You are on page 1of 1

1

UNION
NIPPLE
FILL/INSPECTION CAP

TOP VIEW
GI THREADED ROD
DRAIN PAN
TEE
SPECIFIED DUCT SIZE X
DUCT DUCT THERMAL INSULATION FIBRE GLASS
SECONDARY DRAIN PAN PITCH
HARDWOOD INSERT INSTALLED IN CASE OF FALSE CEILING DOWN TO
MS CHANNEL/ANGLE DRAIN
1.5X
(HOT DIP GALVANIZED)
MINIMUM DROP

SPACING OF SUPPORTS X = NEGATIVE INTERNAL STATIC U-BEND


PRESSURE AT FAN INLET
MAX. DUCT SIZE HANGER BEARING MEMBER MAX. SPACING 3D VIEW
(longer side) ROD(dia.) mm ANGLE OF HANGER(mm)

8 25x25x3mm 3000 DETAIL OF HVAC CONDENSATE DRAIN CONNECTION FRONT VIEW


UP TO 300mm

301mm-600mm 8 25x25x3mm 2400 NTS


601mm-1000mm 10 32x32x3mm 2400

1001mm-1500mm 10 40x40x3mm 2400


VERTICAL FAN COIL UNIT (VFCU)
NTS
1501mm-1800mm 10 40x40x6mm 1800
NOTES:-
1801mm-2400mm 10 50x50x6mm 1800
1- ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP.
T
2- PITCH DRAIN FOR PROPER RUN OFF.
3- MANUALLY PRIME FILL TRAP BEFORE START UP TO FORM
INITIAL DRAIN SEAL
T
MM

DUCT SUPPORT DETAILS EXHAUST FAN (WALL MOUNTED) 2" PRE FILTER BAG FILTER TS

NTS NTS SUPPLY AIR

155mm WIDE PRESSURE SENSITIVE


ADHESIVE TAPE AT JOINTS FRESH AIR

PURGE AIR PURGE AIR RETURN AIR

GI THREADED ROD
2No. GALVANIZED `U` BOLT CLAMPS
ON MINIMUM 100mm LONG G.I SLEEVE EXHAUST AIR
HARD RUBBER INSERT
INSULATION WITH REINFORCED
ALUMINUM VAPOR BARRIER
TOTAL ENERGY COOLING COIL SENSIBLE ENERGY 2" PRE FILTER
SHEET METAL DUCT GALVANIZED BOLT, NUTS & WASHER RECOVERY WHEEL RECOVERY WHEEL

INSULATION MECHANICAL MS CHANNEL/ANGLE


CLIP AT 403mm INTERVAL (HOT DIP FRESH AIR AHU WITH DOUBLE RECOVERY WHEELS
GALVANISED)
NTS (FOR PLANT VENTILATION)
NOTES :

1, UNIT SELECTION AND AIR CONDITIONS AT DIFFERENT SECTIONS TO BE PROVIDED BY SUPPLIER BASED ON
SUPPLY, RETURN AND FRESH AIR CONDITIONS.
INSULATION FASTENING INSULATION FASTENING 2, FACE VELOCITY THROUGH RUN AROUND COIL & HEAT PIPES SHOULD NOT EXCEED 2.5 m/sec.
3, TEMPERATURE SENSOR TO BE INSTALLED IN OFF COIL AIR STREAM TO MAINTAIN THE
CHILLED WATER COIL CONNECTION DETAIL CHILLED WATER PIPE SUPPORT DETAILS SPECIFIED OFFCOIL DRY BULB TEMP. BY CONTROLING THE MODULATING VALVE

NTS NTS
DUCT INSULATION AND HANGER
NTS
Rev. Description Date Drawn Chkd

REVISION STATUS
Employer :

1
ANTI VIBRATION SPRING HANGER Engineer :

THREADED GI ROD NOTE 6


FIRE BARRIER SLEEVE, NOTE 2
1"(25 MM)
PARTITION OR CHASE MIN
DAMPER COLLAR EXTENSION Engineer's Assistant :
TYPICAL DUCT
INSULATION INTEGRAL PART OF SLEEVE
DAMPER, NOTE 1
RETURN AIR
Contractor :
FILTER
ACCESS
PANEL
NOTE 5

PERIMETER ANGLE, DUCT CONNECTION District Cooling Consultant :


NOTE 3 (NOTE NOTE 4
SECONDARY
FASTENED TO SLEEVE, NOTE 2
DRAIN PAN
PARTITION)
TYPICAL FAN COIL UNIT HANGING DETAIL
NTS VERTICAL SECTION P.O. BOX 22851 SHARJAH, TEL. : 971 6 5566880 FAX. : 971 6 5566881
1 SUPPLY AIR
P.O. BOX 99352 DUBAI, TEL. : 971 4 3432110 FAX. : 971 4 3432113

SECTION THOUGH TYPICAL FIRE DAMPER INSTALLATION P.O. BOX 110512 ABU DHABI, TEL. : 971 2 6316782 FAX. : 971 2 6316783

Local Consultant :
NTS

NOTES:
DESIGN DRAWING
1. A VERTICAL DAMPER 1S SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR Project :
CPC02
SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION
OR FLOOR AND NOT OUTSIDE THE PENETRATION.
DEVELOPMENT OF ISF CAMP AT DUHAIL
Location :
2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES. AL - DUHAIL
Quantity 8
3. PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1 1/2" x 1 1/2" (40 x 40 MM), 14 Date : 07-07-2013 Job No. : Q 1309
GAGE, TO PROVIDE 1" (25 MM) MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES. SAND DRAIN HOLES
Dwg.Title :
4. BREAKAWAY DUCT CONNECTION: AS PER SMACNA LPDS, FIG. 2-13, SEAL JOINTS.
5. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

AHU DUCTING CONNECTION DETAILS (TYPICAL) HVAC DETAILS


SIDE VIEW END VIEW SHOWS FROM INLET END OF UNIT
6. PROVIDE 1/4" TO 1/2" (8 TO 15 MM) CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE
WITH ROCK WOOL FIRESTOP FIBER.
HORIZONTAL SECTION
NTS

CEILING MOUNTED SMOKE EXHAUST FAN SAND TRAP LOUVERS DETAIL Drawn By : Designed By : Checked By :

V.BALTAO C.SALIBA F.HASHEM


NTS NTS

Dwg No : Scale Rev


CPC02-AJJV-DD-SDCP-HVAC-15-1101 N.T.S 1