Alarm collecting board PBA-ALMCLU 3AL 43185

AAAA
not permitted without written authorization from Alcatel.
document, use and communication of its contents
All rights reserved. Passing on and copying of this

Function
The ALMCLU board provides the interface between up to 24 alarm inputs (external contacts) and the CNCC4.

Features
The PBA-ALMCLU board has the following features:
 A maximum of 24 alarm inputs can be connected.
 Each alarm input can be individually enabled or disabled.
 The status which represents an alarm state can be inverted for each alarm input individually.
 Each alarm input can use a 1-wire or a 2-wire interface individually.
 The ALMCLU board is managed via the CNCC4 board through the low speed Q1 bus using the clock
to shift out the alarms to the CNCC4.

Operational data
Alarm input device:
An opto-coupler is used on the ALMCLU to isolate the alarm inputs from the electronics on the board:
 Internal resistance : 15 kΩ..
 Activation current: 2 mA minimum.
 Deactivation current: 0.7 mA maximum.
 Allowable current: 50 mA maximum.
Power supply:
 Nominal station battery voltage: -48 V or -60 V.
 Operating voltage range: ranges from -36 V to -72 V.
 Power consumption: 4.8 W (for nominal supply voltage -48 V).
Fuse: 1A / 250V (quick).

DOCC: *NA
MMCC: *NA
20000913

3AL 43185 AAAA TNAAA Ed. 02 1/6


3AL 43185 Alarm collecting board PBA-ALMCLU
AAAA

not permitted without written authorization from Alcatel.


document, use and communication of its contents
All rights reserved. Passing on and copying of this
Wiring of alarm input interface
1. When used as a 1-wire interface, one pole of an external contact will be connected to the a-connector of
an alarm input, using 1 wire. The other pole of the external contact will be connected to battery return (refer
to Fig. 1).

AL

Alarm input 24

Alarm
indicator
ALM 0Xa
EMC
External Enable / Disable
Inv selection
contact ALM 0Xb Alarm
input X
BATR BAT1&2 Invert
selection

ALM 0Xa and ALM 0Xb (with x from 1 to 24) are connectors on the front
connector C (refer to Fig. 4)

Figure 1 Wiring of an external contact in case of a 1-wire interface

2. When used as a 2-wire interface, the alarm input will be connected using 2 wires to both poles of an
external contact (refer to Fig. 2).

AL

Alarm input 24

Alarm
indicator
ALM 0Xa
EMC
External Enable / Disable
Inv selection
contact ALM 0Xb
Alarm
input X
BATR BAT1&2 Invert
selection

ALM 0Xa and ALM 0Xb (with x from 1 to 24) are connectors on the front
connector C (refer to Fig. 4)

Figure 2 Wiring of an external contact in case of a 2-wire interface

2/6 3AL 43185 AAAA TNAAA Ed. 02


All rights reserved. Passing on and copying of this
document, use and communication of its contents
not permitted without written authorization from Alcatel.

Figure 3
Front view

3AL 43185 AAAA TNAAA Ed. 02


Front view
Alarm collecting board PBA-ALMCLU

2x32-pin connector (C)


(detail see next page)
AAAA
3AL 43185

3/6
3AL 43185 Alarm collecting board PBA-ALMCLU
AAAA

not permitted without written authorization from Alcatel.


document, use and communication of its contents
All rights reserved. Passing on and copying of this
Front connectors
Connector C : Input and output signals :

CA01 : ALM 01a CB01 : ALM 01b


CA02 : ALM 02a CB02 : ALM 02b
CA03 : ALM 03a CB03 : ALM 03b
CA04 : ALM 04a CB04 : ALM 04b
CA05 : ALM 05a CB05 : ALM 05b
CA06 : Safety ground CB06 : Safety ground
CA07 : ALM 06a CB07 : ALM 06b
CA08 : ALM 07a CB08 : ALM 07b
CA09 : ALM 08a CB09 : ALM 08b
CA10 : ALM 09a CB10 : ALM 09b
CA11 : ALM 10a CB11 : ALM 10b
CA12 : Safety ground CB12 : Safety ground
CA13 : ALM 11a CB13 : ALM 11b
CA14 : ALM 12a CB14 : ALM 12b
CA15 : ALM 13a CB15 : ALM 13b
CA16 : ALM 14a CB16 : ALM 14b
CA17 : ALM 15a CB17 : ALM 15b
CA18 : Safety ground CB18 : Safety ground
CA19 : ALM 16a CB19 : ALM 16b
CA20 : ALM 17a CB20 : ALM 17b
CA21 : ALM 18a CB21 : ALM 18b
CA22 : ALM 19a CB22 : ALM 19b
CA23 : ALM 20a CB23 : ALM 20b
CA24 : Safety ground CB24 : Safety ground
CA25 : ALM 21a CB25 : ALM 21b
CA26 : ALM 22a CB26 : ALM 22b
CA27 : ALM 23a CB27 : ALM 23b
CA28 : ALM 24a CB28 : ALM 24b
CA29 : Safety ground CB29 : Safety ground
CA30 : Safety ground CB30 : Safety ground
CA31 : Safety ground CB31 : Safety ground
CA32 : Safety ground CB32 : Safety ground

Figure 4 Front connector

4/6 3AL 43185 AAAA TNAAA Ed. 02


Alarm collecting board PBA-ALMCLU 3AL 43185
AAAA
not permitted without written authorization from Alcatel.
document, use and communication of its contents
All rights reserved. Passing on and copying of this

S410 S412
S430 S432
S450 S452
S470 S472
S490 S492
S41010 S41012
S510 S512
S530 S532
S550 S552
S570 S572
S590 S592
S51010 S51012
S610 S612
S630 S632
S650 S652
S670 S672
S690 S692
S61010 S61012
S710 S712
S730 S732
S750 S752
S770 S772
S790 S792
S71010 S71012

X269

F253

Figure 5 Position of the straps on the board

3AL 43185 AAAA TNAAA Ed. 02 5/6


3AL 43185 Alarm collecting board PBA-ALMCLU
AAAA

not permitted without written authorization from Alcatel.


document, use and communication of its contents
All rights reserved. Passing on and copying of this
Alarm indicators
The ALMCLU is provided with the following LED indicators (refer to Figure 3).
 PW (green LED): indicates the presence of the +5V power supply.
 AL (red LED): indicates that one or more alarm inputs are active.

Strap options
For the location of the jumpers: refer to Figure 5.

Strap/switch Position Action

A +5V power connected to CCT.


X269
B +5V power disconnected from CCT.
S410, S430, S450, S470, S490, S4010, A Alarm input condition inverted
S510, S530, S550, S570, S590, S5010,
S610, S630, S650, S670, S690, S6010,
B Alarm input condition not-inverted
S710, S730, S750, S770, S790, S7010
S412, S432, S452, S472, S492, S4012, A Alarm input inhibited
S512, S532, S552, S572, S592, S5012,
S612, S632, S652, S672, S692, S6012,
B Alarm input enabled
S712, S732, S752, S772, S792, S7012

6/6 3AL 43185 AAAA TNAAA Ed. 02