No.

Dokumen 05/SET/UPT-RENEV/2018
Edisi / Revisi 02 / 02
Berlaku Efektif 13 februari 2017
Halaman 1 dari 4

EVALUASI SETTING PLN UPT SULSELRABAR


(nilai sekunder)
Karakteristik Rele : Rele OCR/GFR T/L DSSP
Manufactur : Siemens
Tipe : 7SJ82
Arus Input : 5 A

Parameter Setting Satuan


GENERAL
Charac Phase TOC IEC -
Charac Ground TOC IEC -
Inrush restraint Enable -
CT starpoint Towards Line -
CT PRIMARY 800 -
CT SECONDARY 5 -
Rated Frequency 50 Hz -
OCR
50-1 Pickup - IN
50-1 Delay - s
51 Pickup 1 IN
51 Time Dial 2 s
51 Iec CURVE DT
GFR
50N-1 Pickup - -
50N-1 Delay - -
51N Pickup 0,2 IN
51N Time Dial 2 s
51N Iec CURVE DT -
Karakteristik Rele : Rele Distance T/L DSSP
Manufactur : Siemens
Tipe : 7UT8
Arus Input : 5 A
Parameter Setting Satuan
DEVICE CONFIGURATION
Setting group Change Option Disable -
Trip Mode 1-/3pole -
Phase Distance Quadrilateral -
Earth Distance Quadrilateral -
Additional Threshold Iph>(Z1) Disable -
Power Swing Detection Enable -
Teleprotection for Distance Prot PUTT (Z1B acceleration) -
DTT Direct Transfer Trip Enable -
Instantaneous Highspeed SOTF Overcurrent Enable -
Weak Infeed (Trip and/or Echo) Disabled -
Backup Overcurrent Time Overcurrent Curve IEC -
Earth Overcurrent Definite Time -
Teleprotection for Earth fault overcurr. Directional comp.Pickup -
Autoreclose function 1 AR-cycle -
Synchronism and Voltage Check Enable -
Fault Locator Enable -
POWER SYSTEM DATA
CT Starpoint Towards Line -
Rated Primary voltage 150,0 kV
Rated secondary voltage (Ph-Ph) 100V
CT rated Primary Current 800 A
CT rated Secondary Current 5A

1/4 Dibuat oleh: Dievaluasi oleh : Disetujui oleh :


Daftar Evaluasi Setelan Rele Proteksi
Sufardin Sunardi Kamran JR
Rev. 01 GI KENDARI NEW Tgl :08-05-2018 Tgl :08-05-2018
Tgl :08-05-2018
No. Dokumen 05/SET/UPT-RENEV/2018
Edisi / Revisi 02 / 02
Berlaku Efektif 13 februari 2017
Halaman 2 dari 4

U4 Voltage Transformer is Usy2 transformer


Matching ratio Phase-VT to open-Delta-VT 1,73
VT connection for Usy2 L2-E
Angle adjustment Usy2-Usy-1 0o
Matching ratio Usy1/Usy2 1
I4 current transformer is Neutral Current
Matching ratio I4/Iph for CT's 1
System startpoint is Solid Earthed
Rated Frequency 50Hz
Phase Sequence L1 L2 L3
Distance measurement Unit km
Setting format for zero seq.comp.format zeroseq.comp.fac.K0&An.(K0)
Earth Fault O/C: setting for 1pole AR all stages together
System startpoint is Solid Earthed
Rated Frequency 50Hz
Phase Sequence L1 L2 L3
Distance measurement Unit km
Setting format for zero seq.comp.format zeroseq.comp.fac.K0&An.(K0)
Earth Fault O/C: setting for 1pole AR all stages together
Measurement: Full Scale Voltage (100%) 150 kV
Measurement: Full Scale current (100%) 2000 A
Line Angle 71o
Angle of inclination, distance charact. 71o
P,Q operational measured values sign not reversed
X'-Line Reactance per length unit 0,10587 Ohm/km
Line Length 23,7 km
Zero seq.comp.factor RE/RL for Z1 7,91687
Zero seq.comp.factor XE/XL for Z1 0,61719
Zero seq.comp.factor RE/RL (> Z1) 7,91687
Zero seq.comp.factor XE/XL (>Z1) 0,61719
BREAKER
Closing (operating) time of CB 0,16 sec
Minimum TRIP Command Duration 0,10 sec
Maximum Close Command Duration 0,10 sec
Dead Time for CB test-autoreclose 0,10 sec
3 pole coupling with trip
Trip type with 2phase faults 3pole
Line Status
Pole Open Current Threshold 100A
Pole Open Voltage Threshold 4,5 kV
Seal-in Time after ALL closures 0,05 sec
minimal time for line open before SOTF 0,25 sec
Recognition of Line Closures with Manual close BI only
RESET of Trip Command withPoleOpen Curr.Thre.only
open pole detector withmea.(U/I,trip,pickup,Cbaux)
CT Saturation Threshold 2000A
Seal-in Time after MANUAL closures 0,3 sec
Manual CLOSE COMMAND generation NO
MANUAL Closure impulse after CONTROL <none>
Distance Protection General
Distance Protection, ON
Phase Current threshold for dist,meas 50 A
Angle of inclination, distance charact 71o Degree
Series compensated line NO
Instantaneous trip after switchOnToFault with Zone Z1
R load, minimum Load Impedance (ph-e) 4,33629 Ohm (s)
PHI load, maximum Load Angle (ph-e) 37o Degree
R load, minimum Load Impedance (ph-ph) 4,33629 Ohm (s)
PHI load, maximum Load Angle (ph-ph) 37o Degree
Single pole trip for faults in Z2 NO
Z1B enabled before 1st AR (int. Or ext.) NO

2/4 Dibuat oleh: Dievaluasi oleh : Disetujui oleh :


Daftar Evaluasi Setelan Rele Proteksi
Sufardin Sunardi Kamran JR
Rev. 01 GI KENDARI NEW Tgl :08-05-2018 Tgl :08-05-2018
Tgl :08-05-2018
No. Dokumen 05/SET/UPT-RENEV/2018
Edisi / Revisi 02 / 02
Berlaku Efektif 13 februari 2017
Halaman 3 dari 4

Earth Faults
3I0 threshold for neutral current pickup 0,25 A
3U0 threshold zero seq. Voltage pickup 30 kV
3I0>pickup-stabilisation (3I0>/Iphmax) 0,1
criterion of earth fault recognition 3I0> OR 3U0>
Loop selection with 2Ph-E faults block lagging ph-e loop
Time Delays
Condition for zone timer start with distance pickup
T1-1phase, delay for single phase faults 0,0 Sec
T1multi-ph, delay for multi phase faults o,0 Sec
T2-1phase, delay for single phase faults 0,4 Sec
T2multi-ph, delay for multi phase faults o,4 Sec
T3 delay 1,2 Sec
T4 Delay 1,2 Sec
T5 Delay 0,9 Sec
T6 Delay 1,5 Sec
T1B-1phase, delay for single phase faults 0,0 Sec
T1Bmulti-ph, delay for multi phase faults 0,0 Sec
Zone 1
Operating mode Z1 forward
R(Z1), Resistance for ph-ph-faults 3,20867 Ohm
X (Z1), Reactance 0,80289 Ohm
RE(Z1), resistance for ph-e faults 3,20867 Ohm
T1-1phase,delay for single phase faults 0,00 sec
T1multi-ph, delay for multi phase faults 0,00 sec
Zone reduction Angle (load compensation) 0o

Zone 1B-Extend
Operating mode Z1B (overreach zone) forward
R(Z1B), Resistance for ph-ph-faults 3,20867 Ohm
X (Z1B), Reactance 1,20434 Ohm
RE(Z1B), resistance for ph-e faults 3,20867 Ohm
T1B-1phase,delay for single phase faults 0,00 sec
T1Bmulti-ph, delay for multi phase faults 0,00 sec
Z1B enabled before 1st AR (int.or ext.) NO
Zone 2
Operating mode Z2 forward
R(Z2), Resistance for ph-ph-faults 3,20867 Ohm
X (Z2), Reactance 1,20434 Ohm
RE(Z2), resistance for ph-e faults 3,20867 Ohm
T2-1phase,delay for single phase faults 0,40 sec
T2multi-ph, delay for multi phase faults 0,40 sec
Single pole trip for faults in Z2 NO
Zone 3 ( InActive )
Zone 4 ( InActive )
Zone 5 ( InActive )
Zone 6 ( InActive )
AUTORECLOSE
Autoreclose function ON
CB Ready interrogation at 1st trip NO
Reclaim time after successful AR cycle 30 sec
AR blocking duration after manual close 30 sec
Evolving fault recognition with trip
Evolving fault (during the dead time) starts 3pole AR-cycle
AR start-signal monitoring time 0,2 sec
Circuit Breaker (CB) Supervision time 3 sec
Send delay for remote close command 00 sec
1st AR-cycle
Start of AR allowed in this cycle YES
Action time 0,2 sec

3/4 Dibuat oleh: Dievaluasi oleh : Disetujui oleh :


Daftar Evaluasi Setelan Rele Proteksi
Sufardin Sunardi Kamran JR
Rev. 01 GI KENDARI NEW Tgl :08-05-2018 Tgl :08-05-2018
Tgl :08-05-2018
No. Dokumen 05/SET/UPT-RENEV/2018
Edisi / Revisi 02 / 02
Berlaku Efektif 13 februari 2017
Halaman 4 dari 4

Dead time after 1pole trip 1 sec


Dead time after 3pole trip 2 sec
Dead time after evolving fault 2sec
CB ready interrogation before reclosing NO
Request for synchro-check after 3pole AR YES
3p TRIP/DLC/RDT
3pole TRIP by AR YES
Dead Line Check or Reduced Dead Time without
Supervision time for dead/live voltage 0,1 sec
Voltage threshold for live line or bus 72 kV
Voltage threshold for dead line or bus 45 kV
Start AR with
AR with Distance Protection YES
AR with SOTF overcurrent NO
AR with E/F Overcurrent prot. NO
AR with DTT NO
AR with Back-up overcurrent NO
Synchronism and Voltage Check
Synchronism and Voltage Check Function ON
Voltage threshold dead line/bus 7,5 kV
Voltage threshold live line / bus 30 kV
Maximum permissible voltage 165 kV
Maximum duration of synchronism-check 1 sec
Synchronous condition stability timer 0,0 sec
Synchronizable circuit breaker <none>
with AR
Operating mode with AR
Maximum voltage difference 6 kV
Maximum frequency difference 0,1 Hz
Maximum angle defference 10O
AR at Usy1< and Usy2> YES
AR at Usy1> and Usy2< YES
AR at Usy1< and Usy2< YES
Override of any check before AR NO
Man.Close+CNTRL
Operating mode with Man.Cl
Maximum voltage difference 3 kV
Maximum frequency difference 0,1 Hz
Maximum angle defference 10O
Man.Cl at Usy1< and Usy2> YES
Man.Cl at Usy1> and Usy2< YES
Man.Cl at Usy1< and Usy2< YES
Override of any check before Man.Cl NO
Fault Locator
Star fault Locator with Pickup
Load Compensation NO

4/4 Dibuat oleh: Dievaluasi oleh : Disetujui oleh :


Daftar Evaluasi Setelan Rele Proteksi
Sufardin Sunardi Kamran JR
Rev. 01 GI KENDARI NEW Tgl :08-05-2018 Tgl :08-05-2018
Tgl :08-05-2018