You are on page 1of 2

Module 3: Activity No.

3
Experiment No. 3:

Name:
Student No.

Problem:
A 40-TOR, ammonia ice plant operates on a simple saturation cycle with the following
temperatures: condensing temp = 350C and evaporating temp = - 150C. It produces tons
of ice per day at – 60C from water with raw temperature of 25 0C. Draw the cycle on PH
plane and determine:
(a) The tons of ice it can produce in one day at – 8 deg C if the raw
temperature of water is 28 deg C.
(b) COP

35 ℃

3 2
−15 ℃
t2
35 ℃
4 1
−15 ℃
a. Ref .Cap .=40TOR ( 3.5167 kW
1 TOR )( 3600 s
1 hr )=506 404.8
kJ
hr
Ref .Cap=Q s=M i [ C pw ( t s−t f ) + L+C pi ( t f −t e ) ]

506 404.8
kJ
=
Mi
hr 24 hr
4.187[ kJ
kg ∙ K
kJ
( 28−0 ) ℃+335 +2.093
kg
kJ
kg ∙ K
( 0+8 ) ℃ ]
M i=25 915.21003 kg ( 2.205
1 kg
lb
)( 1 ton
2000 lb ) M =28.57
i
tons
day

b.

Ideal COP for cooling;

Q A h1 −h4 kJ
Ideal COP= = where :h1=hg at−15 ℃=1443.9
TP h 2−h1 kg

kJ kJ
h2 ≅ 1707 using diagram for superheated ammonia vaporh 4=h 3=h f at 35 ℃=366.072
kg kg

Ideal COP=
h −h
=
(
1
1443.9 )−( 366.072 )
4
kJ
kg
kJ
kg
Ideal COP=4.1
h −h 2
(1707 kg )−(1443.9 kg )
1 kJ kJ

You might also like