Professional Documents
Culture Documents
© 2003
Technical Documentation SAACKE
January 2004
For more than 70 years SAACKE has set Power of innovation, technical perfection
standards in economic, ecofriendly and and reliability of all products account for
easytoservice burner technology. SAACKE’s technological leadership.
Competent project management, com
Firstrate engineering and continuous prehensive operational advice, and a
optimization of products and systems, worldwide service network stand for cu
supported by extensive inhouse re stomer proximity and partnership with a
search and development, ensure fulfil guaranteed future within the industrial
ment of all specific operational require thermal market.
ments and sustain great flexibility.
1 Validity ................................................................5
3 Preparation of commissioning.........................7
Appendix 1..................................................................15
Appendix 2..................................................................16
Technical Documentation
1-8254-8015a/02
Page 4 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
1 Validity
This specification describes how to use the flame detection system FLUS 06 / FLS 09 that consists of the flame
monitoring unit FLUS 06 or FLUS 06 UV and the flame scanner FLS 09 or FLS 09 UV.
Attention!
The flame detector is a safety system. Operations/manipulations at this system may therefore be carried out by
the manufacturer or authorized persons only. Such operations must not be carried out by others.
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 5 / 18
Trouble identification
2 Commissioning sequence
Setting measures before commissioning the burner
Check whether all electric connections exist and are properly fastened
• Verify the cable layout incl. of the shielding
Flame monitoring unit FLUS 06
• Potentiometer for intensity to left-side limit stop in IR units, whereas right-side limit stop has to be chosen exclusively for UV units;
otherwise provide for the UV-version of FLUS 06
Check of the flame detector for proper operation (point 3.4)
Inspect the flame detector's function (point 2.1).
Flame scanner:
• If possible, alignment of the flame scanner to the first third of the ignition or main flame to be monitored. The flame must be visible over the
entire operation range
- Check whether enough ignition flame is in the sight range of the scanner; if
Burner start required modify the pilot burner settings
- Inspect the sight opening for possible soiling
- Check the alignment of the scanner; if required modify the insertion depth and
no alignment in the burner head;
in case of UV the signal intensity at the measuring outlet of the flame scanner can
Flame 'On' be maximized by a better alignment
- in case of an IR-unit, step-by-step increase of the sensitivity at the FLUS 06
(potentiometer in direction of right-side limit stop).
yes
Optimization of the set values
− In case of IR: in order to achieve an optimum between detection of the flame and the suppression of a possible reflection, the
potentiometer at the flame monitoring unit may be turned in direction of the right-side limit stop only so far that the intensity display
will not be lowered
− In case of UV: the signal intensity at the measuring outlet of the flame scanner can be maximized by a better alignment to the
flame, i.e. the ignition flame in case of a common monitoring of both the ignition and the main flame
− Measure the signal voltage at the scanner (point 4)
Note the set values, the measured values and the production number of the FLUS 06 and the FLS 09
as well as the maximum scanner temperature in the Commissioning Documentation.
Technical Documentation
1-8254-8015a/02
Page 6 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
3 Preparation of commissioning
Check whether the optical flame scanner has been positioned correctly.
Before connecting the flame monitoring unit to the auxiliary energy, check whether the connections at the connector
block of the flame monitoring unit have been realized according to the connection diagram.
Inspecting the flame detector's function
The intensity potentiometer for the evaluation of the flame intensity must be adjusted accordingly.
Should there be no reaction at the first burner start, the right side limit stop adjustment can be chosen for a stable flame
detection. Until switch-off tests have been successfully carried out, it must be assured that- in addition to the flame
detector - there are sufficient means to react in case of a flame that does not burn correctly or even extinguishes.
As soon as the burner has been adjusted correctly, the sensitivity must be reduced again to a value that guarantees a
stable and safe operation.
Attention!
Use flame scanner FLS 09 UV with type FLUS 06 UV only;
with type FLUS 06 intensity setting to right position: small flame
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 7 / 18
Trouble identification
During that time, the LED changes its radiation intensity antivalently in the cycle rhythm of the monitoring electronics.
1. The flame detector is electrically completely installed and supplied with voltage.
2. Simulation of a flame radiation in front of the sight window of the flame scanner. This can be done with a pocket-
lighter or an other modulated light source (not mains frequency) with sufficient intensity, e.g. when moving
spread fingers between the light source and the flame scanner, the light of a lamp can be sufficiently modulated.
3. The analysis unit must switch on its outlet contacts. This is proved by the red LED going out and the lighting-up
of the green LED. The two-stage intensity indicator lights up (bridge of terminal 7-8 or external display
connected). In case of problems, the outlet contact should be checked at first. In case of a longer modulation (>
5 seconds), you can note the change between the two processing channels when the green 'Flame existing'
LED becomes brighter or darker in a certain rhythm.
Technical Documentation
1-8254-8015a/02
Page 8 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
The flame radiation can be measured between the blue wire (mass) and the pink wire (measuring line) of the scanner
connection line. For this purpose, a standard volt-free measuring instrument e.g. a manual multimeter that corresponds
with the directive EN 61010 with a measuring resistance > 5 MΩ must be used.
The table below specifies the values with which the scanner evaluates signals as flame signal.
For an optimum suppression of background radiation, the values measured after burner shut-down should be clearly
below the specified values.
For a sure recognition of the flame, the double value should be sufficient with a stable signal. In case of an instable
flame recognition, higher values can be required.
In a FLS 09 (IR) it is possible to open the casing and to modify the sensitivity by means of DIP-switches (see Chapter
7). The minimum value for the FLAME ON signal is modified accordingly.
For technical reasons, this is not possible with scanners of type FLS 09 UV. In normal cases, the casing must not be
opened.
See chapter 7
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 9 / 18
Trouble identification
If in case of an excessive temperature rise, there are difficulties with the flame detection when re-starting
the burner, in no case the sensitivity of the flame detector should be increased at once. At first,
wait for the cooling down of the flame scanner.
• Check the sight opening of the flame scanner for possible soiling
• Check whether the ignition flame is burning steadily
• Check if there is sufficient ignition flame to be seen in the sight area of the scanner; if required modify
the pilot burner settings
• Measure the flame radiation that is absorbed by the scanner (pint 4); optimize the alignment inclusive of
the insertion depth in the burner head where required
• in case of an IR-type, increase the sensitivity at the FLUS 06 when necessary
• The red LED goes out and the green LED lights up. The green LED, however, does not change its
brightness in intervals of abt. 3 seconds. That means that there is a common-mode fault (the signal exists
in both evaluation channels simultaneously). This is mainly caused by the interfering radiation from the
ignition transformer and/or its connected lines.
Technical Documentation
1-8254-8015a/02
Page 10 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
• Check the sight opening of the flame scanner for possible soiling
• Check whether the main flame is burning steadily, i.e. it can be seen by the flame scanner over the
complete operation range of the burner
• Measure the flame radiation that is absorbed by the scanner (point 4); optimize the alignment inclusive
of the insertion depth in the burner head where required
• in case of an IR-type, increase the sensitivity at the FLUS 06 when necessary
2. Interfering irradiation prevents a stable detection
• The red LED goes out and the green LED lights up. The green LED, however, does not change its
brightness in intervals of abt. 3 seconds. That means that there is a common-mode fault (the signal exists
in both evaluation channels simultaneously).
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 11 / 18
Trouble identification
As for all flame detection systems on an infrared basis, the specialty of the 'background radiation' (e.g. a
glowing brickwork) in the furnace must be considered. Shutdown tests should therefore be carried out
when the boiler is warm.
The breakaway or extinguishment of the flame must be reproduced. For this purpose, the fuel supply to the burner that
is monitored by the flame scanner must be shut-off.
It must be checked whether the flame detector gives the signal to close the safety shut-off system within a time of tV out ≤
1 s after the flame extinguishment:
With the infrared-type flame scanners FLS 09 (IR) care must always be taken that the sensitivity of the flame detector is
only set as high as necessary to monitor the flame safely and reliably over the complete range of operation of the
burner.
Technical Documentation
1-8254-8015a/02
Page 12 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 13 / 18
Trouble identification
As for all flame detection systems on an infrared basis, the specialty of the 'background radiation' (e.g. a
glowing brickwork) in the furnace must be considered. Shutdown tests should therefore be carried out
when the boiler is warm.
3. Two switches are located on the back of the circuit board. These switches must in all cases be adjusted
symmetrically as described in point 7.2. The setting should always be modified step by step only.
4. Mount the flame scanner again thoroughly. Place the sensor located on the back of the circuit board in
direction of the sight opening of the scanner. Besides, a wrong alignment of the sensor to the sight opening
is prevented by the asymmetrical arrangement of the three screws.
Technical Documentation
1-8254-8015a/02
Page 14 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
Appendix 1
7.2 Adjusting the sensitivity of the flame scanner FLS 09, FLS 09 (-L), FLS 09
(-S)
Sensitivity
OFF ON OFF ON
1
35% min
S1
S2
<1> 4
1
S1
S2
S1
<2> FLS09 (-S) factory setting 4 50%
1
S1
S2
4 S2
<3> 80%
1
S1
S2
Attention!
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 15 / 18
Trouble identification
Appendix 2
7.3 Special remarks for GLS burners (Teminox)
for mounting the IR-flame scanner FLS 09-L (long version)
C
D
A
E
F
A- Mounting depth
B- Connection cable
C- Clip
D- Scanner mount
E- Burner casing
F- Gas ring
G- Light entry opening
Optimum mounting conditions were tested for the GLS burners of type series 75 - 125. For an optimum flame
detection in combination with an optimum extraneous light suppression already by constructive means, a
mounting depth (towering-out of the FLS 09-L) of 4 - 6 cm into the mounting opening at the 'burner neck'
at abt. 10 -11 o'clock.
Problems with the ignition load recognition can occur due to a constriction of the ignition gas supply
piping (e.g. from 15 mm to 12 mm). This would result in the fact that the ignition flame burns too faintly
and the ignition load would be set accordingly. Compared with the basic load and the ignition flame,
this ignition load will then result in a decisive loss of intensity for the flame detection.
Technical Documentation
1-8254-8015a/02
Page 16 / 18 2004-01-08
Instructions for servicing and commissioning
FLUS 06 / FLS 09 flame monitoring
Technical Documentation
1-8254-8015a/02
2004-01-08 Page 17 / 18
Compact Burner SKV/SKVGA 68...134
for heavy fuel oil, light oil and gas
SAACKE Service GmbH SAACKE South Africa (Pty) Ltd., SOUTH AFRICA
Südweststraße 13 · 28237 Bremen Phone: +27 21 94 53 806, Fax: +27 21 94 53 808
GERMANY
SAACKE ESPAÑA, SPAIN
Phone: +49 421 64 95 0 Phone: +34 976 48 70 13, Fax: +34 976 48 70 14
Fax: +49 421 64 95 244
EMail: service@saacke.de SAACKE AG, SWITZERLAND
Phone: +41 1 82 15 656, Fax: +41 1 82 15 644
www.saacke.com
SAACKE TURKEY Ltd. Sti, TURKEY
Phone: +90 216 34 93 112, Fax: +90 216 33 03 778
1−2417−4206/02
2001−XX−XX Page 1/XX