutral
63 A UR
63 A UR
50 A 1 50 A 1
2 2
3 3
150 A N N
150 A
N N PE
63 A UR
63 A UR
50 A 1 50 A 1
2 2
3 3
150 A N 150 A N
PE
51027358EN/AD - Page 13
Autotransformer for 208 volt mains
installation manual (continued)
SineWave™ 120 A
Recommended protective devices connection to SineWave™
terminal block where Pcu = function of Isc
Non-distributed neutral
IT system
80 A UR
208 V A3 265 A 130 A a 65 A 1
B3 b 2
C3 c 3
130 A N 65 A N
80 A UR
65 A 1
2
3
65 A N
TT system
80 A UR
208 V A3 265 A 130 A a 65 A 1
B3 b 2
C3 c 3
130 A N 65 A N
208V / 400V 80 A UR
65 A 1
autotransformer
2
3
65 A N
Page 14 - 51027358EN/AD
Autotransformer for 208 volt mains
installation manual (continued)
Distributed neutral
80 A UR 80 A UR
65 A 1 65 A 1
2 2
3 3
200 A N N
200 A
80 A UR 80 A UR
65 A 1 65 A 1
2 2
3 3
200 A N 200 A N
PE
51027358EN/AD - Page 15
Autotransformer for 208 volt mains
installation manual (continued)
Connection procedure
Connection operations must Procedure :
be carried out with the ◗ make sure that the circuit breaker on To avoid interference, control
equipment de-energised. the circuit supplying the SineWave™ wires connected to the
For the protection of unit is in the "off" position ( O ); SineWave™ unit (connections
persons, always connect the ◗ connect the PE or PEN conductor with current sensors,
PE or PEN conductor first. first; communications cables, relay contact
◗ connect the other conductors, taking wiring) should never be run near the
Earthing arrangement: SineWave™ is care to respect the phase rotation power cables or the autotransformer.
suitable for all types of earthing direction. For the same reason, the power cables
arrangements. connected to the outputs of the
SineWave™ conditioner or the
The connecting cables must autotransformer should not be run near
be mechanically secured other power cables.
near the terminal block to
prevent any mechanical
forces from being exerted on
the connections .
Autotransformer characteristics
Unless otherwise stipulated, the Input ◗ nominal voltage ◗ 208V -20% +15%
performance data given in the table ◗ nominal frequency ◗ 50Hz, 60HZ ± 5%
below are typical values corresponding
◗ number of phases ◗ 3 phases with or without neutral
to use under a nominal 3-phase 50 Hz
mains voltage of 208 volts and rated Technical ◗ inrush current ◗ < 10 times the rated peak current
current. characteristics ◗ losses ◗ < 510W for ratings 20A to 30A
◗ < 1000W for ratings 45A to 60A
◗ < 1250W for ratings 90A to 120A
◗ ventilation ◗ natural convection
Environmental ◗ ambient temperature ◗ < 25°C recommended
conditions ◗ 0 à 40°C permanently
◗ relative humidity ◗ 0 to 95 % relative humidity
without condensation
◗ operating altitude ◗ < 1000 m
Dimensions ◗ height ◗ 370 mm - 20A, 30A
and weight ◗ 415 mm - 45A, 60A
◗ 590 mm - 90A, 120A
◗ length ◗ 360 mm - 20A, 30A
◗ 420 mm - 45A, 60A
◗ 590 mm - 90A, 120A
◗ width ◗ 200 mm - 20A, 30A
◗ 220 mm - 45A, 60A
◗ 560 mm - 90A, 120A
◗ weight ◗ 70 Kg - 20A, 30A
◗ 115 Kg - 45A, 60A
◗ 195 Kg - 90A, 120A
Page 16 - 51027358EN/AD