10 ACU - 2 HP 2760 230 12 40AT 2-P 240V PLUG-IN 2 - 5.5mm2 THHN 20mm Ø PVC
DESIGN ANALYSIS
BRANCH CIRCUIT PROTECTIONS AND CONDUCTORS SERVICE EQUIPMENT AND SERVICE ENTRANCE CONDUCTORS
USE: USE: USE: USE: C.B. SERVICE ENTRANCE CONDUCTORS 150AT 15AT
II. LIGHTING AND CONVENIENCE
2 - 2.0mm2 THHN 2 - 2.0mm2 THHN 2 - 3.5mm2 THHN 2 - 3.5mm2 THHN I = 2.17 x 250% = 5.43 A 2 - 50mm² THHN
RECEPTACLE LOAD Lighting Loads 3700 VA C1
15AT 2-P 240V C.B. Plug-in 15AT 2-P 240V C.B. Plug-in 30AT 2-P 240V C.B. Plug-in 30AT 2-P 240V C.B. Plug-in 15AT 30AT
Receptacle Loads 8100 VA 100% 11800 VA
USE: SERVICE ENTRANCE CAP C2 C3
2 - 3.5mm2 THHN 11800 VA 30AT 20AT
230 V, 60 Hz, 1ɸ, 2 WIRE
20AT 2-P 240V C.B. Plug-in (FROM THE POWER SOURCE) C4 C5
III. COOKING LOAD 20AT 20AT
2 - Range 6000 VA 80% 4800 VA C7
C6
20AT 20AT
IV. OTHER LOADS C8 C9
1 - Refrigerator 500 VA 20AT 30AT
1 - Washing Machine 1200 VA 40% 680 VA SPARE
C10
CIRCUIT 6 CIRCUIT 7 CIRCUIT 8 CIRCUIT 9 CIRCUIT 10 1700 VA 40AT
WASHING MACHINE RANGE RANGE ACU - 1HP ACU - 2HP SPARE
TOTAL VA 21880 VA
P = 1200 W P = 3000 W P = 3000 W P = 1840 W P = 2760 W GROUND BUS
I = 1200 / 230 = 5.22 A I = 3000 / 230 = 13.04 A I = 3000 / 230 = 13.04 A I = 1840 / 230 = 8 A I = 2760 / 230 = 12 A
SERVICE EQUIPMENT:
C.B. USE: USE: C.B. C.B.
I = 5.22 x 250% = 13.05 A 2 - 3.5mm2 THHN 2 - 3.5mm2 THHN I = 8 x 250% = 20 A I = 12 x 250% = 30 A [ 2760(250%) + 1840 + 11800 + 4800 + 680 ] ÷ 230 = 113 AMPERES
20AT 2-P 240V C.B. Plug-in 20AT 2-P 240V C.B. Plug-in USE: 150AT 2-P 240V Circuit Breaker, Plug-in Type
USE: USE: USE:
2 - 3.5mm2 THHN 2 - 3.5mm2 THHN 2 - 5.5mm2 THHN
20AT 2-P 240V C.B. Plug-in 30AT 2-P 240V C.B. Plug-in 40AT 2-P 240V C.B. Plug-in SERVICE ENTRANCE CONDUCTORS:
[ 21880 + 2760(25%) ] ÷ 230 = 98 AMPERES
USE: 2 - 50mm2 THHN in 50mm Ø Intermediate Metal Conduit
T
UT
2
RODRINER C. BILLONES BSEE - 4A
EG
TIN: 1470008233
ENGR. ROLANDO R. FRANCISCO PROPOSED TWO STOREY
IT
RA
TE
IN
ELECTRICAL ENGINEER 1
D
S
ER
2
EC
1975
GI
IC
MAIN CAMPUS
EN
AL
COLLEGE OF ENGINEERING, ARCHITECTURE & TECHNOLOGY ISSUED AT: CAPSU LOCATION: SUNSHINE VILLAGE, BRGY. BANICA, ROXAS CITY, CAPIZ DATE CHECKED: DATE STARTED: 10/19/21 DATE FINISHED: 10/27/21