Professional Documents
Culture Documents
ON
2017 - 2018
1 .7 6 4 7 j 7 .0 5 8 8 0 .5 8 8 2 j 2 .3 5 2 9 0 1 .1 7 6 5 j 4 .7 0 5 9
0 .5 8 8 2 j 2 .3 5 2 9 1 .5 6 1 1 j 6 .6 2 9 0 0 .3 8 4 6 j1 .9 2 3 1 0 .5 8 8 2 j 2 .3 5 2 9
Ybus
0 0 .3 8 4 6 j1 .9 2 3 1 1 .5 6 1 1 j 6 .6 2 9 0 1 .1 7 6 5 j 4 .7 0 5 9
1 .1 7 6 5 j 4 .7 0 5 9 0 .5 8 8 2 j 2 .3 5 2 9 1 .1 7 6 5 j 4 .7 0 5 9 2 .9 4 1 2 j1 1 .7 6 4 7
The basic equation for power-flow analysis is derived from the nodal analysis
equations for the power system:
Y b u sV I (11.9.1)
Y1 1 Y1 2 Y1 3 Y1 4 V1 I1
Y Y22 Y23 Y24 V2 I2
21 (11.9.2)
Y31 Y32 Y33 Y34 V 3 I3
Y41 Y42 Y43 Y44 V
4 I4
where Yij are the elements of the bus admittance matrix, Vi are the bus voltages,
and Ii are the currents injected at each node. For bus 2 in this system, this equation
reduces to
Y 2 1V 1 Y 2 2 V 2 Y 2 3V 3 Y 2 4 V 4 I 2 (11.9.3)
However, real loads are specified in terms of real and reactive powers, not as
currents. The relationship between per-unit real and reactive power supplied to
the system at a bus and the per-unit current injected into the system at that bus is:
S VI P jQ
*
(11.10.1)
where V is the per-unit voltage at the bus; I* - complex conjugate of the per-unit
current injected at the bus; P and Q are per-unit real and reactive powers.
Therefore, for instance, the current injected at bus 2 can be found as
P2 jQ 2 P2 jQ 2
V 2 I 2 P2 jQ 2 I 2 I 2
* *
(11.10.2)
*
V2 V2
Substituting (11.10.2) into (11.9.3), we obtain
P2 jQ 2
Y 2 1V 1 Y 2 2 V 2 Y 2 3V 3 Y 2 4 V 4 *
(11.10.3)
V2
Solving the last equation for V2, yields
1 P2 jQ 2
V2 *
Y 2 1V 1 Y 2 3V 3 Y 2 4V 4 (11.11.1)
Y22 V2
Similar equations can be created for each load bus in the power system.
(11.11.1) gives updated estimate for V2 based on the specified values of real and
reactive powers and the current estimates of all the bus voltages in the system.
Note that the updated estimate for V2 will not be the same as the original estimate
of V2* used in (11.11.1) to derive it. We can repeatedly update the estimate wile
substituting current estimate for V2 back to the equation. The values of V2 will
converge; however, this would NOT be the correct bus voltage since voltages at
the other nodes are also needed to be updated. Therefore, all voltages need to be
updated during each iteration!
The iterations are repeated until voltage values no longer change much between
iterations.
This method is known as the Gauss-Siedel iterative method. Its basic procedure
is:
1. Calculate the bus admittance matrix Ybus including the admittances of all
transmission lines, transformers, etc., between busses but exclude the
admittances of the loads or generators themselves.
2. Select a slack bus: one of the busses in the power system, whose voltage will
arbitrarily be assumed as 1.00˚.
3. Select initial estimates for all bus voltages: usually, the voltage at every load
bus assumed as 1.00˚ (flat start) lead to good convergence.
4. Write voltage equations for every other bus in the system. The generic form is
1 Pi jQ i
N
Vi
Y ii Vi
*
ik k
Y V (11.12.1)
k 1
k i
5. Calculate an updated estimate of the voltage at each load bus in succession
using (11.12.1) except for the slack bus.
6. Compare the differences between the old and new voltage estimates: if the
differences are less than some specified tolerance for all busses, stop.
Otherwise, repeat step 5.
7. Confirm that the resulting solution is reasonable: a valid solution typically has
bus voltages, whose phases range in less than 45˚.
Example 11.2: in a 2-bus power system, a generator
attached to bus 1 and loads attached to bus 2. the
series impedance of a single transmission line
connecting them is 0.1+j0.5 pu. The shunt admittance
of the line may be neglected. Assume that bus 1 is the
slack bus and that it has a voltage V1 = 1.00˚ pu. Real
and reactive powers supplied to the loads from the
system at bus 2 are P2 = 0.3 pu, Q2 = 0.2 pu (powers
supplied to the system at each busses is negative of
the above values). Determine voltages at each bus for
the specified load conditions.
1. We start from calculating the bus admittance matrix Ybus. The Yii terms can be
constructed by summing the admittances of all transmission lines connected to
each bus, and the Yij terms are the negative of the admittances of the line
stretching between busses i and j. For instance, the term Y11 is the sum of the
admittances of all transmission lines connected to bus 1 (a single line in our case).
The series admittance of line 1 is
1 1
Y lin e 1 0 .3 8 4 6 j 1 .9 2 3 1 Y1 1 (11.14.1)
Z lin e 1 0 .1 j 0 .5
2. Next, we select bus 1 as the slack bus since it is the only bus in the system
connected to the generator. The voltage at bus 1 will be assumed 1.00˚.
3. We select initial estimates for all bus voltages. Making a flat start, the initial
voltage estimates at every bus are 1.00˚.
4. Next, we write voltage equations for every other bus in the system. For bus 2:
1 P2 jQ 2
V2 *
Y 2 1V 1 (11.15.1)
Y 2 2 V 2 , o ld
Since the real and reactive powers supplied to the system at bus 2 are P2 = -0.3 pu
and Q2 = -0.2 pu and since Ys and V1 are known, we may reduce the last equation:
1 0 .3 j 0 .2
V2 0 .3 8 4 6 j1 .9 2 3 1 V 1
0 .3 8 4 6 j1 .9 2 3 1
*
V 2 , o ld
1 0 .3 6 0 3 1 4 6 .3
1 .9 6 1 2 1 0 1 .3 1 0 (11.15.2)
1 .9 6 1 2 7 8 .8
*
V 2 , o ld
5. Next, we calculate an updated estimate of the voltages at each load bus in
succession. In this problem we only need to calculate updated voltages for bus 2,
since the voltage at the slack bus (bus 1) is assumed constant. We repeat this
calculation until the voltage converges to a constant value.
The initial estimate for the voltage is V2,0 = 10˚. The next estimate for the voltage
is
1 0 .3 6 0 3 1 4 6 .3
V 2 ,1 1 .9 6 1 2 1 0 1 .3 1 0
1 .9 6 1 2 7 8 .8
*
V 2 , o ld
1 0 .3 6 0 3 1 4 6 .3
1 .9 6 1 2 1 0 1 .3
1 .9 6 1 2 7 8 .8 1 0
0 .8 7 9 7 8 .4 9 9 (11.16.1)
This new estimate for V2 substituted back to the equation will produce the second
estimate:
1 0 .3 6 0 3 1 4 6 .3
V 2 ,2 1 .9 6 1 2 1 0 1 .3 1 0
1 .9 6 1 2 7 8 .8 0 .8 7 9 7 8 .4 9 9
0 .8 4 1 2 8 .4 9 9 (11.17.1)
The third iteration will be
1 0 .3 6 0 3 1 4 6 .3
V 2 ,3 1 .9 6 1 2 1 0 1 .3 1 0
1 .9 6 1 2 7 8 .8 0 .8 4 1 2 8 .4 9 9
0 .8 3 4 5 8 .9 6 2 (11.17.2)
The fourth iteration will be
1 0 .3 6 0 3 1 4 6 .3
V 2 ,4 1 .9 6 1 2 1 0 1 .3 1 0
1 .9 6 1 2 7 8 .8 0 .8 3 4 5 8 .9 6 2
0 .8 3 2 0 8 .9 6 2 (11.17.3)
The fifth iteration will be
1 0 .3 6 0 3 1 4 6 .3
V 2 ,5 1 .9 6 1 2 1 0 1 .3 1 0
1 .9 6 1 2 7 8 .8 0 .8 3 2 0 8 .9 6 2
0 .8 3 1 5 8 .9 9 4 (11.17.4)
6. We observe that the magnitude of the voltage is barely changing and may
conclude that this value is close to the correct answer and, therefore, stop the
iterations.
This power system converged to the answer in five iterations. The voltages at each
bus in the power system are:
V 1 1 .0 0
(11.18.1)
V 2 0 .8 3 1 5 8 .9 9 4
7. Finally, we need to confirm that the resulting solution is reasonable. The results
seem reasonable since the phase angles of the voltages in the system differ by
only 10˚. The current flowing from bus 1 to bus 2 is
V1 V 2 1 0 0 .8 3 1 5 8 .9 9 4
I1 0 .4 3 3 3 4 2 .6 5 (11.18.2)
Z lin e 1 0 .1 j 0 .5
The power supplied by the transmission line to bus 2 is
0 .8 3 1 5 8 .9 9 4 0 .4 3 3 3 4 2 .6 5 0 .2 9 9 9 j 0 .1 9 9 7
*
S VI
*
This is the amount of power consumed by the loads; therefore, this solution
appears to be correct.
Note that this example must be interpreted as follows: if the real and reactive
power supplied by bus 2 is 0.3 + j0.2 pu and if the voltage on the slack bus is 10˚
pu, then the voltage at bus 2 will be V2 = 0.8315-8.994˚.
This voltage is correct only for the assumed conditions; another amount of power
supplied by bus 2 will result in a different voltage V2.
Therefore, we usually postulate some reasonable combination of powers supplied
to loads, and determine the resulting voltages at all the busses in the power
system. Once the voltages are known, currents through each line can be
calculated.
The relationship between voltage and current at a load bus as given by (11.12.1)
is fundamentally nonlinear! Therefore, solution greatly depends on the initial
guess.
At a generator bus, the real power Pi and the magnitude of the bus voltage |Vi|
are specified. Since the reactive power for that bus is usually unknown, we need to
estimate it before applying (11.12.1) to get updated voltage estimates. The value
of reactive power at the generator bus can be estimated by solving (11.12.1) for
Qi:
1 Pi jQ i
N N
*
Vi
Y ii Vi
*
ik k
Y V Pi
jQ i
V i
ii i ik k (11.20.1)
Y V Y V
k 1 k 1
k i k i
Bringing the case k = I into summation, we obtain
*
N N
Pi jQ i V i Y ik V k Q i Im V i Y ik V k
*
(11.20.2)
k 1 k 1
Once the reactive power at the bus is estimated, we can update the bus voltage at
a generator bus using Pi and Qi as we would at a load bus. However, the
magnitude of the generator bus voltage is also forced to remain constant.
Therefore, we must multiply the new voltage estimate by the ratio of magnitudes
of old to new estimates.
Therefore, the steps required to update the voltage at a generator bus
are:
1. Estimate the reactive power Qi according to (11.20.2);
2. Update the estimated voltage at the bus according to (11.12.1) as if the
bus was a load bus;
3. Force the magnitude of the estimated voltage to be constant by
multiplying the new voltage estimate by the ratio of the magnitude of
the original estimate to the magnitude of the new estimate. This has
the effect of updating the voltage phase estimate without changing the
voltage amplitude.
Example 11.3: a 4-bus power system
with 5 transmission lines, 2
generators, and 2 loads. Since the
system has generators connected to
2 busses, it will have one slack bus,
one generator bus, and two load
busses. Assume that bus 1 is the slack
bus and that it has a voltage V1 =
1.00˚ pu. Bus 3 is a generator bus.
The generator is supplying a real
power P3 = 0.3 pu to the system with a
voltage magnitude 1 pu. The per-unit
real and reactive power loads at
busses 2 2and
0.3 pu, Q 4 are
= 0.2 pu,PP24 =
= 0.2 pu, Q4 = 0.15 pu (powers supplied to the system at
each busses are negative of the above values). The series impedances of each
bus were evaluated in Example 11.1. Determine voltages at each bus for the
specified load conditions.
The bus admittance matrix was calculated earlier as
1 .7 6 4 7 j 7 .0 5 8 8 0 .5 8 8 2 j 2 .3 5 2 9 0 1 .1 7 6 5 j 4 .7 0 5 9
0 .5 8 8 2 j 2 .3 5 2 9 1 .5 6 1 1 j 6 .6 2 9 0 0 .3 8 4 6 j1 .9 2 3 1 0 .5 8 8 2 j 2 .3 5 2 9
Ybus
0 0 .3 8 4 6 j1 .9 2 3 1 1 .5 6 1 1 j 6 .6 2 9 0 1 .1 7 6 5 j 4 .7 0 5 9
1 .1 7 6 5 j 4 .7 0 5 9 0 .5 8 8 2 j 2 .3 5 2 9 1 .1 7 6 5 j 4 .7 0 5 9 2 .9 4 1 2 j1 1 .7 6 4 7
Since the bus 3 is a generator bus, we will have to estimate the reactive power at
that bus before calculating the bus voltages, and then force the magnitude of the
voltage to remain constant after computing the bus voltage. We will make a flat
start assuming the initial voltage estimates at every bus to be 1.00˚.
Therefore, the sequence of voltage (and reactive power) equations for all busses
is:
1 P2 jQ 2
V2 *
Y 2 1V 1 Y 2 3V 3 Y 2 4 V 4 (11.24.1)
Y 2 2 V 2 , o ld
*
N
Q 3 Im V 3 Y ik V k (11.24.2)
k 1
1 P3 jQ 3
V3 *
Y 3 1V 1 Y 3 2 V 2 Y 3 4V 4 (11.24.3)
Y 3 3 V 3 , o ld
V 3 , o ld
V3 V3 (11.24.4)
V3
1 P4 jQ 4
V4 *
Y 4 1V 1 Y 4 2 V 2 Y 4 3V 3 (11.24.4)
Y 4 4 V 4 , o ld
The voltages and the reactive power should be updated iteratively, for instance,
using Matlab.
Computations converge to the following solution:
V 1 1 .0 0 p u
V 2 0 .9 6 4 0 .9 7 p u
(11.25.1)
V 3 1 .0 1 .8 4 p u
V 4 0 .9 8 0 .2 7 p u
The solution looks reasonable since the bus voltage phase angles is less than 45˚.
After the bus voltages are calculated at all busses in a power system, a power-flow
program can be set up to provide alerts if the voltage at any given bus exceeds,
for instance, 5% of the nominal value. This is important since the power needs to
be supplied at a constant voltage level; therefore, such voltage variations may
indicate problems…
Additionally, it is possible to determine the net real and reactive power either
supplied or removed from the each bus by generators or loads connected to it. To
calculate the real and reactive power at a bus, we first calculate the net current
injected at the bus, which is the sum of all the currents leaving the bus through
transmission lines.
The current leaving the bus on each transmission line can be found as:
N
Ii Y V ik i
Vk (11.26.1)
k 1
k i
The resulting real and reactive powers injected at the bus can be found from
S i V i I i Pi jQ i
*
(11.27.1)
where the minus sign indicate that current is assumed to be injected instead of
leaving the node.
Similarly, the power-flow study can show the real and reactive power flowing in
every transmission line in the system. The current flow out of a node along a
particular transmission line between bus i and bus j can be calculated as:
I ij Y ij V i V j
where Yij is the admittance of the transmission line between those two busses. The
resulting real and reactive power can be calculated as:
S ij V i I ij Pij jQ ij
*
Also, comparing the real and reactive power flows at either end of the
transmission line, we can determine the real and reactive power losses on each
line.
In modern power-flow programs, this information is displayed graphically. Colors
are used to highlight the areas where the power system is overloaded, which aids
“hot spot” localization.
Power-flow studies are usually started from analysis of the power system in its
normal operating conditions, called the base case. Then, various (increased) load
conditions may be projected to localize possible problem spots (overloads). By
adding transmission lines to the system, a new configuration resolving the
problem may be found. This estimated models can be used for planning.
Another reason for power-flow studies is modeling possible failures of particular
lines and generators to see whether the remaining components can handle the
loads.
Finally, it is possible to determine more efficient power utilization by
redistributing generation from one locations to other. This variety of power-flow
studies is called economic dispatch.
S o f a r w e 'v e a s s u m e d th a t th e lo a d is in d e p e n d e n t o f
th e b u s v o lta g e ( i.e ., c o n s ta n t p o w e r ) . H o w e v e r , th e
p o w e r f lo w c a n b e e a s ily e x te n d e d to in c lu d e v o lta g e
d e p e d e n c e w ith b o th th e r e a l a n d r e a c tiv e l o a d . T h is
is d o n e b y m a k in g P D i a n d Q Di a f u n c tio n o f V i :
n
V i V k ( G ik c o s ik B ik s in ik ) PG i PD i ( V i ) 0
k 1
n
V i V k ( G ik s in ik B ik c o s ik ) Q G i Q D i ( V i ) 0
k 1
In p r e v io u s tw o b u s e x a m p le n o w a s s u m e t h e lo a d is
c o n s ta n t im p e d a n c e , s o
2
P2 ( x ) V 2 (1 0 s in 2 ) 2 .0 V 2 0
2 2
Q2 (x) V2 ( 10 cos 2 ) V2 (1 0 ) 1 .0 V 2 0
N o w c a lc u la te th e p o w e r f lo w J a c o b ia n
1 0 V 2 c o s 2 1 0 s in 2 4 .0 V 2
J (x)
1 0 V 2 s in 2 10 cos 2 20 V2 2 .0 V 2
(0) 0
A g a in s e t v 0 , g u e s s x
1
C a lc u la te
V 2 (1 0 s in 2 ) 2 .0 V 2
2
2 .0
(0)
f(x )
2 2
V 2 ( 1 0 c o s 2 ) V 2 (1 0 ) 1 .0 V 2 1 .0
(0) 1 0 4
J (x )
0 12
1
(1 ) 0 1 0 4 2 .0 0 .1 6 6 7
S o lv e x
1 0 12 1 .0 0 .9 1 6 7
With constant impedance load the MW/Mvar load at
bus 2 varies with the square of the bus 2 voltage
magnitude. This if the voltage level is less than 1.0,
the load is lower than 200/100 MW/Mvar
160.0 MW -160.0 MW
120.0 MVR Line Z = 0.1j -80.0 MVR
0.894 pu
One 1.000 pu Two -10.304 Deg
160.0 MW 160 MW
120.0 MVR 80 MVR
Since most of the time in the Newton-
Raphson iteration is spend calculating the
inverse of the Jacobian, one way to speed
up the iterations is to only
calculate/inverse the Jacobian
occasionally
• known as the “Dishonest” Newton-Raphson
• an extreme example is to only calculate the
Jacobian for the first iteration
( v 1) (v) ( v ) -1 (v)
H o n e s t: x x - J (x ) f (x )
( v 1) (v) ( 0 ) -1 (v)
D is h o n e s t: x x - J (x ) f (x )
(v )
B o th re q u ire f ( x ) fo r a s o lu tio n
U s e th e D is h o n e s t N e w to n -R a p h s o n to s o lv e
2
f (x) x -2 0
1
(v )
df (x (0)
) (v)
x f (x )
dx
(v ) 1 (v) 2
x (( x ) - 2 )
2 x ( 0 )
( v 1) (v ) 1 (v) 2
x x (( x ) - 2 )
2 x ( 0 )
( v 1) (v) 1 (v) 2
x x (( x ) - 2 )
2 x ( 0 )
(0 )
G uess x 1 . Ite r a tiv e ly s o lv in g w e g e t
(v ) (v )
v x ( h o n e s t) x ( d is h o n e s t)
0 1 1 We pay a price
1 1 .5 1 .5 in increased
2 1 .4 1 6 6 7 1 .3 7 5
iterations, but
with decreased
3 1 .4 1 4 2 2 1 .4 2 9
computation
4 1 .4 1 4 2 2 1 .4 0 8 per iteration
Slide shows the region of convergence for
different initial
guesses for the 2 bus case using the Dishonest N-R
Red region
converges
to the high
voltage
solution,
while the
yellow region
converges
to the low
voltage
solution
Maximum
of 15
iterations
The completely Dishonest Newton-
Raphson is not used for power flow
analysis. However several approximations
of the Jacobian matrix are used.
One common method is the decoupled
power flow. In this approach
approximations are used to decouple the
real and reactive power equations.
G e n e r a l f o r m o f th e p o w e r f lo w p r o b le m
P (v ) P
(v)
θ V θ (v ) P (x (v ) )
(v )
f ( x )
(v ) (v ) (v ) (v)
Q Q V Q ( x )
θ V
w h e re
P2 ( x ( v ) ) PD 2 PG 2
(v )
P (x )
(v )
n
P ( x ) PD n PG n
(v ) (v)
P Q
U s u a lly th e o f f -d ia g o n a l m a tr ic e s , and
V θ
a r e s m a ll. T h e r e f o r e w e a p p r o x im a te th e m a s z e r o :
P (v )
0 θ (v ) P (x (v ) )
θ
f ( x
(v )
)
Q
(v )
V
(v )
(v )
Q ( x )
0
V
T h e n th e p r o b le m c a n b e d e c o u p le d
1 1
(v )
P (v )
(v) (v ) Q (v)
(v)
θ P (x ) V Q (x )
θ V
J u s tif ic a tio n f o r J a c o b ia n a p p r o x im a tio n s :
1 . U s u a lly r x , th e r e f o r e G ij B ij
2 . U s u a lly ij is s m a ll s o s in ij 0
T h e re fo re
Pi
Vi G ij c o s ij B ij s in ij 0
V j
Q i
Vi V j G ij c o s ij B ij s in ij 0
θ j
By continuing with our Jacobian approximations
we can actually obtain a reasonable
approximation that is independent of the
voltage magnitudes/angles.
This means the Jacobian need only be
built/inverted once.
This approach is known as the fast decoupled
power flow (FDPF)
FDPF uses the same mismatch equations as
standard power flow so it should have same
solution
The FDPF is widely used, particularly when we
only need an approximate solution
T h e F D P F m a k e s th e f o llo w in g a p p r o x im a ti o n s :
1. G ij 0
2. Vi 1
3. s in ij 0 c o s ij 1
T hen
(v ) (v )
(v) 1 P (x ) (v ) 1 Q (x )
θ B V B
(v) (v)
V V
W h e r e B is ju s t th e im a g in a r y p a r t o f th e Y b u s G j B ,
e x c e p t th e s la c k b u s r o w /c o lu m n a r e o m itte d
Use the FDPF to solve the following three bus system
Line Z = j0.07
One Two
200 MW
100 MVR
Line Z = j0.05 Line Z = j0.1
Three 1.000 pu
200 MW
100 MVR
3 4 .3 1 4 .3 20
Ybus j 1 4 .3 2 4 .3 10
2 0 10 3 0
3 4 .3 1 4 .3 20
2 4 .3 10
Ybus j 1 4 .3 2 4 .3 10 B
10 30
2 0 10 3 0
1 0 .0 4 7 7 0 .0 1 5 9
B
0 .0 1 5 9 0 .0 3 8 9
Pi ( x )
n
PD i PG i
V k ( G ik c o s ik B ik s in ik )
Vi k 1 Vi
(2)
2 0 .1 2 7 2 0 .0 4 7 7 0 .0 1 5 9 0 .1 5 1 0 .1 3 6 1
3 0 .1 0 9 1 0 .0 1 5 9 0 .0 3 8 9 0 .1 0 7 0 .1 1 5 6
(2)
V 2
0 .9 2 4
V 3 0 .9 3 6
0 .1 3 8 4 0 .9 2 2 4
A c tu a l s o lu tio n : θ V
0 .1 1 7 1 0 .9 3 3 8
The “DC” powerflow makes the most
severe approximations:
• completely ignore reactive power, assume all the
voltages are always 1.0 per unit, ignore line
conductance
This
makes the power flow a linear set of
equations, which can be solved directly
1
θ B P
A major problem with power system operation is the limited capacity
of the transmission system
• lines/transformers have limits (usually thermal)
• no direct way of controlling flow down a transmission
line (e.g., there are no valves to close to limit flow)
• open transmission system access associated with
industry restructuring is stressing the system in new
ways
We need to indirectly control transmission
line flow by changing the generator outputs
One Five Four Three
A A
360 MW 520 MW
MVA MVA
A
0 Mvar
MVA
slack
0 Mvar
1.000 pu 1.000 pu A A
1.000 pu 80 MW
0.000 Deg -4.125 Deg MVA MVA
-1.997 Deg 0 Mvar
1.000 pu
0.524 Deg
1.000 pu Two
-18.695 Deg
800 MW
0 Mvar
Notice with the dc power flow all of the voltage magnitudes are
1 per unit.
What we would like to determine is how a change
generation at bus k affects the power flow on a lin
from bus i to bus j.
The assumption is
that the change
in generation is
absorbed by the
slack bus
One way to determine the impact of a generator change is to
compare a before/after power flow.
For example below is a three bus case with an overload
131.9 MW
124%
One Two
200.0 MW 200 MW
68.1 MW 68.1 MW
71.0 MVR 100 MVR
0 MW
64 MVR
Increasing the generation at bus 3 by 95 MW (and hence
decreasing it at bus 1 by a corresponding amount), results
in a 31.3 drop in the MW flow on the line from bus 1 to 2.
101.6 MW
100%
One Two
105.0 MW 200 MW
3.4 MW 98.4 MW
64.3 MVR 100 MVR
92%
Z for all lines = j0.1
Limit for all lines = 150 MVA
1.000 pu
Three
95 MW
64 MVR
Calculating control sensitivities by repeat
power flow solutions is tedious and would
require many power flow solutions. An
alternative approach is to analytically calculate
these values
T h e p o w e r f lo w f r o m b u s i to b u s j is
Vi V j i j
Pij s in ( i j )
X ij X ij
i j ij
S o Pij W e ju s t n e e d to g e t
X ij PG k
F r o m th e f a s t d e c o u p le d p o w e r f lo w w e k n o w
1
θ B P (x )
S o to g e t th e c h a n g e in θ d u e to a c h a n g e o f
g e n e r a tio n a t b u s k , ju s t s e t P ( x ) e q u a l to
a ll z e r o s e x c e p t a m in u s o n e a t p o s itio n k .
0
P 1 B u s k
0
61
In the per-unit system, the voltages, currents,
powers, impedances, and other electrical
quantities are expressed on a per-unit basis by
the equation:
Actual value
Quantity per
unit = Base value of
quantity
It is customary to select two base quantities to
define a given per-unit system. The ones usually
selected are voltage and power.
62
Assume:
V b V rated
S b S rated
63
And the per-unit system is:
V actual I actual
V p .u . I p .u .
Vb Ib
S actual Z actual
S p .u .
Z p .u .
Sb Zb
Z% Z p .u .
100 % Percent of base Z
64
An electrical lamp is rated 120 volts, 500 watts.
Compute the per-unit and percent impedance of
the lamp. Give the p.u. equivalent circuit.
Solution:
(1) Compute lamp resistance
2 2 2
V V (120 )
P R 28 . 8
R P 500
65
(2) Select base quantities
S b 500 VA
V b 120 V
V S 1 0 p .u . Z 1 0 p .u .
67
An electrical lamp is rated 120 volts, 500 watts. If
the voltage applied across the lamp is twice the
rated value, compute the current that flows
through the lamp. Use the per-unit method.
Solution:
V b 120 V
V 240
V p .u . 2 0 p .u .
Vb 120
Z p .u .
1 0 p .u .
68
The per-unit equivalent circuit is as follows:
V S 2 0 p .u . Z 1 0 p .u .
V p .u . 2 0
I p .u . 2 0 p .u .
Z p .u .
1 0
Sb 500
Ib 4 . 167 A
Vb 120
I actual I p .u .
I b 2 0 4 . 167 8 . 334 0 A
69
One-phase circuits
S b S 1 V I
where
V V line to neutral
I I line current
V bLV V LV V bHV V HV
Sb Sb
I bLV I bHV
V bLV V bHV
70
2 2
V bLV (V bLV ) V bHV (V bHV )
Z bLV Z bHV
I bLV Sb I bHV Sb
S
V pu I
*
S pu pu
Sb
P
P pu V pu I pu
cos
Sb
Q
Q pu
V pu I pu
sin
Sb
71
Selection 1
S b1 S A V b1 V A
Then 2
V b1 Z
Z b1
L
Z pu 1
S b1 Z b1
Selection 2
Sb2 S B Vb2 V B
Then 2
Vb2 Z
Z b2
L
Z pu 2
Sb2 Z b2
72
2
Z pu 2 ZL Z b1 Z b1 V b1 Sb2
2
Z pu 1
Z b2 ZL Z b2 S b1 Vb2
2
V b1 Sb2
Z Z pu 1
pu 2
Vb2 S b1
“1” – old
“2” - new
2
V b , old S b , new
Z Z
pu , new pu , old
V S
b , new b , old
73
Generally per-unit values given to another base
can be converted to new base by by the
equations:
S base
( P , Q , S ) pu
1
( P , Q , S ) pu _ on _ base _ 2 _ on _ base _ 1
S base 2
V base
V pu
1
V pu _ on _ base _ 2 _ on _ base _ 1
V base 2
2
(V base 1 ) S base
( R , X , Z ) pu
2
( R , X , Z ) pu _ on _ base _ 2 _ on _ base _ 1 2
(V base 2 ) S base 1
74
Consider the equivalent circuit of transformer
referred to LV side and HV side shown below:
RS X
j
S
R S jX 2 2
S a a
V LV V HV V LV V HV
N1 N V LV N1
2 Define a 1
S V HV N 2
75
Choose:
V b 1 V LV , rated Normal choose rated
values as base values
S b S rated
Compute: V HV 1
Vb2 V b1 V b1
V LV a
2 2
V b1 Vb2
Z b1 Z b2
Sb Sb
2 2
Z b1 V b1 V b1
a
2
2
Z b2 Vb2 1 2
( V b1 )
a 76
Per-unit impedances are:
R S jX
S
Z p .u .1
Z b1
RS jX RS jX
S
S
a
2
a
2
a
2
a
2 R S jX
S
Z p .u .2
Z b2 Z b1 Z b1
2
a
Per-unit equivalent
So:
Z
circuits of transformer
Z p .u .1 p .u .2 referred to LV side and
HV side are identical !!
77
R S jX S S
V LV N1
a 1
Z b1 V HV N 2
N1 N 2
V b1 V LV V HV Vb2
V b1 Vb2
V b1 Vb2
Sb
1 :1
Fig 2. Per-unit Eq Ckt referred to LV side Fig 3.
78
RS X
j
S
2 2
S a a
V LV N1
a 1
Z b2 V HV N 2
N1 N 2
V b1 V LV V HV Vb2
V b1 Vb2
V b1 Vb2
Sb
1 :1
Fig 5. Per-unit Eq Ckt referred to HV side Fig 6.
79
Voltage regulation is defined as:
V no load V full load
VR 100 %
V full load
In per-unit system:
V pu , no load V pu , full load
VR 100 %
V pu , full load
Solution:
VP j 0 .1 VS
V b 2 400 V
S b 200 kVA X S
S load
S load , pu
1 0 pu
X S , pu
j 0 . 1 pu
Fig 7. Per-unit equivalent circuit
81
Rated voltage:
V S , pu 1 . 0 0 pu
*
S load , pu
*
1 .0 0
I load 1 . 0 0 pu
, pu
V
S , pu 1 .0 0
V P , pu V S , pu I pu
X S , pu
1 .0 0 1 .0 0 j 0 .1 1 j 0 .1
1 . 001 5 . 7 pu
o
82
Secondary side:
V pu , full load
V S , pu 1 . 0 0 pu
V pu , no load V P , pu 1 . 001 5 . 7 pu
o
Voltage regulation:
1 . 001 1 . 0
100 % 0 . 1 %
1 .0
83
j100
84
Three-phase circuits
S b S 3 3 S 1 3V I
where
V V line to neutral
V L ( line ) / 3
I I line current
IL
Sb 3V L I L
V bLV V L , LV V bHV V L , HV
2
(V bHV )
Z bHV
Sb
*
S 3 3V L I L
V pu I pu
*
S pu
Sb 3V b I b
86
Three 25-kVA, 34500/277-V transformers
connected in -Y. Short-circuit test on high voltage
side:
V Line , SC
2010 V
I Line , SC
1 . 26 A
P3 , SC 912 W
87
(a) Using Y-equivalent
R S jX
I SC 1 . 26 S
2010
V SC S b 25000 VA
3
34500
277
3
2010
V SC 1160 . 47 V
3
1160 . 47
Z SC 921 . 00
1 . 26
88
912 P 304
P 304 W RS 2
2
191 . 48
3 I SC 1 . 26
2
RS 191 . 48 900 . 86
2 2 2
X S
Z SC 921
So Z SC 191 . 48 j 900 . 86
34500
S b 25000 VA V b , HV 19918 . 58 V
3
2
19918 . 58
Z b , HV 15869 . 99
25000
191 . 48 j 900 . 86
Z SC , pu ,Y 0 . 012 j 0 . 0568 pu
15869 . 99
89
(b) Using -equivalent
1 . 26
I SC
3 Z SC ,
V SC 2010 S b 25000 VA
34500 277
1 . 26
V SC 2010 V I SC 0 . 727 A
3
2010
Z SC ,
2764 . 79
0 . 727
90
912 P 304
P 304 W R S , 2
2
575 . 18
3 I SC 0 . 727
2
R S , 575 . 18 2704 . 30
2 2 2
X S ,
Z SC , 2764 . 79
So Z SC 191 . 48 j 900 . 86
S b 25000 VA V b , HV 34500 V
2
34500
Z b , HV 47610
25000
575 . 18 j1704 . 30
Z SC , pu , 0 . 012 j 0 . 0568 pu
47610
91
UNIT-III
SHORT CIRCUIT ANALYSIS
Start with Newton again ....
T=Ia
We want to describe the motion of the
rotating masses of the generators in
the system
2H d2 d = Pacc
wo dt2
P = T w
a = d2d/dt2, acceleration is the second
derivative of angular displacement
w.r.t. time
w = dd/dt, speed is the first derivative
Accelerating Power, Pacc
Pacc = Pmech - Pelec
Steady State => No acceleration
Pacc = 0 => Pmech = Pelec
Generator connected to Infinite bus through
2 lossless transmission lines
2 dd d2d = wo Pacc dd
dt dt2 H dt
=>
d {dd}2 = wo Pacc dd
dt {dt } H dt
{dd}2 wo Pacc dd
=
{dt} H dt
For the system to be stable, d must go
through a maximum => dd/dt must go
through zero. Thus . . .
dm
wo Pacc dd = 0 = { dd}2
H { dt }
do
For the total area to be zero, the positive
part must equal the negative part. (A1 =
A2)
dcl
P
do
acc dd = A1 <= “Positive” Area
dm