Professional Documents
Culture Documents
Unit 1: Definitions
Aircraft electrical system represents all power supplies and power conversion
equipments, distribution systems and power consuming
equipments (loads).
Electrical power generating system (EPGS) provides the energy to operate all the electrical
equipments in an aircraft and is a combination of
rotating and static electrical power sources and
the devices which provide their control and
protection. Generally, these are mainly on board
generators and converters.
Emergency power source consists of generator, power conversion device (or a combination
thereof not involving part of utilization equipment) or battery
installed to provide independent electrical power for essential
purposes during conditions of electrical emergency in flight.
Emergency electric system operation electrical system condition during flight when the
primary electric power system becomes unable to supply sufficient or
proper electrical power, thus requiring the use of independent and
potentially limited source(s) to power a reduced complement of
distribution and utilization equipment selected to maintain safe flight
and personnel safety.
primary-auxiliary
Depending on
the way of
transformation secondary
of output
energy into
input energy
tertiary
Electric drives;
ECS (Environmental control system);
Lighting system;
Starter-generator system;
Passenger cabin services ;
Measuring instruments, warning indicators;
Avionics;
Navigation equipments;
Automation Flight Control system;
Special equipments.
Reliability
Reduce vulnerability
Whenever a conductor is moved within a magnetic field in such a way that the
conductor cuts across the magnetic flux lines, a voltage is generated in the conductor.
'
::::*:: :*. me::gain
. E N
d
constant dt
a
magnetic field B- is
given by :
0 B A B A cos
A
B
Brush
Brush
Armature loop
Commutator Load (external
circuit)
Day
E N N NBA
dt dt dt
d( )
NBA sin NBA sin
dt
separately - excited;
A typical shunt-wound self - excited generators four pole generator, with an output
power of 9 kW at a continuous current of 300 A over the speed range of 4,500 to 8,500
rev/min, is illustrated.
2. The transmission from the gear-box is made it by a drive shafts with serrations or
splines, also known as quill drives, able to absorb mechanical vibration from the
3. The electric machine load (current in windings) is higher than in a common electric
machine (J=15 20 A/mm2 to the 3 8 A/mm2 );
4. The air gap inductance is higher than in a common electric machine (L=1.0 1.5 T to
the 0.6 0.9 T );
5. The rotation speed is also higher than in a common electric machine (n=4,500 9,000
rev/min to the 2,000 3,000 rev/min ).
The air passes over the brush-gear and the commutator and cools this high
temperature area, and then follows through apertures all the way through the length
of the machine to the exhaust at the drive end of the DC generator.
To assist the cooling and to provide some extra cooling on the ground many types of
DC generators have a fan fitted at the drive end of the armature.
The term “shunt-wound” is derived from the high-resistance field winding that is
connected across or in parallel with the armature.
Ie IL
Ia
Field
Generator
regulator
Terminal voltage
Shunt field
In this case the armature current, Ia, is divided into two currents, one formed by
the field winding circuit (excited circuit, Ie) and other by the external circuit, IL.
0 Ia Ie IL
fundamental requirement that the generator voltage at the distribution busbar system
is maintained constant under all conditions of load and at variable speeds, within the
limits of a preset range.
The device that will regulate the output voltage of a DC generator at the designed
value and within a specified tolerance is called voltage regulator.
A
IL
Ie
Ia
E, Ra
E V Ra I a Vb E
Ia Ie IL
it can be obtained:
V E Ra I a Vb E E Ra I L Ra I e Vb E
The loss of voltage given by the current used to excite the field coils, also
called losses in shunt-filed winding;
4pN a n p
E k en p
2a
where: - 2a is the number of parallel current paths of the armature windings;
- p is the number of pole pairs;
- Na is the number of turns in the armature windings;
- n is the rotation speed;
- p is the flux per pole;
- ke is the electrical constant.
By neglecting the core and brushes losses the basic the circuit equation for a
generator will be: constants
V E Ra I a k en p Ra I a
requirement: V constant
Depending on the Depending on the
p k Ie
Voltage regulation is made using
the excited current, Ie
Electrical Power Systems 1
Carbon Pile Regulator
Topologies of
voltage Vibrating Contact Regulator
regulators
Electronic Regulator
Ie
Ia
Ie Ie
m
Ie
FS
Fem
A C
B p
-controlled
armature.
The force which pull the armature is the difference between the electromagnetic
force of the electromagnet and the elastic force of the spring. That is calculated to act
resistance of the shunt-field increases, the excitation current decreases, the flux in
decreases too, also the force which pull the armature decreases. In this case the
resistance of the shunt-field decreases, the excitation current increases, the flux in
In aircraft applications the batteries used are from secondary type and are either
of the lead-acid or nickel-cadmium type.
In aircraft applications the batteries used are from secondary type and are either
of the lead-acid or nickel-cadmium type.
The
directly into current electricity.
The -hours
discharged 2 2 KOH
2O2 4e- 2 O2
Internal electrical
resistance
Ri
Emf E
Is given by the emf of the galvanic couple between the positive plate and the
negative plate.
Voltage of the
battery
V
Vc E Ep R iI c
Vd E Ep R iI d
where: Ep is the polarization emf produced by the dissociation of water into oxygen
and hydrogen that form a micro cell;
IC the charge current;
Id the discharge current, which in fact is load current (IL) .
Electrical Power Systems 1
Capacity of the
battery
Q
The capacity of a battery (amount of energy available), depends upon the size and
number of plates.
Efficiency of the
battery td
I d dt
% Q I d average td
Capacity efficiency: Q 100 d 100 0
tc
100
Qc I caverage tc
I c dt
0
td
I d U d dt UU d const .
Energy efficiency: %
c const . U d I d average td
100 0
tc
100
W
U c I caverage tc
I c U c dt
0
Electrical Power Systems 2
3.5. Thermal runaway
If the temperature and charging rate are exceeded the stability is lost so a condition
called “thermal runaway” can occur, a condition which causes violent gassing, boiling of
the electrolyte and finally melting of the plates and casing, with consequent danger to
the aircraft structure and also to the electrical system.
Since batteries have low thermal capacity heat can be dissipated and this results in
lowering of the effective internal resistance. Thus, when associated with constant
voltage charging, a battery will draw a higher charging current and thereby set up the
“runaway” condition of ever-increasing charging currents and temperatures.
Electrical Power Systems 1
Other factors which can cause overheating of a battery can be:
i) Voltage regulator of aircraft generating system incorrectly adjusted.
ii) Frequent or lengthy engine starts at very high discharge rates.
iii) Loose link connections between cells.
iv) Leakage currents between a cell and battery container and the airframe structure.
v) Use of unregulated, or poorly regulated, ground support equipment to charge a
battery, particularly a battery which has become hot as a result of excessive engine
cranking or an aborted engine start.
vi) High initial charging currents imposed on a hot battery.
vii)Unbalanced cells (cell unbalance - refers to an apparent loss of capacity and to
variations in cell voltage at the end of charging cycles). These variations can develop
over a period of time, particularly when subjected to operating conditions like those
occurring in aircraft utilizing charging circuits of the constant potential type. Other
factors which may also contribute to cell unbalance are cell position in the battery, e.g.
centre cells run warmer than outer cells, and the self-discharge of individual cells.
In some aircrafts, particularly those using nickel-cadmium batteries, temperature-
sensing devices are located within the batteries to provide a warning of high battery
temperatures and to prevent overcharging by disconnecting the batteries from the
charging source at a predetermined temperature.
Electrical Power Systems 2
3.6. Location of the batteries in an aircraft
Depending on the size of the aircraft and on the power requirements for operating
the essential services under emergency conditions, a single battery or several batteries
may be provided.
When several batteries are provided, most often they are connected in parallel
although in some types of aircrafts it is possible to operate using a series connection, e.g.
in case of two 14-volt batteries.
Batteries are installed in individual compartments specially designed and located to
provide adequate heat dissipation, ventilation of gasses and protection of airframe
structure against corrosive elements. At the same time batteries physically should be
placed as near as possible to the main and the battery busbars in order to avoid the use
of long leads with consequently high resistance
Batteries are normally mounted on, and clamped to, a tray secured to the aircraft
structure. The tray can also collect any acid that may leak from the battery. Trays may
be of any materials which is acid-proof, non-absorbent and resistant to reasonable
impact. Usually they are made from metal treated with an anti-corrosive paint and in
some cases sprayed or coated with p.v.c.
Electrical Power Systems 3
Fumes and gases generated by the battery at the
installation are extracted by the difference of
pressure existing across the aircraft. During normal
flight air tapped from the cabin pressurization
system enters the battery ventilation chamber and
continues through to the outside of the aircraft. On
the ground, when no pressure differential exists, a
non-return valve fitted in the air inlet prevents
fumes and gases from entering into the aircraft.
Electrical Power Systems 4
Unit 4: On board AC generators
The values of voltage and current produced by an AC generator are quantities with
a time dependence given by a periodic function
i (t ) I max sin i
Cycle or Period, T, is the time interval in which the alternating quantity v repeats all
values in the same time sequence.
v(t T ) v(t )
i (t T ) i (t )
t
F ; F Hz
T
n p
F
60
1T
Mean value or arithmetic mean value v v(t ) dt
T0
1T
Rectified value or absolute mean value v v(t ) dt
T0
If a point P moves in an x-y coordinate system along a circle of radius r around the
origin in the mathematically positive sense and with a constant angular velocity, the
projection of this point onto y-axis has a sine-like time behavior, the projection onto
the x-axis a cosine-like time behavior.
Electrical Power Systems 1
Phasor diagram, representation of phasor in the complex plane.
Transformation between an alternating quantity and its phasor in the complex plane:
the sine function describing the alternating quantity is viewed as the imaginary part of
a complex number whose real part is a cosine function of equal phase and equal
amplitude:
Vmax e j t 0
Depending of number of phases the type of generating systems an/or circuit could
be: single-phase when it produces a single-phase current;
poly-phase when it produces a several single alternating currents with
different phases.
0 3 2
2 2
I
T
Pure resistive – in
phase
The current and voltage in an AC circuit have the same frequency; because the wave
form of the alternating quantities is similar, if the voltage is sinusoidal then the
current is also sinusoidal.
In some circuits the flow of current is affected solely by the applied voltage so that
both voltage and current pass through zero and attain their maximum in the same
direction simultaneously. Under these conditions they are said to be in phase.
The difference between corresponding points on the wave form being known as phase
difference or phase angle.
Electrical Power Systems 4
Pure resistive in this type of circuit the resistance is constant, so the
magnetic and electrostatic effects are absent. The
applied voltage is the only factor affecting current
Phase relationships flow.
Inductive the voltage and the current are always out-of-phase
because the magnetic field surrounding the conductors is
continually changing in magnitude and direction with the
alternating current. In this case a a self-induced e.m.f. is
set up the circuit to oppose the change of current.
Therefore the wave form of the current is delayed with 90
degrees, or the current “lags” the voltage by 90 degrees.
Capacitive capacitance in an AC circuit also oppose the current flow
and causes a phase difference with reverse effect between
the applied voltage and the current, similar to the inductive
circuits; in this case the current “leads” the voltage by 90
degrees.
Vmax V Vmax V
Imax Imax I
I
0 3 2 0 3 2
2 2 2 2
Self-induced
e.m.f.
Pure inductive – I lags behind E Pure capacitive – I leads E
Electrical Power Systems 5
Interconnections of phases
Vl 3 V ph Il 3 I ph
Il I ph Vl V ph
One end of each phase windings is connected to a common point known as the neutral
point, while the opposite ends of the windings are connected to three separate lines
assigned with L1, L2 and L3.
Electrical Power Systems Vgen 208/120 V. 6
4.1.6 Generator power units
P
P V I cos
reactive power, Q appeared when the current and
V
the voltage are not in phase;
the reactive power unit (SI) is volt I
I cos
ampere-reactance (var);
Q V I sin
I sin Q
apparent power, S the product of the effective values of current and voltage;
the apparent power unit (SI) is volt-ampere (VA);
S V I P2 Q2
The Power factor, cos (PF), is the cosine of cur .
Electrical Power Systems P 7
PF cos
S
4.2. Constant Frequency Systems (CFS)
Constant
Shaft Speed
Variable
Shaft Speed
Constant Constant
Speed Frequency
Variable T drive
Engine u e 3-Phase
r n (C S D)
Speed 2:1 b g 115Vac
o i 400Hz
(for f n
Turbofan) a e
n Gear Box Generator
8:10
Integrated Drive Generator (I D G)
The Constant Speed Drive (CSD) in effect acts as an automatic gearbox, maintaining
the generator shaft speed at a constant rpm which results in a constant frequency output
of 400 Hz, usually within approximately 10 Hz or less.
Constant
Shaft Speed
Variable
Shaft Speed
Constant Constant
Speed Frequency
Variable T drive
Engine u e 3-Phase
r n (C S D)
Speed 2:1 b g 115Vac
o i 400Hz
(for f n
Turbofan) a e
n Gear Box Generator
8:10
Integrated Drive Generator (I D G)
The Constant Speed Drive (CSD) in effect acts as an automatic gearbox, maintaining
the generator shaft speed at a constant rpm which results in a constant frequency output
of 400 Hz, usually within approximately 10 Hz or less.
Alternator
Voltage
regulator
As the rotor rotates, the field induces a three-phase AC within the stator which is
The use of brushes and slip rings for conveying excitation current to AC generator
field windings presents similar problems to those associated with DC machines and
although not quite as severe, because of the lower values of DC carried, the elimination
of rotating surfaces in contact is desirable.
Thus, the brushless AC generator was conceived, and although not specifically limited
to constant-
system, and is now normally associated with those systems employed in several current
aircraft types.
As the rotor rotates, the field induces a three-phase AC within the stator which is
The use of brushes and slip rings for conveying excitation current to AC generator
field windings presents similar problems to those associated with DC machines and
although not quite as severe, because of the lower values of DC carried, the elimination
of rotating surfaces in contact is desirable.
Thus, the brushless AC generator was conceived, and although not specifically limited
to constant-
system, and is now normally associated with those systems employed in several current
aircraft types.
main generator.
Brushless generator Permanent magnets Parallel shunt field Stabilizing feedback
windings windings
Main generator Rotating rectifier AC exciter The exciter (located in the end bell
section of the generator casing)
comprises a stator and a 3-phase star-
wound rotor or exciter armature. The
exciter armature is mounted on the
same shaft as the main generator
rotor and the output from its 3-phase
windings is fed to the rotating
Voltage
sensing and
supply
Current transformer Power transformer and load Exciter output rectifier assembly.
output magnetic amplifier Rectified AC excitation
The main generator consists of a 3-phase star-wound stator, and 8-pole rotor and its
associated field windings which are connected to the output of the rotating rectifier.
The leads from the three stator phases are brought directly to the upper surface of an
output terminal board, thus permitting the aircraft wiring to be clamped directly against
the phase leads without current passing through the terminal studs. In addition to the
fields coils, damper windings are fitted to the rotor and are located in the longitudinal
slots in the pole faces. Large copper bands, under steel bands at each end of the rotor
stack, provide the electrical squirrel-cage circuit. The purpose of the damper windings is
to provide an induction motor effect on the generator whenever sudden changes in load
or driving torque tend to cause the rotor speed to vary above or below the normal or
synchronous system frequency. In isolated generator operation, the windings serve to
reduce excessively high transient voltages caused by line-to-line system faults; it also
decreases voltage unbalance, during unbalanced load conditions.
Some types of aircraft use oil from the CSD hydraulic system for cooling instead of
air; the oil is pumped through the generator for cooling of the rotor windings, diodes and
the stator windings. The oil itself is afterwards cooled by an external cooler through
which air is passed via a tapping produced in the compressor stage of the engine. In one
particular type of aircraft the oil was cooled by passing it through a section of the cooler
medium. This was the case of the Concorde, that flew at a speed of Mach 2, the
C.
The output of the bridge rectifier in the error detector is a DC voltage slightly lower
than the average of the three AC line voltages; it may also be adjusted by using a
variable resistor RV1 to balance the regulator system to a balanced condition for any
nominal value of line voltage.
A balanced condition is obtained when the voltage applied across the bridge, between
point A and B is exactly twice the voltage drop across each tube. In this case, the
voltage drop across resistors R1 and R2 will be equal to the drop across each tube,
therefore no current will flow in the output of the pre-amplifier. If the AC line voltage
changes above or below the fixed value, the voltage drop across R1 and R2 will differ
causing an unbalance of the bridge circuit and a flow of current to the “error” control
winding of the pre-amplifier.
The direction and magnitude of the current flow will depend on whether the variation,
or the error in the line voltage, is above (positive error signal) or below (negative error
signal) the balanced nominal value, and will also depend on the magnitude of the
variations.
Electrical Power Systems 6
When the current flows through the “error” control winding, the set up magnetic flux
alters the total flux in the cores of the amplifier (both pre-amplifier and amplifier are
3-phase magnetic amplifiers), thereby establishing a proportional change in the amplifier
output which is applied to the signal winding of the power amplifier.
If the error signal is negative it will cause an increase in the core flux, thereby
increasing the power amplifier output current to the generator exciter field winding.
For a positive error signal the core flux and excitation current will be reduced. If the
generator output is adjusted and maintained to the preset value, this will restore the
error detector bridge circuit to the balanced condition
In the aircraft electrical installations various types of consumer equipment are used
which require power supplies different from the standard supplies provided by the main
generator. As it has already been discussed in Unit 1, these power supplies are for the
secondary and tertiary – types of electrical power supplies.
Usually these power supplies are called convertors because they convert electrical
power from one form (DC or AC) to another, or convert one form of supply to a higher or
lower value, or another frequency.
operation, and as we have already seen, the DCs cannot be entirely eliminated even for
aircrafts which in concept are primarily AC powered.
The most commonly converting equipment used on board of the aircrafts are the
static converting equipments, which may be grouped in:
rectifiers;
transformers;
static DC/AC converters.
The rectifying process is based on the principle that when a voltage is applied to
certain elements called semiconductors an exchange of negative and positive charge
carriers (known as “electrons” and “holes”, respectively) takes place at the contact
surfaces. As a result of this exchange, a barrier layer that exhibits different resistance
and conductivity characteristics is formed; it allows the current to flow through the
combination more easily in one direction than in the opposite. Thus when the applied
voltage is an alternating quantity the barrier layer converts the current into
unidirectional flow and provides a rectified output.
of the electrons from the n area and of the holes from the p area. This area becomes an
effective insulator called barrier layer or potential barrier and has the variation of the
electric charge as shown in the figure below.
p-type n-type
semiconductor semiconductor
p-type n-type p-type n-type +
semiconductor semiconductor semiconductor semiconductor +
+
+
+
+
p n p n
_ Ia Ia _
+ +
_ + + _
Ua Ua
a) b)
_
+
A-Anode C-Cathode
Otherwise if the polarity of the power supply is reversed the barrier potential area is
narrowed therefore the flow current (called forward current) is important and the p-n
junction is called “forward” polarized.
temperature is limited and the protection against short duration overloads is difficult,
they are not recommended in main power systems.
In the aircraft electrical installations various types of consumer equipment are used
which require power supplies different from the standard supplies provided by the main
generator. As it has already been discussed in Unit 1, these power supplies are for the
secondary and tertiary – types of electrical power supplies.
Usually these power supplies are called convertors because they convert electrical
power from one form (DC or AC) to another, or convert one form of supply to a higher or
lower value, or another frequency.
The most commonly converting equipment used on board of the aircrafts are the
static converting equipments, which may be grouped in:
rectifiers;
transformers;
static DC/AC converters.
The rectifying process is based on the principle that when a voltage is applied to
certain elements called semiconductors an exchange of negative and positive charge
carriers (known as “electrons” and “holes”, respectively) takes place at the contact
surfaces. As a result of this exchange, a barrier layer that exhibits different resistance
and conductivity characteristics is formed; it allows the current to flow through the
combination more easily in one direction than in the opposite. Thus when the applied
voltage is an alternating quantity the barrier layer converts the current into
unidirectional flow and provides a rectified output.
p-type n-type
semiconductor semiconductor
p-type n-type p-type n-type +
semiconductor semiconductor semiconductor semiconductor +
+
+
+
+
The value of the potential barrier is between 0.2 and 0.4 V for Germanium and
between 0.6 and 0.8 V for Silicon.
p n p n
_ Ia Ia _
+ +
_ + + _
Ua Ua
a) b)
_
+
A-Anode C-Cathode
Otherwise if the polarity of the power supply is reversed the barrier potential area is
narrowed therefore the flow current (called forward current) is important and the p-n
junction is called “forward” polarized.
The single-phase half-wave circuit is the simplest possible circuit for a rectifier and
summarizes, in a practical manner, the operating principles already described. The output
from the single rectifier is a series of positive pulses the number of which is equal to the
frequency of the input voltage.
Current flow in 1st half-cycle
Current flow in 2nd half-cycle
+-
1st 1st
2nd
2nd 1 cycle
1 cycle
+-
Input Output
-+
1st
2nd
1 cycle
-
+
1st 2nd
Input 1 cycle
Output
Current flow in 1st half-cycle
Phase 1
Input
Phase 3 Phase 2
Output
Input
The figure shows the bridge type circuit arrangement for the full-wave rectification
of a 3-phase AC input, most commonly used for power rectification in aircraft.
In this type of circuit the line voltage is smoother than in a three single-phase
rectification circuit and the most harmonic is the sixth ( 400 6 2.400 Hz ).
AC AC
input output
a secondary winding.
Lets note with N1 the number of turns of the primary winding and with N2 the number
of turns of the secondary winding, respectively.
N1 E1
transformation ratio (r), or turns, is expressed by: r
N2 E2
Conversely, a “step-down” transformer is the one which lowers the secondary voltage.
Circuit connections Voltage transformers are connected so that the primary windings are in
parallel with the supply voltage; the primary windings of current transformer are
connected in series.
As the name suggests, a single-phase transformer is transforming the voltage from a
single-phase supply or from any one phase of a 3-phase supply.
Star connection three-wire Star connection four-wire Star and Delta connection
When the star connection is used in 3-phase transformers for the operation of 3-
phase consumer equipment, the transformer may be connected as a 3-phase system. If a
single-phase loads has to be powered from a 3-phase supply it is sometimes difficult to
keep them balanced, so it is essential to provide a fourth or neutral wire so that
connections of the loads may be made between this wire and any one of 3-phase lines.
N1 I2
transformation ratio (r), or turns, is expressed by: r
N2 I1
X1 X2 Secondary
(Start) (Finish) winding
Side H1 Side H2
Towards generator Towards load
Primary
Current – carrying conductor winding
Secondary
input
Primary
input
When a circuit load is connected to the secondary terminals, a current due to the
induced voltage will flow through the whole winding and will be in apposition to the
primary current from the input terminals.
The difference between the output terminal voltages at full-load and no-load, with a
constant input voltage, is called the regulation of the transformer.
AC
generator
input
To warning
Thermal lamps
switches
+ DC input
Main
output
To
ammeter
Rectifier
section
Ammeter
shunt
terminals
AC input
terminals Temperature
warning system
terminals
DC output
terminals
Transformer-rectifier unit
Constant
28 V DC Filter current
input network generator
400 Hz Square
Turn on wave generator
delay
notch
notch time
time
Odd 115 V AC
Pulse Power Output 400 Hz
harmonic
shaper driver stage output
filter
Voltage
sensor
Notch
Regulator
control
Current
sensor
Electrical Power Systems 11
The DC is supplied to the transistorized circuits of a filter network, a pulse shaper, a
constant current generator, power driver stage and the output stage. After any
variations in the input have been filtered or smoothed out, the DC is supplied to a square-
wave generator which provide first-stage conversion of the DC into square-wave form AC
and also establishes the required operating frequency of 400 Hz. This output is then
supplied to a pulse shaper circuit which controls the pulse width of the signal and
changes its wave form before it is passed on to the power driver stage.
It will be noted that the DC required for the pulse shaper operation is supplied via a
turn-on delay circuit. The reason for this is to cause the pulse shaper to delay its output
to the power driver stage until the voltage has been stabilized. The power driver supplies
a pulse-width modulated symmetrical output to control the output stage, the signal having
a square-wave form. The power driver also shorts itself out each time the voltage falls to
zero, i.e. during “notch time”.
The output stage also produces a square-wave output but of variable pulse width. This
output is finally fed to a filter circuit which reduces the total odd harmonics to produce
a sine wave output at the voltage and frequency required for operating the systems
connected to the inverter.
Constant
28 V DC Filter current
input network generator
400 Hz Square
Turn on wave generator
delay
notch
notch time
time
Odd 115 V AC
Pulse Power Output 400 Hz
harmonic
shaper driver stage output
filter
Voltage
sensor
Notch
Regulator
control
Current
sensor
Electrical Power Systems 1
The DC is supplied to the transistorized circuits of a filter network, a pulse shaper, a
constant current generator, power driver stage and the output stage. After any
variations in the input have been filtered or smoothed out, the DC is supplied to a square-
wave generator which provide first-stage conversion of the DC into square-wave form AC
and also establishes the required operating frequency of 400 Hz. This output is then
supplied to a pulse shaper circuit which controls the pulse width of the signal and
changes its wave form before it is passed on to the power driver stage.
It will be noted that the DC required for the pulse shaper operation is supplied via a
turn-on delay circuit. The reason for this is to cause the pulse shaper to delay its output
to the power driver stage until the voltage has been stabilized. The power driver supplies
a pulse-width modulated symmetrical output to control the output stage, the signal having
a square-wave form. The power driver also shorts itself out each time the voltage falls to
zero, i.e. during “notch time”.
The output stage also produces a square-wave output but of variable pulse width. This
output is finally fed to a filter circuit which reduces the total odd harmonics to produce
a sine wave output at the voltage and frequency required for operating the systems
connected to the inverter.
Electrical power is required to start the engines, to operate certain activities during
servicing periods at airports, e.g. lighting, and to test the electrical systems during
routine maintenance checks.
The batteries of an aircraft are, of course, a mean of supplying the necessary power,
and although capable to start the engine, their capacity does not permit a wide scale use
on the ground; as we have already discussed in Unit 3, they are restricted to the supply
of power under emergencies conditions.
It is necessary to incorporate a separate circuit through which power from an
system. In its simplest form, a ground power supply system consists of a connector
located in the aircraft at a conveniently accessible point (at the side of a fuselage for
example) and a switch for completing the circuit between the ground power unit and the
busbar system.
In addition to the ground power supply system, some types of aircrafts carry
separate batteries that can supply the ground services in the event of a non-available in
ground power unit; these will help to conserve the main batteries for engine starting.
Power
selector
switch
“Ground” “Flight”
Battery
Ground
+
power
_ connector
The power selector switch has two positions, “ground” and “flight”, respectively. By
selecting the “ground” position the ground power supply will be connected to the main
busbar via the ground power connector. Alternatively, in the “flight” position the battery
will be connected to the main busbar and the battery will be constantly supplied with the
charging current. This is the position the switch is selected when aircraft is in flight.
Power
selector
switch
_
“GND” “BAT”
+
+ To battery
Ground power
plug
From the figure it can be observed that the short positive pin is connected to the coil
circuit of the ground power relay. The reason for this is that in the event of the
withdrawal of the ground supply socket with the circuit “on”, the ground power relay will
de-energize before the main pins are disengaged from the socket. This ensures that the
breaking of the supply will take place at the heavy-duty contacts of the relay thus
preventing arching at the main pins.
Because aircrafts are mainly of the “AC type” from the electrical point of view, it is
essential for the understanding of installation ground supply system to include a section
where an external source of AC power may be supplied. The circuit arrangements for the
appropriate systems vary between aircraft types but in order to gain some understanding
of the circuit requirements and operation we consider the next circuit:
In general, an A.P.U. consists of a small gas turbine engine, a bleed-air control and
supply system, and an accessory gearbox. The gas turbine comprises a two-stage
centrifugal compressor connected to a single-stage turbine. The bleed-air control and
supply system automatically regulates the amount of air bled from the compressor for
for engine operation, e.g. fuel pump control unit and oil pumps, the accessory gearbox
drives a generator which, depending on the type required for a specific aircraft, may
supplied either with DC or AC.
A motor for starting the A.P.U. is also secured to the gearbox and is operated by the
aircraft battery system or, when available, from a ground power unit. In some types of
A.P.U. the functions of engine starting and power generation are combined in a
starter/generator unit.