Professional Documents
Culture Documents
absolute the volume will have become 1.7 m3/kg and the work done will be
represented by the area under the curve between the limits shown by Pi and
Pi.
If, now, the final pressure is reduced to 0.5 bar absolute the expansion will
continue to Λ and the volume will be 3.3 m3/kg. Thus, the extr$ work
obtained per kilogram of steam is represented by the shaded area. This is a
considerable amount of extra work, obtained by improving the back pres-
sure by 0.5 bar. To achieve a comparable amount of extra work at the inlet to
the turbine the steam pressure would have to be lifted from Pl to P4, i.e.
from 11 to 17.5 bars as shown by the cross-hatched area.
Of course, in practice it is normal to operate with considerably lower back
pressures than depicted in Figure ILL It is easy to see that even small
changes in back pressure can cause considerable changes in the work done
per kilogram of steam - and remember there are over a million kilograms of
steam entering the condenser per hour on large units. So it is easy to see why
turbine back pressure is the most important terminal condition of all.
Therefore it is important to the efficient operation of a unit that its back
pressure is always maintained at the optimum level.
condenser. Now, the steam leaves the last row at a velocity which depends
upon the conditions prevailing at that point. As this velocity is not utilized
usefully it represents a loss of possible work. This is known as the 'Leaving
Loss'. There is always a leaving loss but as the back pressure is reduced its
magnitude increases rapidly. For example, if the back pressure is 60 mbar
the loss would be a certain value. If the back pressure is reduced to 30 mbar
the specific volume of the steam will be approximately doubled, and so the
velocity of the steam through the fixed annulus must also double. But the
leaving loss varies as the squar£ of the velocity, and consequently will
increase four times.
Increased wetness of steam. The lower the back pressure the greater the
wetness of the steam. The extra moisture could result in damage to the
moving blades. In addition the volume of steam is reduced. Thus at 30 mbar
back pressure the volume of the steam without wetness would be 45.7 m3/kg.
If there were 10% wetness the steam volume per kg would be reduced to
41.1 m3. As a rough guide it can be assumed that every 1% wetness will
reduce the efficiency of the associated stage by 1%.
102 r-
1-
c ioi I—
o
'■*->
a
E
c
o
100h
50 40
Back pressure, millibars abs.
30 h
E 20r-
0)
k-
a
■g 10
QQ
_L J-
40 60 80 100 120
Load, MW
Figure 11.3 Minimum back pressure for various loads— 120MWT/A
Deviation due to CW inlet temperature. Plot a line vertically from the actual
CW inlet temperature of 18.2°C to the intersection with the optimum 'CW
rise' of 8.5°C. Thence plot horizontally to the intersection with the optimum
'terminal temperature difference' (l "I'D) line, and then vertically downward
to cut the 'saturated steam temperature' line. The corresponding back
pressure is 47.2 mbar. Hence, the loss due to the high CW inlet temperature
is the difference in back pressure between 47.7 mbar and the optimum value
of 43.65, i.e. 4.05 mbar.
Deviation due to CW flow. Plot a line from the actual CW inlet temperature
vertically to the intersection with the actual CW rise of 10.0°C. Thence plot
horizontally to the optimum TTD, then vertically downward to the satura-
tion temperature of 33.7°C. The corresponding back pressure is 52.0 mbar
so the loss due to incorrect CW flow is given by 52.0 - 47.7 = 4.30 mbar.
Deviation due to air/dirty tubes. The effect of air and dirty tubes on heat
transfer is to increase the TTD above optimum. As they both give the same
effect they are lumped together in this exercise. (Note: They can be segre-
gated, as will be shown later). Plot from the actual CW inlet temperature to
the actual CW rise and thence across to the actual TTD line of 7°C. Plotting
vertically downward the saturated steam temperature is 35.1°C, and the
back pressure is 56.22 mbar. So the deviation due to air/dirty tubes is given
by 56.22 - 52.0 mbar = 4.22 mbar.
The effect of air ingress into the condenser is to increase the value of the
10 c
Terminal temperature 9
difference °C 8
7
6
5
'air suction depression' from optimum. In the case being considered the
optimum value, obtained from the acceptance tests, is 4.5°C, but it is
actually 8°C, so there must be air present. Action should be taken to locate
and stop the ingress. Then a new set of readings can be obtained and all the
deviation due to 'air/dirty tubes' can be attributed to dirty tubes. Inciden-
tally, when condenser tubes are cleaned it is only the 'dirty tube' component
which is eliminated.
70i-
60l·
50 h
= 40
E
I 30
co 20
10 (t\o«*
M\\r^(
_L _L -L -L J_ -L
40 50 60 70 80 90 100 110 120
Load, MW
to be determined for any load and for any probable CW inlet temperature.
Thus, with a loading of 100 MW and a CW inlet temperature of 20°C the
optimum back pressure would be 43.6 mbar.
Condensers and back pressure 499
Also shown on the curve is the specified back pressure for any load, i.e.
the optimum back pressure when the CW inlet temperature is at the design
value (in this case 14.5°C), and shown by the dotted line. To derive the
curves in Figure 11.5 proceed as follows:
From design data determine the optimum CW rise and terminal tempera-
ture difference for a range of loads as in curve 2 (Figure 11.6). Thus, at 100
1 I i I , I i I i I I
0 40 60 80 100 120
Load, MW
Figure 11.6 Optimum CW. temperature rise and terminal temeperature difference —
120-MW T/A. (Curve No 2)
MW the CW rise is 7.5°C and the TTD is 3°C. Hence the saturation
temperature will be 10.5°C above the CW inlet temperature. So with a CW
inlet temperature of, say, 20°C the saturation temperature of the condensate
will be 30.5°C, which corresponds to a back pressure of 43.65 mbar. Simi-
larly, if the CW inlet temperature is 16°C the saturation temperature will be
26.5°C and the corresponding back pressure 34.6 mbar. Proceeding in this
500 Condensers and back pressure
40 r
30
20
10
-L I
0 10 20 30 40 50 60 70
Back pressure, millibars
Date
Test / 2 3 4
had been 8°C then the target back pressure would be 25.5 mbar. Line 21 is
self-explanatory.
Deviation due to air ingress. This is an entirely preventable loss and steps
should be taken to locate and stop any air ingress into the system under
vacuum as soon as the condition is detected. Remember, the resistance to
heat transfer of a layer of air 1.0 mm thick is equal to that of a slab of copper
16.5 m thick. Excessive air in the condenser may lead to an increased reading
on the condensate oxygen meter. On the other hand there are times when
the air ingress is so small that only one 50% air pump or steam ejector is
required to handle it. In such a case it is a waste of energy to run two 50%
pumps or ejectors 'just to be safe'.
Deviation due to dirty tubes. Operationally little can be done to eliminate the
cause of the loss, as the tubes must be cleaned when the condenser is out of
Condensers and back pressure 503
I ■ I ■ I ■ i I 1 1 1 J
0 100 200 300 400 500
Steam to condenser, kg/s
When air mixes with steam it has very little effect on the absolute pres-
sure. For example, mixing saturated steam with 1/2000 of its weight of air
will increase the back pressure by only about one quarter of one per cent
(0.25%) if the back pressure is 34 mbar, when only Dalton's law of partial
pressures is considered. The real trouble with air is that it is incondensable,
and so, when the steam condenses on the CW tubes, the air remains, and
may form a film on the tube surface. As stated above, air is such an excellent
insulator that it only requires a film a few molecules thick to interfere
seriously with the heat transfer, and as a result the back pressure suffers.
Fortunately it is easy to determine whether air is present merely by
measuring the temperature of the contents of the air suction pipe to the air
pumps. When there is only a little air present the temperature is very little
below the saturated steam temperature (say within 4.5°C). As more and
more air is present the temperature falls - the more air present the greater
the depression of the air suction compared to the saturated steam tempera-
ture. Preferably the thermometer should be in direct contact with the
contents of the air suction pipe.
It may happen that at very low back pressures there is an accumulation of
air in the condenser. This could be because the specific volume of the air
504 Condensers and back pressure
becomes greater the lower the back pressure. Consequently the total
volume to be handled by the air removal equipment may increase to such an
extent that the equipment cannot cope. Therefore, if the condenser perfor-
mance falls off sharply at low back pressures but returns to normal at higher
pressures (for example going from part-load to full-load operation) then
air-removal limitations should be considered a possibility.