You are on page 1of 2

PROJECT Improvement of Ventilation FACTORY

NAME: System PLACE: Nidec Sankyo P 1


ROOM

B F P t ' Production Area 86.95 m X 29.6 m AREA = 2,569.4 m² H= 10.0 m VOL. = 25,693.7 m³
NAME: t'
INDOOR SUMMER t= 25 °C 50 % x = 0.0102 I 12.6 t RH% x i
CONDITION

t x i t x i t x i t x i t x i
DESIGN

RH%

OUTDOOR 30 °C 0.0176 18

Δ 5 °C 0.0074 5.4
OUTSIDE WALL TIME WINTER
DIRECT-
ION LENGTH X HEIGHT A K Δt SH Δt SH Δt SH Δt SH D Δt TH
S 29.6 m X 1.5 m 44.40 3.94 5 874.68
(G L A S S)
HEAT TRANSFER

E 18.0 m X 1.5 m 27.00 3.94 5 531.90

S 29.6 m X 1.5 m 44.40 78.33 0.58 2,017.2


HEAT TRANSFER
(DIRECT
SUNLIGHT)

E 18.0 m X 1.5 m 27.00 71.67 0.58 1,122.4


(S H A D O
TRANSFER
HEAT

W)

N 29.6 m x 10.0 m 296.00 2.42 5 °C 3,582


(OUTSIDE
HEAT TRANSFER

E 87.0 m x 10.0 m 870.00 2.42 12 °C 25,265


WALL)

W 87.0 m x 10.0 m 870.00 2.42 5 °C 10,527


S 29.6 m x 10.0 m 296.00 2.42 19 °C 13,531
ROOF 87.0 m X 29.6 m 2569.37 1.25 43 °C 138,104
FLOOR 87.0 m x 29.6 m 2569.37 1.87 5 °C 24,024
SUB - TOTAL 219,577
INSIDE WALL

SUB - TOTAL 0

WIND
SH 0.29 X 1 □/h X 15,000.0 m³ m³ X Δ t 5 °C ºC 21,750 1.2 X □/h X m³
ENTERING
LH 710 X 1 □/h X 15,000.0 m³ m³ X Δ x 0.0074 kg/kg' 78,810 X Δi

HEATING LOAD INSIDE THE ROOM S H L H


BULB 0.86 X W/m² X m²
ILLUMINA -
TION
FLOURES CENT 1.0 X 18 Watts X 110 pcs 1,980
ELECT.
POWER 860 X 2264.43 kW X * Xφ 0.42 817,912
PERSON ٨ / m² X m² = 100 ٨ 63 6,300 50.4 5,040
ALL
CONNECTED
TO C.O.
(20% USED)

SUB - TOTAL 826,192 5,040


S H 1,067,520

TOTAL L H 83,850
T H 1,151,370
1 1-ɳ
REMARKS NOTE:
* ɳ F, F, ɳ F x 1.10 = 1,266,507 kCal/hr 492.92 kcal / m² kcal / m²
= 418.8 TR