Siemens 7sa522 Distance Protection Relay Setting PDF Free
Siemens 7sa522 Distance Protection Relay Setting PDF Free
R0 = 0.255 Ω/KM
X0 = 1.51 Ω/KM
R0 = 0.21998 Ω/KM
X0 = 1.33923 Ω/KM
1 of 25
2.13 Positive & Negative Sequence Line Impedance /KM
R0 = 0.51 Ω/KM
X0 = 3.02 Ω/KM
3.03 Class = PS
2 of 25
3.06 Rct = 4 Ω
4.02 Class = 3P
4.03 Burden = 50 VA
= 0.41067 78.91
3 of 25
6.1.5 Zero Sequence Line impedance per KM
R0 = 0.255 Ω/KM
X0 = 1.51 Ω/KM
= 1.53138 80.41
= 0.40621 79.38
R0 = 0.21998 Ω/KM
X0 = 1.33923 Ω/KM
= 1.35718 80.67
4 of 25
6.3.3 Positive & Negative Sequence Line Impedance /KM
= 0.82134 79
R0 = 0.51 Ω/KM
X0 = 3.02 Ω/KM
= 3.06 80
= 6 x 262.44
= 1574.64 A
= 262.44 A
5 of 25
= 437.4 A
= 100000 / (1.732 x 11 )
= 5248.79 A
= 40 KA
= √3 x 40x 220
= 15241.6 MVA
= 12 KA
= 0.403 / 0.079
= 5.101
= 40 KA
= 40x 220
= 8800 MVA
6 of 25
= 12 KA
0.403 / 0.079
5.101
P.T Ratio
= 800 / 1 x Zpri
( 220/ √3 ) / ( 0.11 / √3 )
= 0.4 X Zpri
Magnitude Angle
Magnitude Angle
7 of 25
(Assumed equal to Line Angle)
= 1.53138 x 12.56
Magnitude Angle
= 1/3 * ((R0/R1) - 1)
= 0.743
= 1/3 * ((X0/X1) - 1)
= 0.916
= 1/3 * ((Z0/Z1) - 1)
Magnitude Angle
= 0.910 -178
= 150.00 MVA
Magnitude Angle
8 of 25
= 3.18 78.91
= 129.07 Ω
= 0.8 x 129.07
= 103.256 Ω
7.2 Arc Resistance (RArc) = = 76KV2/Short ckt. KVA at min. Fault Current
= 1.26 Ω
7.4 For Phase to Earth Fault :- Resistance Tolerance with respect to secondary-Rt-e
= 9.783 Ω
Where,
= 0.63 Ω
9 of 25
= 10.072 Ω
10 of 25
8.1.4 Reactance Reach,X(Z1) = 80% ofProtected line * X1 * C.F
= 1.62 Ω
Selected Setting:
Resistive
Resistive Reach for Ph to Reach for
Reactance Reach, Protected Time
Zone Earth Fault,RE(Z1) Direction Ph to Ph
X(Z1) Length Delay
Fault,R
(Z1)
Zone I 10.072 Forward 0.63 1.62 80% INST
8.2 Zone II: Reach Setting Proposed at (100% of the protected Line +
8.2.2 Resistive Reach For Φ to Φ Faults,R(Z2): = (((100% of Prot. line length x R1) +
= 0.986 Ω
[ { (1 x 12.56 x 0.079) +
= 0.91 ] + 9.783
= 10.397 Ω
= 3.44 Ω
Selected Setting:
11 of 25
Zone II 10.397 Forward 3.44 0.986 100% 0.4
= 220^2 / 100
= 484 Ω
= 55.66 Ω
= 2.06
(Comparing the above value with the reach of prot. line and the longest line at the remote)
= 38 Ω
As the transformer capacities are variable the reach is as calculted from the above 8.3.8 is
taken for reach setting which is nearer to the calculated value at 8.3.5
8.3.8 Resistive Reach For Φ to Φ Faults, = { [(110% of Protected line length x R1) +
x 0.4)+ 0.312
3.132 Ω
8.3.9 Resistive Reach For Φ to E Faults, = { [(110% of Protected line length x R1) +
12 of 25
x 0.4)+ 9.783
12.603 Ω
14.94 Ω
= 0.25 x 0.63
= 0.16 Ω
= 0.25 x 10.072
= 2.52 Ω
= 0.25 x 1.62
= 0.41 Ω
Selected Setting:
13 of 25
8.6 Controlled Zone (Z1B) Reach Setting Proposed at 120% of the Protected Line
= 0.79 Ω
+ Rt-E
+ 9.783
= 10.2164 Ω
= 2.430 Ω
Selected Setting:
Resistive Reach for Ph to Reactanc Resistive Reach
Protected Time
Zone Earth Fault,RE(Z2) Direction e Reach, for Ph to Ph
Length Delay
X(Z2) Fault,R(Z2)
9.4 Uph-e> : Initial Stage for Minor Over voltage 110%of Un= 69.85 Volts
14 of 25
9.9 CURR.SUP.Uph-e>: = ON
= 31.7552 Ω
11.3 Earth Fault Current Pick-up = 20% of rated Full load current / C.T ratio
Setting(3I0>)
= 0.098415 ≈ 0.1 A
= 984 A
15 of 25