Professional Documents
Culture Documents
This is the most widely used scheme for the protection of EHV and UHV power
lines. In this scheme a carrier channel at high frequency is employed. The carrier
signal is directly coupled to the same high voltage line that is to be protected. The
frequency range of the carrier signal is 50 kHz to 700 kHz. Below this range, the
size and the cost of coupling equipment becomes high whereas above this range,
signal attenuation and transmission loss is considerable. The power level is about
10-20 W. In this scheme, the conductor of the power line to be protected are used for
the transmission of carrier signals. So the pilot is termed as a power line carrier
With the rapid development of power systems and the large amount of intercon-
nection involved, it has become very essential to have high speed protective schemes.
Carrier current schemes are quite suitable for EHV and UHV power lines. They are
faster and superior to distance schemes. Distance protective schemes are non-unit
type schemes. They are fast, simple and economical and provide both primary and
back-up protection. The main disadvantage of conventional time-stepped distance
protection is that the circuit breakers at both ends of the line do not trip simultane-
ously when a fault occurs at one of the end zones of the protected line section. This
may cause instability in the system. Where high voltage auto-reclosing is employed,
non-simultaneous opening of the circuit breakers at both ends of the faulted section
does not provide sufficient time for the de-ionisation of gases. The carrier current
protection or any other unit protection does not suffer from these disadvantages.
In unit protection, circuit breakers trip simultaneously at both ends. It is capable of
providing high speed protection for the whole length of the protected line section.
In a carrier current scheme, the carrier signal can be used either to prevent or initi-
ate the tripping of a protective relay. When the carrier signal is used to prevent the
operation of the relay, the scheme is known as carrier-blocking scheme. When the
carrier signal is employed to initiate tripping, the scheme is called a carrier intertrip-
ping or transfer tripping or permissive tripping scheme.
Carrier current schemes are cheaper and more reliable for long lines compared
to wire pilot schemes, even though the terminal equipment is more expensive and
more complicated. In some cases, the carrier signal may be jointly utilised for tele
phone communication, supervisory control, telemetering as well as relaying. Thus,
the cost of carrier equipment chargeable to relaying work can be reduced. The cou-
pling capacitors required for carrier signal can be used also as potential dividers to
supply reduced voltage to instruments, relays etc. This eliminates the use of separate
potential transformers.
There are two important operating techniques employed for carrier current protec-
tion namely the phase comparison technique and directional comparison technique.
In the phase comparison technique, the phase angle of the current entering one end is
compared with the phase angle of the current leaving the other end of the protected
line section. If the currents at both the ends of the line are in phase, there is no fault
on the protected line section. This will be true during normal conditions or in case of
external faults. In case of faults on the protected line section, the two currents will be
180° out of phase. In this scheme, the carrier signal is employed as a blocking pilot.
In the directional comparison technique, the direction of power flow at the two
ends of the protected line section is compared. During normal conditions and in the
case of external faults, the power must flow into the protected line section at one end
and out of it at the other end. In case of an internal fault, the power flows inwards
from both ends.
impedance to carrier frequency current. On the other hand, the inductance offers a
low impedance to power frequency current and high impedance to carrier frequency
current. Thus the transmitter and receiver are insulated from the power line and effec-
tively grounded at power frequency current. But at carrier frequency they are con-
nected to the power line and effectively insulated from the ground.
For the transmission of carrier signal either one phase conductor with earth return
or two phase conductors can be employed. The former is called phase to earth cou-
pling and the latter is called phase to phase coupling. The phase to earth coupling is
less expensive as the number of coupling capacitors and line traps required is half of
that needed for phase to phase coupling. However the performance of phase to phase
coupling is better compared to phase to earth coupling because of lower attenuation
and lower interference levels.
The half-cycle blocks of carrier signals are injected into the transmission line
through the coupling capacitor. Fault detectors control the carrier signal so that it is
started only during faults.
The voltage outputs of the summation network at stations A and B are 180° out
of phase during normal conditions. This is because the CT connections at the two
ends are reversed. The carrier signal is transmitted only during positive half cycle
of the network output. Figure 7.8 shows the transmission of carrier signal during
external fault and internal fault conditions. Wave (a) shows the output of the summa-
tion network at A. Wave (b) shows the carrier signal transmitted by the transmitter
at A. Wave (c) shows the output of the summation network at B for external fault at
C. Wave (d) shows the carrier signal transmitted by the transmitter at B. Thus for an
external fault, carrier signals are always present in such a way that during one half-
cycle, signals are transmitted by the transmitter at A and during the next half-cycle by
the transmitter at B. As the carrier signal is a blocking signal and it is always present
the relay does not trip. For an internal fault, the polarity of the network output voltage
at B is reversed, as shown by the wave (e). The carrier signal sent by the transmitter at
B is shown by wave (f). In case of internal faults, carrier signals are transmitted only
during one half-cycle and there is no signal during the other half-cycle. As the carrier
signal is not present during the other half-cycle, the relay operates and the circuit
breaker trips. The comparator receives carrier signal from the receiver. So long as
the carrier is present, it does not give an output to the auxiliary tripping relay. When
the comparator does not receive the carrier signal, it gives an output to the auxiliary
tripping relay.
The ideal phase difference between carrier blocks is 180° for internal faults and
zero degree for external faults. In practice, it is kept 180° 30° for internal faults
because of
(i) the phase displacement between emfs at the ends of the protected line
section.
ii) through current being added to the fault current at one end and subtracted at
the other.
(ii) errors produced by CTs.
The phase comparison scheme provides only primary protection. The back-up
protection is provided by supplementary three step distance relays for phase and
ground faults. In a phase comparison scheme, the relay does not trip during swings
at B is reversed, as shown by the wave (e). The carrier signal sent by the transmitter at
Bis shown by wave (). In case of internal faults, carrier signals are transmitted only
during one half-cycle and there is no signal during the other half-cycle. As the carrier
signal is not present during the other half-cycle, the relay operates and the circuit
breaker trips. The comparator receives carrier signal from the receiver. So long as
the carrier is present, it does not give an output to the auxiliary tripping relay. When
the comparator does not receive the carrier signal, it gives an output to the auxiliary
tripping relay.
The ideal phase difference between carrier blocks is 180° for internal faults and
zero degree for external faults. In practice, it is kept 180° t 30° for internal faults
because o
) the phase displacement between emfs at the ends of the protected line
Section.
(i) through current being added to the fault current at one end and subtracted at
he other.
(ii) errors produced by CTs.
The phase comparison scheme provides only primary protection. The back-up
protection is provided by supplementary three step distance relays for phase and
ground faults. In a phase comparison scheme, the relay does not trip during swings
Network output at A
(a) for fault at Dor C
Carrier signal
(b) transmitted from A toB
for fault at Dor C.
Network output at B
(C) forfault atC
Carrier signal
(d) transmitted from B to A
for fault at C.
Network output at B
(e) for fault at D
Carrier signal
transmitted from B to A
for fault at D.
Fig. 7.8 Transmission of carrier signals during internal and external fault conditions
or out of step conditions or because of zero sequence current induced from a parallel
line, if there is no fault on the protected line section. It is used as a primary protection
for all long distance overhead EHV and SHV transmission lines.
The length of transmission line which can be protected by phase comparison
scheme is limited by phase shifts produced by the following factors
i) The propagation time, i.e. the time taken by the carrier signal to travel from
one end to other end of the protected line section (up to 0.06° per km).
i) The time of response of the band pass filter (about 5°).
(ii) The phase shift caused by the transmission line capacitance (up to 10).
and also because of the high altitude ie., lower pressure) the electric field required
for breakdown of air is only about 10 kV/cm. The lightning discharge mechanismis
well explained with the help of Fig. 16.1.
Stepped
Leader
Pilot Return
Streamer
Streame
+************ **+++++++++
a) (b)
edrt
Leader
Return
Bamer
Strean
(c)
When a potential gradient of about 10 kV/cm is set up in the cloud, the air
immediately surrounding the cloud gets ionised and the first process of the actual
lightning discharge starts. At this instant, a streamer called a 'pilot streamer starts
from the cloud towards the ground which is not visible. The current associated with
this streamer is of the order of 100 amperes, and the most frequent velocity of propa-
gation of he streamer is about 0,.15 m/us (1.e. 0.05 per cent of the velocity of hght).
Depending upon the state of ionisation of the air surrounding the pilot streamer, it
is branched into several paths, a stepped leader is formed, as shown in Fig. 16.1(a).
It is called a stepped leader because of its zig-zag shape. It contains a series of steps
about 50 m in length. The velocity of propagation of these steps should be more
than 16.6 per cent that of light. A portion of the charge in the centre from which
the strike originated is lowered and distributed over this entire system of temporary
conductors. This process continues until one of the leaders strikes the ground. When
one of the stepped leaders strikes the ground, an extremely bright return streamer, as
shown in Fig. 16.1(b) propagates upward from the ground to the cloud following the
ame n th as tho anne of the dom d leader The charge distributed olon
Protection Against Overvoltages 595
one of the stepped leaders strikes the ground, an extremely bright return streamer, as
shown in Fig. 16.1(6) propagates upward from the ground to the cloud following the
same path as the main channel of the downward leader. The charge distrbuted along
the leaders is thus discharged progressively to the ground. giving rise to the very
large currents associated with lightning discharges. The conventional directions of
the current in the stepped leader and return streamer are the same. The curent varies
between I kA and 200 kA and the velocity of propagation of the streamer is about I10
per cent that of light. It is here that the negative charge of the cloud is being neutral-
ized by the positive induced charge on the ground. It is this instant which gives rise
to the lightning flash which is visible with our naked eye.
After the neutralization of the most of the negative charge on the cloud any further
discharge from the cloud may have to originate from another charge centre within
the cloud near the already neutralized charge centre. Such a discharge from another
charge centre will, however, make use of the already 10nised path, and consequently
it will have a single branch and will be associated with a high current. This streamer
of discharge is called a dart leader as shown in Fig. 16.1(©). The velocity of propaga-
tion of the dart leader is about 3 per cent that of light. The dart leader can cause more
Severe damage than the return stroke.
Though the discharge current in the return streanmer is relatively large but since
it continues only for a few microseconds, it contains less energy and hence this
streamer is called a cold lightning stroke. The dart leader is called a hot lightning
stroke because even though the current in this leader is relatively smaller, it contains
relatively more energy since it continues for some milliseconds.
It has been observed that every thundercloud may consist of as many as
40 separate charged centres due to which a heavy lightning stroke may occur. This
lightning stroke is called multiple (or repetilive) stroke.
When a lightning stroke takes place to a point adjacent to the line, the current asso-
C1ated with it induces a voltage on the line which is in the form of a travelling wave.
A lightning discharge may have currents in the range of 10 kA t0 about 100 kA, and
the duration of the lightning flash may be of the order of a few microseconds. The
current wave form is generally a unidirectional pulse which rises to a peak value in
about 3 jus and decays to a small values in several tens of microseconds. Therefore,
the overvoltage due to lightning will have travelling waves of very steep wave front
which may be dangerous to the line and equipment of the power system and may
cause damage.
Lightning causes two kinds of voltage surges (overvoltage), one by direct stroke to a
line conductor, and the other induced by indirect stroke when bound eharges are dis
sipated following a lightning discharge to an object near the line conductor. A direct
stroke to a phase (line) conductor is the most severe lightning stroke as it produces
the highest overvoltage for a given stroke current. The current in a direct stroke to
a phase conductor is hardly affected by the voltage which it sets up between the
conductor and ground, so that a direct lightning stroke approximates to a constant
current source. lf a current flows in a direct stroke to a phase conductor, forward
and backward travelling currents i, and i, cach of magnitude /2 flow in the conduc-
tor away from the pont of strike in both directions of the line as shown in Fig. 16.3.
Therefore, the voltage surge magnitude at the striking point is given by
(16.2)
fCloud
Direct Lightning Stroke
Phase Conductor
Owers
16.8.3 Lightning Arresters or Surge Diverters
Lightning arresters are also known as surge diverters or surge arresters. They are
connected between the line and ground at the substation and always act in shunt
(parallel) with the equipment to be protected, and perform their protective function
by providing a low-impedance path for the surge currents so that the surge arrester's
protective level is less than the surge voltage withstanding capacity of the insulation
of equipment being protected. A lightning arrester's protective level is the voltage
appearing across the terminals of the arrester at sparkover or during the flow of cur-
rent through the arrester after sparkover. The main purpose of lightning arresters is to
divert or discharge the surge to the ground.
The action of the surge diverter can Surge voltage if no
be studied with the help of Fig. 16.15. protective device
Is present
When the travelling surge reaches the
diverter, it sparks over at a certain pre-
fixed voltage as shown by point P and , Initial peak
provides a relatively low-impedance Residual voltage
path to ground for the surge current. The
current flowing to ground through the
surge impedance of the line limits the
amplitude of the overvoltage across the
line and ground known as 'residual volt- Time
age' (as shown by point Q in Fig. 16.15)
to such a value which will protect Fig. 16.15 Voltage characteristic of
surge diverter
the insulation of the equipment being
protected.
insulator should be more than one-third of the gap length i.e. L) in order to
prevent the are from being blown to the insulator. The accurate breakdown value of
the rod gap cannot easily be predicted because the breakdown of air depends upon
the atmospheric conditions (ie., humidity, temperature and pressure), as also upon
polarity, steepness and the waveshape of the wave.
The major disadvantage of the rod gap is that it does not interrupt the power fre-
queney follow current after the surge has disappeared. This means that every opera
tion of the rod gap creates an L-G fault which can only be cleared by the operation
of the circuit breaker. Thus, the operation of the rod gap results in circuit outage and
interruption of power supply.
Thyrite discs
Thyrite discs
Foundation Base
Fig. 16.18 A typical value-type lightning arrester
The main function of the diverter is the protection
of the insulation against dan-
gerously high overvoltages and for this reason the breakdown
voltage of the diverter
at system frequency is made greater than 1.8 times
the normal value.
The ideal characteristic for the non-linear resistor would
be RI = constant, since
such a resistor will maintain constant voltage by changing its
resistance in inverse
proportion to the current. The non-linear resistor is in the form of discs
of 9 cm diam-
eter and 2.5 cm thickness. The material used for such resistors,
called by trade names
of "Thyrite", and "Metrosil" is a hard ceramic substance in the form
of cylindrical
blocks which consist of small crystals of silicon carbide bound
together by means
of an inorganic binder, with the whole assembly being subjected to heat
treatment.
The non-linear characteristic is attributed to the properties of the electrical
contacts
between the grains of silicon carbide. As the material used f non-linear
resistors for
the arrester is known by trade name as thyrite, this type of lightning
arrester is also
sometimes called Thyrite type lightning arrester.
Figure 16.19 shows the volt-ampere characteristic of the non-linear resistor,
the
dotted curve being the static characteristic, while the solid curve is the dynamic char-
acteristic corresponding to the application of a voltage surge. If a horizontal line,
tangential to the dynamic characteristic is drawn, then its intercept with the voltage
axis gives the residual voltage. The residual voltage is defined as the peak (erest)