You are on page 1of 1

4.

4 BASE PLATE AND ANCHOR BOLT CHECK

DESIGN OF BASE PLATE


STRUCTURE: XFR AREA J
Column Mark : UC-203 UC203X203X46
1. DESIGN FORCES SUMMARY
UC-203 STAAD OUTPUT DESIGN FORCES
DESCRIPTION Fx Fy Fz Axial (F) (Fy2+Fz2)0.5 Friction (f) Shear
Condition Beam L/C NODE (kN) (kN) (kN) F = Fx (kN) Q (kN) f=0.45F (kN) Q - f (kN)

Max Compression 2027 456 255 232.8 30.2 3.3 232.8 30.4 104.8 0.0
Max Tension 2001 595 245 -13.9 10.5 0.0 -13.9 10.5 0.0 10.5
Max Shear 2030 595 256 -7.2 22.9 -0.5 -7.2 22.9 0.0 22.9
F = Fc (Axial Compression) if value is positive, F = Ft (Axial Tension) if values is negative
2. MATERIAL PROPERTY AND DIMENSION
Steel Column : D= 203.2 mm
B= 203.6 mm
t= 7.2 mm
T= 11.0 mm
Base Plate : Pyp = 265.0 Mpa (S275)
Dp = 250.0 mm
Bp = 250.0 mm
tp = 22.0 mm
Anchor Bolt : Grade : 4.6
db = 24.0 mm
n= 2.0 pcs
Effective Area per bolt (Aeperbolt) = 353.0 mm2
Effective Area of bolts (Aebolts) = 706.0 mm2
3. CHECK FOR CONCRETE BEARING STRENGTH (4.13.1 of BS 5950-1:2000)
fcu = 30.0 Mpa Fc / BpDp = 3.7 Mpa < 0.6fcu OK!
0.6fcu = 18.0 Mpa Areq = Fc / 0.6Fcu
Fc = 232.8 kN (Maximum Compression Force) = 12,933.3 mm2
4. CHECK FOR BASE PLATE THICKNESS BY EFFECTIVE AREA METHOD (sec 4.13.2.2 of BS 5950-1:2000)

0.5
base plate thickness (tpreq) = c (3x0.6f cu/Pyp) Column Perimeter (Percol) = 1,190.0 mm
2
effective area (Aeff) = 4c1 + c1(Percol) + Acol (Assuming no Overlap of Effective Area) Area of Steel Column Acol = 5,870.0 mm2
effective area (Aeff) = 4c2 2 + 2(D + B)c2 + DB (Assuming Effective Area has Overlap)
solving for c by equating Aeff to Areq : 12,933.3 = 4c12 + 1,190.0c1 + 5,870.0 c1 = 5.82 mm
2
12,933.3 = 4c2 + 813.6c2 + 41,371.5 c2 = -44.84 mm
(D-2T )/2 = 90.6 mm > c1, effective area has no overlap (use value of c1 for c)
D +2c = 214.84 mm < Dp
B + 2c = 215.24 mm < Bp
Hence the calculated value of c is valid.
c= 5.82 mm
tpreq = 2.7 mm < tp, OK!