Professional Documents
Culture Documents
INTRODUCTION
This application guide describes the procedure to set directional overcurrent elements in SEL-351
series relays. Other SEL relays use similar settings for directional and torque control.
The SEL-351 Protection System includes multiple directional elements. Different types of faults
require different directional elements. A positive-sequence directional element is used for three-
phase faults, a negative-sequence directional element is used for phase-to-phase faults, and the
Best Choice Ground Directional Element® logic is used for ground faults. The Best Choice
Ground Directional Element uses one of three independent directional elements: negative-
sequence impedance, zero-sequence impedance, or zero-sequence current polarized. The
SEL-351 may be ordered with other ground directional elements, including the following, for
certain applications.
• Zero-sequence voltage-polarized directional element (low-impedance grounded system).
• Wattmetric and incremental conductance directional elements (Petersen coil-grounded
system).
• Zero-sequence voltage-polarized directional element (ungrounded and high-impedance
grounded system).
However, these optional elements are not discussed in this application guide. All directional
elements are enabled by the E32 setting in the relay. Refer to the device instruction manual for
information on these directional elements.
DIRECTIONAL CONTROL
Overview
There are two methods that may be used to add directional control to an overcurrent element.
A typical control logic diagram for the instantaneous overcurrent elements (50Pn, 50Gn, 50Nn,
and 50Qn) is shown in Figure 1.
Relay
Word Relay
Bit Word
50P1 Bits
67P1
67P1D
DIR1 Directional Control
67P1T
(Level 1) (asserted to logical 1 0
continuously if E32 = N)
SELOGIC®
Setting SELOGIC
Torque Control
67P1TC
Figure 2 shows the logic diagram for a typical inverse-time overcurrent element (51Pn, 51Gn,
51Nn, and 51Qn).
Relay
Word
Bits
51P1 Pickup
DIRn controls the n level of instantaneous and definite-time overcurrent elements (67). In
addition, the DIR1 setting also adds directional control to the inverse-time overcurrent elements
(51).
Each of the DIR settings can be set to:
• N (elements are nondirectional).
• F (elements are directionally controlled in the forward direction).
• R (elements are directionally controlled in the reverse direction).
When one of the communications-assisted tripping schemes is used, the Level 2 elements must be
set to be directionally controlled in the forward direction and the Level 3 elements must be set to
be directionally controlled in the reverse direction.
RWBs are available for the individual forward and reverse directional elements included in the
SEL-351. The directional element RWBs shown in Table 2 and Table 3 can be used in the torque
control equations to customize the application of directional control.
Table 2 and Table 3 provide a list of the RWBs for the most commonly used directional elements.
The ORDER setting determines the Best Choice Ground Directional Element selection. The
ORDER setting is a combination of the Q, V, I, S, P, and U directional elements. This application
guide is limited to Q, V, and I. For most applications, the RWBs of Table 2 are used. RWBs
32GF and 32GR are used to control ground and neutral overcurrent (OC) elements. RWBs 32PF
and 32PR are used to control phase and negative-sequence overcurrent elements.
APPLICATION EXAMPLES
Example 1
The following overcurrent elements are used in this example:
• Three levels of phase instantaneous.
• Three levels of residual ground instantaneous.
• One level of neutral ground instantaneous.
• One level of -phase time-overcurrent.
Note that SEL-351 series relays include two types of ground overcurrent elements. Residual
ground overcurrent elements (50G, 51G) operate from the residual (3I0) current calculated from
the three phase currents. Neutral ground overcurrent elements (50N, 51N) operate on the single-
phase current connected to the neutral current transformer (CT) inputs of the relay.
The following directional control is desired:
• All Level 1 elements forward.
• All Level 2 elements forward.
• All Level 3 elements reverse.
As shown in Figure 1, the 50 elements are not directionally controlled in the SEL-351. The
50 elements are used to create the directionally controlled 67 elements. Therefore, the actual
overcurrent RWBs used in this example are:
• Level 1: 67P1, 67G1, 67N1, 51P1T.
• Level 2: 67P2, 67G2.
• Level 3: 67P3, 67G3.
In this example, the simplest method to directionally control the overcurrent elements is to use the
DIRn settings. To accomplish the desired control, apply the following settings:
DIR1 = F
DIR2 = F
DIR3 = R
The SELOGIC control equation for tripping is:
TR = 67P1 + 67G1 + 67N1 + 67P2 + 67G2 + 67P3 + 67G3 + 51P1T
No time delay is specified for the 67 elements. If time delay is required, the appropriate definite-
time overcurrent RWB should be used (67P1T, 67G1T, and so on).
The default torque control equations for these overcurrent elements are:
67P1TC = SH0
67P2TC = 1
67P3TC = 1
67N1TC = 1
67G1TC = 1
67G2TC = 1
67G3TC = 1
51P1TC = 1
All torque control equations are set equal to logical 1 except 67P1TC. RWB SH0 indicates that
the built-in recloser logic has not issued an automatic reclose signal. When an automatic reclose
signal is initiated, the shot counter advances. At the first reclose, RWB SH0 deasserts, causing
67P1TC to deassert. The 67P1 overcurrent element will be blocked. Thus, the 67P1TC setting
disables the 67P1 element during an automatic reclose cycle. If the 67P1 element should always
be in service and in the forward direction, set 67P1TC = 1.
Example 2
The following overcurrent elements are used in this example:
• Three levels of phase instantaneous elements.
• Three levels of residual instantaneous elements.
• One level of neutral instantaneous elements.
• One level of inverse-phase time overcurrent elements.
The following directional control is desired:
• Phase and residual ground Level 1 elements should be nondirectional.
• Neutral ground and phase time-overcurrent elements should be forward.
• Phase and residual ground Level 2 elements should be forward.
• Phase Level 3 instantaneous elements should be forward.
• Residual ground Level 3 instantaneous elements should be reverse.
As shown in Figure 1, the 50 elements are not directionally controlled in the SEL-351. The
50 elements are used to create the directionally controlled 67 elements. Therefore, the overcurrent
RWBs for the directionally controlled overcurrent elements used in this application are:
• Level 1: 67N1, 51P1T.
• Level 2: 67P2, 67G2.
• Level 3: 67P3, 67G3.
For the nondirectional overcurrent elements, the following RWBs can be used:
• 50P1.
• 50G1.
No time delay is specified for the 67 elements. If time delay is required, the appropriate definite-
time overcurrent element RWB should be used (67N1T, 67P2T, and so on).
Several approaches can be used to obtain the desired directional control. One such approach is as
follows. Set:
DIR1 = F
DIR2 = F
DIR3 = N
67P3TC = 32PF
67G3TC = 32GR
Setting DIR1 = F directionally controls all Level 1 overcurrent elements in the forward direction.
However, as shown in Figure 1, while the 67P1 and 67G1 elements are directionally controlled,
the 50P1 and 50G1 elements are nondirectional. Thus, the 50P1 and 50G1 elements can still be
used to provide nondirectional tripping when DIR1 = F or DIR1 = R.
Because one of the Level 3 overcurrent elements is required to be forward and the other reverse,
the DIR3 setting must be set to N (nondirectional) and the torque control equations must be used
to provide the desired directional control.
Example 3
The torque control equations are not limited to directional control. Many different types of logic
can be used to provide control of the overcurrent elements. Consider the default settings in the
SEL-351S. Pushbutton 1 (PB1) is used to enable and disable ground protection. This is
accomplished with several SELOGIC control equations, as follows:
SET4 = !LT4*PB5
RST4 = LT4*PB5
SET1 = !LT1*PB1*LT4
RST1 = LT1*PB1*LT4
51G1TC = LT1
PB5 is used to lock PB1 to prevent an accidental change in the ground enable status. The SET4
and RST4 logic equations control Latch Bit 4 (LT4). LT4 toggles the lock on and off each time
PB5 is pressed. When Latch Bit LT4 is asserted (lock off), PB1 toggles Latch Bit LT1 on and off.
When LT1 is asserted, 51G1TC is a logical 1 and the 51G1 element can time out. When LT1 is
deasserted, 51G1TC is a logical 0 and the 51G1 element is prevented from asserting and timing
out.
CONCLUSION
Directional control of the SEL-351 overcurrent elements may be accomplished using two
methods:
• DIR1 through DIR4 settings provide a simple means to directionally control groups of
overcurrent elements with a single setting.
• Torque control equations provide a means to customize the directional control for each
overcurrent element.
Choose the method best suited for the particular application. See the SEL-351 Instruction Manual
section “Directional Control Provided by Torque Control Settings” for additional information.
Detailed information on the design, operation, and setting of the various directional elements in
SEL-351 series relays is available in the device instruction manuals and in a number of SEL
technical papers, which can be downloaded at https://www.selinc.com.
FACTORY ASSISTANCE
We appreciate your interest in SEL products and services. If you have questions or comments,
please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
www.selinc.com • info@selinc.com