Professional Documents
Culture Documents
~\
~\-*\, a;1:..i\o~'i ~b.1\ w~\yJ\
SECTION 15860:
KIN.GDOM
OFSAUDIARABIA ~~~1 4IrtJl~I
RoyalCommissionlor Jubail & Yanbu ~1~~1~1
SECTION 15860
AIR CLEANING DEVICES
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 2
1.05 SUBMITTALS....................................................................................................... 3
3.03 INSTALLATION.................................................................................................. 23
PART 1 GENERAL
A. This Section describes the cleaning of particulate contaminants from both ventilation
air and re-circulated air for the conditioning of building interiors.
C. This Section covers the furnishing, installation, and testing of HVAC Air Cleaning
Devices in the location and quantities shown on the drawings. The Contractor shall
furnish all labor, materials, tools, and equipment required to complete the work.
M. Sterilizing Filters
O. Filter Gages
O. Section 15955 Testing, Adjusting and Balancing of Air and Hydronic System
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
Engineers Inc.
1.05 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
work:
3. Samples
a) Two samples of replacement filter media of each type and each filter
frame.
5. Qualification of Manufacturers
b) Holding Frames
1) Identify locations.
d) HEPA filters.
e) Gages.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
B. The Contractor’s internal quality control shall include but not be limited to:
1. Submit a test report for each Grade of filter being offered. The report shall be
less than 5 years old and shall have been prepared by an independent testing
laboratory using test equipment, method and duct section as specified by
ASHRAE Standard 52.1 for type of filter under test and acceptable to the
Royal Commission, indicating that filters comply with the requirements of this
Specification. Test for 150 m/min. (500 fpm) will be accepted for lower velocity
rated filters provided the test report of an independent testing laboratory
complies with all the requirements of this Specification.
2. Selection Procedures
a) All filters tested shall have been procured by the independent testing
laboratory from the open market independent of manufacturer of these
filters and a statement to this effect must accompany test report.
3. The Royal Commission at its option may take one of the filters for each
different type submitted and run an independent test to determine if the filter
meets the requirements of this Specification. When the filter does not meet the
specification requirements, the manufacturer will be required to pay for the
test and replace the filters with filters that will perform as required by the
specifications.
1. Guarantee the filters against leak, blow-outs and other deficiencies during
their normal useful life. Defective filters shall be replaced at no cost to the
Royal Commission.
E. Nameplates
1. Each filter shall bear a label or name plate indicating manufacturer's name,
filter size, rated efficiency, UL classification and file number.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
1. All re-circulating and outside air systems shall be provided with air filters. Filter
type and efficiency shall be based on the required cleanliness of the supply
air, to meet the objectives of the conditioned space.
3. Filters installed close to an air inlet shall be protected from the weather by
suitable louvers. A large mesh 12 mm wire screen also shall be provided.
4. Filters shall have permanent indicators to give a warning when the filter
resistance reaches the recommended change value.
5. Air filters shall be provided with access doors, sized to allow filter
maintenance.
8. All filters shall conform to UL 900 Class 2 for combustibility and smoke
generation. Systems serving critical areas carrying flammable gases shall
have the additional fire resistance of Class 1 filters when specified by the
Royal Commission.
10. Glass fibrous media filter, having a 90 to 95% average atmospheric dust spot
efficiency shall be provided for computer rooms.
1. A sand trapping box (STB) shall be provided for the fresh air inlet of each
HVAC system servicing areas housing vital equipment.
4. STB casing shall be rigidly constructed with steel sheets and supporting
members.
5. STB shall capture sand in the fresh air at the sand louver and the sand shall
be exhausted out of the STB by the bleed fan.
1. Chemical filter units shall be skid-mounted and selected for both corrosion
control and pressurization based on project requirements.
2. Chemical filter media shall be selected based on air quality at the project site
to provide ISA S71.04 severity level G1 quality air to the spaces served. The
levels for benzene, vinyl chloride monomer and ethylene di-chloride shall be
controlled to 0.1 ppm.
3. Chemical filters shall be provided for the fresh air intake of control buildings,
remote instrument enclosures and other buildings requiring corrosion
protection for electronic equipment.
4. Chemical filters shall also be provided for other buildings in the plant where
the possibility of high concentrations of harmful gases exists in the area or as
specified by the Royal Commission.
A. The Contractor shall deliver, handle and store materials in accordance with
SECTIONS 01650 and 01660, as well as the following requirements
1. Protect products against dirt, water and chemical and mechanical damage. Do
not install damaged parts; remove from project site.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
2. Filter shall be made of coarse fibers with high porosity. The filter media shall
be coated with a non-flammable viscous substance.
3. The thickness of the filter shall be between 12.5 and 100 mm (½ to 4 in.) as
required or indicated in the Contract Documents.
5. Holding frame shall be of 0.91 mm (20 gage) galvanized steel and shall be
gasketed to prevent unfiltered air by passing between media frames and
holding members.
6. Filters shall be with rated face velocity of 2.5 m/s (500 ft/min), initial resistance
of not greater than 75 Pascal (0.3 in. wg.), final rated resistance of 125 Pa
(0.5 in. wg.) and average arrestance of 80%.
B. Washable type air filters shall be highly efficient made up of 1.5 mm thick extruded
aluminum channel. Filter media shall be of multi-layer aluminum wire screen and
covered by expanded slit bonded layers of aluminum mat mesh.
C. Media
a) Frame
1) 1.52 mm (16 gage) galvanized steel, OR
2) 0.91 mm (20 gage) stainless steel, OR
3) Aluminum.
b) Nominal Size
1) 400 x 500 mm (16 x 20 in.).
c) Thickness
1) 25 mm (1 in.) thick.
D. Performance Rating
A. Use factory assembled air filters of the extended surface type with supported or
non-supported cartridges for removal of particulate matter in air conditioning, heating
and ventilating systems. Filter units shall be of the extended surface type fabricated
for disposal when the dust-load limit is reached as indicated by maximum (final)
pressure drop.
B. Filter Classification
1. Grade A: 90 to 95 after-filter.
2. Grade B: 80 to 85 after-filter.
3. Grade C: 50 to 60 pre-filter.
4. Grade D: 25 to 30 pre-filter.
D. Filter Media
b) A metal grid backing shall be bonded to the air leaving side of the
media to maintain uniform pleat shape and stability for proper air flow
and maximum dust loading.
F. Maximum initial and final resistance, Pa (inches of water), for each filter cartridge
when operated at 150 m/min (500 feet per minute) face velocity shall be as per
Table 2B.
1. When tested to 250 Pa (1 in. water) at 150 m/min (500 fpm) face velocity, the
dust holding capacity for each 600 by 600 mm (24 x 24 in.) (face area) filter
shall be at least the values listed below. For other filter sizes, the dust holding
capacity shall be proportionally higher or lower to the face area. Refer to
Table 2C.
1. The minimum net effective media area in square meter (square feet) for each
600 x 600 mm (24 x 24 in.) (face area) filter at 150 m/min (500 fpm) face
velocity shall be at least the values listed below.
2. For other filter sizes the net effective media area shall be proportionally higher
or lower. Refer to Table 2D.
2. Access Doors
1. Minimum 1.52 mm (16 gage) galvanized steel, 100 mm (4 in.) deep, factory
complete with hardware necessary for field assembly, suitable for either
upstream or downstream filter servicing. All members shall be cut to size and
pre-punched for easy assembly into modules of the size and capacity noted in
the schedules.
L. Factory-fabricated, dry, extended surface filters with holding frame in sizes indicated
in Project Documents.
M. Holding frames shall be of 1.21 mm (18 gage) galvanized steel provided with
suitable fasteners and gasketing to hold media and media frame and to prevent
unfiltered air passing between media frames.
N. Filters shall be with rated face velocity of 2.5 m/s (500 ft/min), initial operating
resistance of 62 Pa (0.25 in. wg.) with 60 to 65% dust spot efficiency and 100 Pa
(0.40 in. w.g) with 80 to 85% efficiency and 175 Pascal (070 in. wg.) with 90 to 95%
efficiency and final rated resistance of 250 Pascal (1.0 in. wg.).
A. High Efficiency Particulate Air (HEPA) filters shall be individually tested and certified
to be 99.97% minimum efficient when handling 0.3 micron particles in accordance
with DOP test method. Filters shall be factory scanned. The DOP efficiency along
with filter serial number and name of manufacturer shall be marked on the filter.
HEPA filter shall have maximum pressure drop of 250 Pa (1 in. wg.) when clean, at
rated flow with a final pressure drop of 500 Pa (2 in. wg.).
B. Filter Media
a) Media
1) UL 586, pleated, water-resistant glass fiber with separators of
aluminum.
(a) Holding Frame: Plywood.
(b) Media to Frame Side Bond: Polyurethane foam.
(i) Face Gasket: Neoprene expanded rubber.
(c) Nominal Size: 610 x 610 x 300 mm (24 x 24 x 12 in.)
deep.
b) Performance Rating
1) MIL-STD-282 Test 0.3 Micron Dioctyl Phthalate Smoke (DOP)
Efficiency
(a) 99.97%.
2) Rated Air Flow Capacity at 250 Pa (1 in. wg.)
C. Enclosing frame shall be 1.52 mm (16 gage) galvanized steel. Provide pre-filters in
the same housing with a separate removal assembly that operates independently
from the HEPA filters.
D. Pre-Filter
A. Housing shall be fabricated of 1.71 mm (15 gage) Type 304 stainless steel.
B. Housing shall be equipped with weather covers, drilled face flanges and factory
mounted gages with Petcocks housed in stainless steel brackets.
C. Housing shall be pressure tested in factory for high quality to withstand a positive or
negative pressure of 2.5 kPa (10 in. wg.). If HEPA filters are specified for TB
Isolation Rooms, perform a quantitative leakage and filter performance DOP (Dioctyl
Phthalate Penetration) field test in addition to factory test at the initial installation
recommended by the Center for Disease Control (CDC).
D. Housing shall incorporate a spring loaded clamping mechanism that is operated from
outside and which is capable of exerting a 5340 N (1,200 lb.) sealing force across
the top and bottom of each filter.
E. Each housing shall have a bagging ring around the access port that is sealed by a
removable, gasketed access door. The bagging ring shall have 2 continuous ribs to
secure the plastic change-out bag and be hemmed on its outer edge to prevent the
bag from tearing.
F. One 2.2 mm (87 mil) thick PVC change-out bag shall be supplied for each access
door. The bag shall include approximately 300 mm (12 in.) of transparent PVC at the
open end and three glove sleeves built into the body to assist in filter change-out.
Bag-In/Bag-Out housings shall be manufactured under a quality assurance program
that addresses the requirements of ANSI N45.2, “Quality Assurance Requirements
for Nuclear Power Plants.”
1. Factory fabricated, automatic, motor driven, roll type filter with holding casing.
4. Equip filter drive with manual media advance and run-out switches for
stopping media movement of filter bank and operating remote warning signal
lights.
B. Assembly
1. Galvanized steel assembly with drive, controls, and media, which feeds media
across air stream, winds and compresses used media for disposal.
2. Enclose the clean media roll with hinged roll cover. Include tension panel to
compress used media as it is spooled.
C. Media
1. UL 900 Class 2, rolled and compressed, graduated density glass fiber blanket,
nominally 50 mm (2 in.) thick when expanded, 15 m (50 ft.) long; factory
sprayed with flameproof, non-drip, non-volatile adhesive; bonded reinforcing
on leaving side of media to prevent stretching and necking.
E. Drive Mechanism
2. Hand crank for manual operation to rewind spool through chain and sprocket
assembly.
F. Controls
period of time, with media run out switch to stop travel and indicate run out
and manual switch to override controls and advance media.
G. Frame
3. Removable carbon cell trays of 0.45 mm (26 gage) coated perforated steel
and steel framing.
4. Filters with rated face velocity of 500 fpm and resistance of 87 Pascal
(0.35 in. wg.).
B. Assembly
C. Nominal Size
D. Media
3. Trays
4. Carbon
a) 22 kg per 470 L/s (1.42 ft³ /1000 cfm) nominal air flow capacity.
E. Rating
1. 2.54 m/s (500 fpm) face velocity, 110 Pa (0.45 in. wg.) resistance.
A. Media
a) Frame: Non-flammable.
3. Initial Resistance at 2.54 m/s (500 fpm) Face Velocity: 50 Pa (0.20 in. wg).
A. Media
b) Thickness: 25 mm (1 in).
B. Performance Rating
C. Casing
1. Cardboard frame
D. Holding Frames
1. 0.91 mm (20 gage) minimum galvanized steel frame with expanded metal grid
on outlet side and steel rod grid on inlet side, hinged with pull and retaining
handles.
A. Media
3. Initial Resistance at 0.63 m/s (150 fpm) Face Velocity: 87 Pa (0.35 in. wg).
A. Media
1. UL 900 Class 1 reinforced glass fiber preformed into series of pockets with
media spacing controls by variable length stitches; galvanized steel header
frame.
a) Media Area
1) 6.9 m² of media per 1000 L/s (35 ft² per 1000 cfm) capacity.
b) Nominal Size
2) 610 x 610 mm (24 x 24 in.) face, 560 mm (22 in.) deep.
A. Media
b) Nominal Size
2) 610 x 610 x 300 mm (24 x 24 x 12 in.) deep.
5. Recommended Final Resistance: 125 Pa (0.5 in. wg.) above initial resistance.
2. Holding frame shall be predrilled for convenient assembly into banks. They
shall be installed to provide service from the dirty airside.
cartridge type, of sufficient size and capacity to clean the specified air volume with
an average dust weight arrestation of 95% or greater on ASHRAE Test
Standard 52.
1. Agglomerator Framework
2. Agglomerator Cells
3. Power Pack
c) The panel fronts shall also include lamps to indicate the operating
condition of the unit. A safety switch shall be provided to ensure that the
power pack is de-energized when the power pack door is opened.
4. Storage Section
A. General
B. Standard Sizes
A. Provide sand trap louvers where indicated on plans to perform initial separation of
airborne sand and dust mixtures.
C. All louvers shall be furnished with self-emptying sand drain holes and wire mesh bird
screens.
1. Diaphragm-type filter gage for each filter bank, with dial and pointer,
graduated to read from 0 to 500 Pa.
2. Manometer-type filter gage for each filter bank, with logarithmic curve tube
gage, with integral leveling gage, graduated to read from 0 to 750 Pa.
A. Assembly
B. Electronic Agglomerator
C. Power Pack
D. Safety Accessories
1. Manual reset safety switches and warning lights for filter plenum access
doors, signal lights and safety switching upstream and downstream of unit
within duct, and enameled high voltage warning signs.
PART 3 EXECUTION
A. The Contractor shall examine locations with instruments to verify that conditions for
installing air handling systems are satisfactory. Work shall not proceed until
unsatisfactory conditions have been corrected in a manner acceptable to the
installer.
B. Under no circumstances shall any air handling unit or fan coil unit which is shown or
specified to be furnished with filters be operated without filters in-place. Filters on
units during construction shall be replaced as necessary and as directed by the
Royal Commission.
B. Coordinate control work with work of other trades for proper time and sequence to
avoid delays.
C. In the event that units are operated without filters in-place or with filters which have
been damaged so as to allow air to bypass filter, the Contractor shall steam clean all
coils and fans in that particular system before balancing the system.
D. In all cases, filters shall be of the proper size and installed in filter racks in such a
manner that there will be no leakage of air around filters. Filters which have been
torn, distorted, or damaged in any other way will not be acceptable.
E. All testing and balancing of air-side systems shall be done using clean filters.
3.03 INSTALLATION
A. General
1. Before commencing installation work, the Contractor shall visit the site to
thoroughly familiarize himself with all details of the work and working
conditions. He shall check whether holes, openings, chases and the like
which he requires have been executed and are adequate. Should any
amendment in size or position of any hole, opening or chase be necessary,
this amendment shall be notified to the Royal Commission immediately.
2. Built-up central HVAC systems shall be provided with pre-filters and final
filters.
B. Electronic air cleaners or washable type filters shall be installed in the outdoor air
intake ducts of building including sand trap and volume damper.
C. Filters
1. Install air filters and holding devices in accordance with air filter
manufacturer’s instructions.
2. Air filters shall be installed ahead of cooling coils, heating coils and other air
conditioning equipment in the system to protect them from dust.
4. Duct connection to and from the filter should change size or shape gradually
to ensure even air distribution over the entire filter area.
6. Access door of convenient size shall be provided to the filter service areas
and shall have lockable latches for easy opening during maintenance and
inspection.
8. Electric lights shall be installed in the plenum in front of and behind the air
filter.
9. Filters installed close to an air inlet shall be protected from the weather by
suitable louvers or inlet hood. A large mesh wire bird screen and sand trap
shall be placed in front of the louvers or in the hood.
10. Filters, other than electronic air cleaners, shall have permanent indicators to
give a warning when the filter resistance reaches too high a value or is
exhausted, as with automatic roll media filters.
11. Electronic air cleaners shall have an indicator or alarm to indicate when high
voltage is off or switched out.
12. Install filter gage static pressure tips upstream and down stream of filters.
Mount filter gages on outside of filter housing or filter plenum, in accessible
position. Adjust and level.
13. Do not operate fan system until filters (temporary or permanent) are in place.
Replace temporary filters used during construction and testing, with clean
sets.
14. Filters shall be cleaned or replaced prior to system balancing, when dust
loading exceeds the manufacturer’s recommendations.
16. Filters of packaged air handling units and filters of any residential HVAC
system shall be replaceable media or washable material with a minimum 70%
weight arrestance rating (ASHRAE STD 52).
17. The air velocity through filters shall not exceed 3 m/s and dirty pre-filters
pressure drop shall not be greater than 125 Pa (0.5 in. wg.) or final filter
pressure drop greater than 250 Pa (1 in. wg.). Pre-filters and final-filters shall
be upstream of coils and fans.
18. Air filter devices shall be provided to air conditioning unit for cleaning of all the
air passing through the evaporator coil. Air filter performance shall be rated
and tested in conformance with UL 900 Class 1 or ARI 850. Vendor to provide
at least 2 sets of the required number of filters installed for each unit.
20. Filter surface shall be such that air filter operates at its optimum face velocity
for efficiency.
21. Filters shall be located so they are readily accessible and easily removable for
cleaning and replacement.
22. Access door shall be provided on both sides of the unit for easy filter
replacement. For unit up to 2 m wide, a single access door is acceptable.
23. Filter box shall have a calibrated gage installed for monitoring the pressure
drop across the filters. The gage shall read up to 500 Pa (2 in. wg.). A
securely mounted tubing network shall be used to make an average reading
across the filters.
24. Air handling unit filter shall be high efficiency bag filter or washable material
with a minimum Dust Spot Efficiency of 25 and 90% weight arrestance rating
(ASHRAE 52).
a) Sand trap louver, pre-filter (inertial filter), or viscous oil filter or media-
filter capable of 25% minimum Dust Spot Efficiency and 90% weight
arrestance (ASHRAE 52).
26. The air velocity through pre-filters shall not exceed 3.05 m/s (600 fpm) and
dirty pre-filter pressure drop shall not be greater than 125 Pa (0.50 in. wg.).
27. The air velocity through high efficiency filter shall not exceed 1.3 m/s
(255 fpm) and dirty filter pressure drop shall not be greater than 250 Pa
(1 in. wg.).
B. Consider the use of pre-filter with high efficiency units for longer service life.
D. Use a draft gage on constant volume systems to determine when a filter should be
serviced.
F. Select filters carefully when variable air volumes are involved (Volume less than 20%
or more than 30% of normal rating may be encountered which require careful
selection for optimum performance).
I. Do not exceed manufacturer’s recommended final resistance values for any given
filter.
J. Do not forget lint in atmospheric dust is difficult to remove from viscous impingement
filters and can cause electrical short circuit in electrostatic air cleaners.
A. Clean and vacuum air handling units and plenums to the satisfaction of the Royal
Commission prior to starting air handling systems.
C. Upon completion of the project and before final acceptance, all disposable filters
shall be replaced with new filters. This requirement is in addition to the requirement
that a stock of replaceable filters, sufficient to replace all filters in the project one
time, be left for the Royal Commission's maintenance use.
END OF SECTION