Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Code References:
ACI 318M - 2011
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 21.6.3
for column
Maximum area of longitudinal reinforcement
2 : 21.6.3
for column
Minimum longitudinal and transverse
3 : 21.9.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 7.10.5
5 Minimum spacing of transverse ties : 7.10.5
Maximum spacing of longitudinal and
6 : 21.9.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 21.9.6
Area and spacing of special confining
8 : 21.6.4
reinforcement
9 Slenderness Moments : 10.10
Shear Strength provided by concrete for
10 : 11.2
column
11 Design of shear for non-ductile wall : 11.9
12 Design of shear for ductile wall : 21.9.4
13 Minimum Flexural Strength of Columns : 21.6.2.2
14 Shear Check at Column Joint : 21.7.4.1
15 Shear Strength of Column : 21.3.3 & 21.5.4
16 fs,perm : 10.6.4
17 fc,perm : 10.2.7.1
18 Wcr : Eq 4.2(a)
General Data
Column No. : C1
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 100
Critical Analysis Load Combination : 124
[24] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 312.65 kN
Muxt = 9.95 kNm
Muyt = 21.3 kNm
Vuxt = -60.05 kN
Vuyt = -36.82 kN
Pub = 327.07 kN
Muxb = -82.08 kNm
Muyb = 171.39 kNm
Vuxb = -60.05 kN
Vuyb = -36.82 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = 9.95 kNm
M2 = -82.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.45
8.54 < 35.45, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 173.2 mm
Klux /r = 8.54
M1 = 21.3 kNm
M2 = 171.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.51
8.54 < 32.51, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1446.53 kN
Muy = 10.23 kNm
Vuy = -69.9849 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -324.28 kNm
φVcy = 387.19 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C1
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 200
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 1162.23 kN
Muxt = 130.53 kNm
Muyt = 94.07 kNm
Vuxt = 48.47 kN
Vuyt = -78.59 kN
Pub = 1215.25 kN
Muxb = -215.18 kNm
Muyb = -119.14 kNm
Vuxb = 48.47 kN
Vuyb = -78.59 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.23
M1 = 130.53 kNm
M2 = -215.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.23 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 21.94
M1 = 94.07 kNm
M2 = -119.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.94 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1162.23 kN
Muy = 130.53 kNm
Vuy = -78.5919 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -138.24 kNm
φVcy = 366.14 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C1
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 300
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 830.33 kN
Muxt = -31.53 kNm
Muyt = -4.47 kNm
Vuxt = 65.79 kN
Vuyt = -61 kN
Pub = 849.61 kN
Muxb = -129.1 kNm
Muyb = -109.7 kNm
Vuxb = 65.79 kN
Vuyb = -61 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.93
M1 = -31.53 kNm
M2 = -129.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.07
6.93 < 31.07, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.93
M1 = -4.47 kNm
M2 = -109.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.51
6.93 < 33.51, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 849.61 kN
Mux = -129.1 kNm
Muy = -109.7 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 830.33 kN
Muy = 31.53 kNm
Vuy = -60.9965 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -160.48 kNm
φVcy = 339.93 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C1
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1050 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 301
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 799.19 kN
Muxt = 156.66 kNm
Muyt = 111.22 kNm
Vuxt = 73.35 kN
Vuyt = -123.07 kN
Pub = 818.47 kN
Muxb = -40.2 kNm
Muyb = -6.11 kNm
Vuxb = 73.35 kN
Vuyb = -123.07 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.35
M1 = -40.2 kNm
M2 = 156.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.08
6.35 < 37.08, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.06
M1 = -6.11 kNm
M2 = 111.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.66
6.06 < 34.66, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 379.08 kN
Muy = 125.64 kNm
Vuy = -101.2367 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 37.98 kNm
φVcy = 201.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C1
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 400
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 487.55 kN
Muxt = 3.58 kNm
Muyt = 29.56 kNm
Vuxt = 84.53 kN
Vuyt = -36.26 kN
Pub = 506.82 kN
Muxb = -54.42 kNm
Muyb = -105.66 kNm
Vuxb = 84.53 kN
Vuyb = -36.26 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.93
M1 = 3.58 kNm
M2 = -54.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.79
6.93 < 34.79, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.93
M1 = 29.56 kNm
M2 = -105.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.36
6.93 < 37.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 493.65 kN
Muy = 10.26 kNm
Vuy = -50.3627 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -103.9 kNm
φVcy = 311.08 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C1
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1050 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 401
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 462.51 kN
Muxt = 177.33 kNm
Muyt = 119.22 kNm
Vuxt = 64.43 kN
Vuyt = -110.06 kN
Pub = 481.79 kN
Muxb = 1.29 kNm
Muyb = 16.16 kNm
Vuxb = 64.43 kN
Vuyb = -110.06 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.35
M1 = 1.29 kNm
M2 = 177.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.91
6.35 < 33.91, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.06
M1 = 16.16 kNm
M2 = 119.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.37
6.06 < 32.37, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 339.64 kN
Muy = 128.93 kNm
Vuy = -82.9029 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 50.39 kNm
φVcy = 179.97 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C1
Level : 13.3m To 14.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 500
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 154.42 kN
Muxt = -4.92 kNm
Muyt = 13.49 kNm
Vuxt = 39.37 kN
Vuyt = -27.12 kN
Pub = 165.26 kN
Muxb = -48.3 kNm
Muyb = -49.47 kNm
Vuxb = 39.37 kN
Vuyb = -27.12 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 9.24
M1 = -4.92 kNm
M2 = -48.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.78
9.24 < 32.78, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 9.24
M1 = 13.49 kNm
M2 = -49.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.27
9.24 < 37.27, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 186.33 kN
Muy = 8.1 kNm
Vuy = -21.9209 kN
λ = 1
φ = 0.6
deff = 400 mm
ρw (50% of As provided) = 0.014
Mm = -24.51 kNm
φVcy = 161.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C1
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1050 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 501
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 163.63 kN
Muxt = 114.16 kNm
Muyt = 83.87 kNm
Vuxt = 42.76 kN
Vuyt = -71.34 kN
Pub = 174.47 kN
Muxb = 0.06 kNm
Muyb = 15.47 kNm
Vuxb = 42.76 kN
Vuyb = -71.34 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
1500 x 200 x
Bottom 195.744 No Beam 65.174 - 6.016
400
5260 x 400 x
Top 195.744 No Beam 72.601 - 2.695
500
User Defined Effective Length Factor = 1
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 8.47
M1 = 0.06 kNm
M2 = 114.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.99
8.47 < 33.99, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 8.08
M1 = 15.47 kNm
M2 = 83.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.79
8.08 < 31.79, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 146.19 kN
Muy = 74.69 kNm
Vuy = -50.3907 kN
λ = 1
φ = 0.6
deff = 400 mm
ρw (50% of As provided) = 0.014
Mm = 49.11 kNm
φVcy = 89.71 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C2
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 105
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 534.49 kN
Muxt = 0.11 kNm
Muyt = 34.86 kNm
Vuxt = -14.81 kN
Vuyt = -130.12 kN
Pub = 554.13 kN
Muxb = -325.11 kNm
Muyb = 71.88 kNm
Vuxb = -14.81 kN
Vuyb = -130.12 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = 0.11 kNm
M2 = -325.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
7.32 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = 34.86 kNm
M2 = 71.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.18
7.32 < 28.18, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 863.36 kN
Muy = 327.26 kNm
Vuy = 130.9949 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 94.96 kNm
φVcy = 253.06 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C2
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 205
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 419.33 kN
Muxt = 170.95 kNm
Muyt = -8.7 kNm
Vuxt = -16.31 kN
Vuyt = -125.77 kN
Pub = 453.89 kN
Muxb = -382.27 kNm
Muyb = 63.04 kNm
Vuxb = -16.31 kN
Vuyb = -125.77 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 170.95 kNm
M2 = -382.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.37
19.05 < 39.37, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = -8.7 kNm
M2 = 63.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.66
18.81 < 35.66, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 453.89 kN
Mux = -382.27 kNm
Muy = 63.04 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 453.89 kN
Muy = 382.27 kNm
Vuy = -125.7655 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 260.15 kNm
φVcy = 218.2 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C2
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 309
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 997.2 kN
Muxt = -201.35 kNm
Muyt = 133.08 kNm
Vuxt = 82.62 kN
Vuyt = 131.06 kN
Pub = 1049.68 kN
Muxb = 217.93 kNm
Muyb = -131.23 kNm
Vuxb = 82.62 kN
Vuyb = 131.06 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -201.35 kNm
M2 = 217.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = -131.23 kNm
M2 = 133.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 508.07 kN
Muy = 195.24 kNm
Vuy = 117.7145 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 58.54 kNm
φVcy = 277.63 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C2
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 409
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 621.02 kN
Muxt = -188.63 kNm
Muyt = 112.91 kNm
Vuxt = 60.27 kN
Vuyt = 92.56 kN
Pub = 659.58 kN
Muxb = 107.49 kNm
Muyb = -79.89 kNm
Vuxb = 60.27 kN
Vuyb = 92.56 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 107.49 kNm
M2 = -188.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -79.89 kNm
M2 = 112.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 621.02 kN
Muy = 188.63 kNm
Vuy = 92.5613 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 44.82 kNm
φVcy = 196.14 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C2
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 509
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 277.55 kN
Muxt = -115.81 kNm
Muyt = 118.45 kNm
Vuxt = 60.12 kN
Vuyt = 54.5 kN
Pub = 299.24 kN
Muxb = 58.54 kNm
Muyb = -73.89 kNm
Vuxb = 60.12 kN
Vuyb = 54.5 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 195.744 No Beam No Beam - - 5.615
5280 x 400 x 5260 x 400 x
Top 195.744 72.326 72.601 1.35
500 500
User Defined Effective Length Factor = 1
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 58.54 kNm
M2 = -115.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 20.4
M1 = -73.89 kNm
M2 = 118.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.4 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 113
[13] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 200.52 kN
Muy = 103.05 kNm
Vuy = 48.0104 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = 67.9 kNm
φVcy = 91.53 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Load Data
Analysis Reference No. = 112
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 504.27 kN
Muxt = 5.56 kNm
Muyt = 34.56 kNm
Vuxt = -16.21 kN
Vuyt = -133.28 kN
Pub = 523.9 kN
Muxb = -327.54 kNm
Muyb = 75.08 kNm
Vuxb = -16.21 kN
Vuyb = -133.28 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = 5.56 kNm
M2 = -327.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.2
7.32 < 34.2, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = 34.56 kNm
M2 = 75.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.48
7.32 < 28.48, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 114
[14] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 907.8 kN
Muy = 327.16 kNm
Vuy = -133.4015 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 82.9 kNm
φVcy = 262 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C3
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 212
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 504.41 kN
Muxt = -157.7 kNm
Muyt = 53.36 kNm
Vuxt = 35 kN
Vuyt = 122.77 kN
Pub = 538.97 kN
Muxb = 382.34 kNm
Muyb = -100.59 kNm
Vuxb = 35 kN
Vuyb = 122.77 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = -157.7 kNm
M2 = 382.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.95
19.05 < 38.95, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = 53.36 kNm
M2 = -100.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 538.97 kN
Mux = 382.34 kNm
Muy = -100.59 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 538.97 kN
Muy = 382.34 kNm
Vuy = 122.7704 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 237.33 kNm
φVcy = 219.52 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C3
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 316
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 742.04 kN
Muxt = -147.72 kNm
Muyt = 100.91 kNm
Vuxt = 60.37 kN
Vuyt = 96.4 kN
Pub = 794.53 kN
Muxb = 160.68 kNm
Muyb = -92.21 kNm
Vuxb = 60.37 kN
Vuyb = 96.4 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -147.72 kNm
M2 = 160.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = -92.21 kNm
M2 = 100.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 814.03 kN
Muy = 19.96 kNm
Vuy = -11.4334 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -199.06 kNm
φVcy = 439.93 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C3
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 416
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 450.58 kN
Muxt = -143.67 kNm
Muyt = 85.64 kNm
Vuxt = 43.06 kN
Vuyt = 67.26 kN
Pub = 489.13 kN
Muxb = 71.5 kNm
Muyb = -52.12 kNm
Vuxb = 43.06 kN
Vuyb = 67.26 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 71.5 kNm
M2 = -143.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.97
15.59 < 39.97, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -52.12 kNm
M2 = 85.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 496.81 kN
Muy = 7.83 kNm
Vuy = 3.9405 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = -107.22 kNm
φVcy = 309.95 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C3
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 516
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 182.93 kN
Muxt = -68.91 kNm
Muyt = 85.23 kNm
Vuxt = 42.79 kN
Vuyt = 29.94 kN
Pub = 204.62 kN
Muxb = 26.88 kNm
Muyb = -51.65 kNm
Vuxb = 42.79 kN
Vuyb = 29.94 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 195.744 No Beam No Beam - - 5.615
5260 x 400 x 5280 x 400 x
Top 195.744 72.601 72.326 1.35
500 500
User Defined Effective Length Factor = 1
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 26.88 kNm
M2 = -68.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.68
20.78 < 38.68, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 20.4
M1 = -51.65 kNm
M2 = 85.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.4 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 205.66 kN
Muy = 3.83 kNm
Vuy = -1.9581 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = -32.23 kNm
φVcy = 162.28 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C4
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 118
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 105.27 kN
Muxt = -18.57 kNm
Muyt = 21 kNm
Vuxt = -8.13 kN
Vuyt = -60.04 kN
Pub = 119.7 kN
Muxb = -168.64 kNm
Muyb = 41.32 kNm
Vuxb = -8.13 kN
Vuyb = -60.04 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = -18.57 kNm
M2 = -168.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.68
8.54 < 32.68, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 173.2 mm
Klux /r = 8.54
M1 = 21 kNm
M2 = 41.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.9
8.54 < 27.9, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1175.59 kN
Muy = 25.06 kNm
Vuy = 46.4545 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -246.8 kNm
φVcy = 367.16 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C4
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 218
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 882.25 kN
Muxt = -105.14 kNm
Muyt = 68.96 kNm
Vuxt = 36.74 kN
Vuyt = 75.07 kN
Pub = 935.27 kN
Muxb = 225.09 kNm
Muyb = -92.67 kNm
Vuxb = 36.74 kN
Vuyb = 75.07 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.23
M1 = -105.14 kNm
M2 = 225.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.61
22.23 < 39.61, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 21.94
M1 = 68.96 kNm
M2 = -92.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.94 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 322
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 609.07 kN
Muxt = -59.74 kNm
Muyt = 123.82 kNm
Vuxt = 74.84 kN
Vuyt = 40.51 kN
Pub = 647.63 kN
Muxb = 69.85 kNm
Muyb = -115.6 kNm
Vuxb = 74.84 kN
Vuyb = 40.51 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -59.74 kNm
M2 = 69.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -115.6 kNm
M2 = 123.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 609.07 kN
Muy = 59.74 kNm
Vuy = 40.509 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -81.11 kNm
φVcy = 321.26 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C4
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 422
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 353.15 kN
Muxt = -76.95 kNm
Muyt = 125.59 kNm
Vuxt = 62.14 kN
Vuyt = 40.05 kN
Pub = 391.71 kN
Muxb = 51.17 kNm
Muyb = -73.2 kNm
Vuxb = 62.14 kN
Vuyb = 40.05 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 51.17 kNm
M2 = -76.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -73.2 kNm
M2 = 125.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 353.15 kN
Muy = 76.95 kNm
Vuy = 40.0502 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -4.71 kNm
φVcy = 298.22 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C4
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 522
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 129.31 kN
Muxt = -55.73 kNm
Muyt = 88.82 kNm
Vuxt = 41.53 kN
Vuyt = 25.32 kN
Pub = 151 kN
Muxb = 25.28 kNm
Muyb = -44.04 kNm
Vuxb = 41.53 kN
Vuyb = 25.32 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 25.28 kNm
M2 = -55.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.44
20.78 < 39.44, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 20.4
M1 = -44.04 kNm
M2 = 88.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.95
20.4 < 39.95, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 129.31 kN
Muy = 55.73 kNm
Vuy = 25.3214 kN
λ = 1
φ = 0.6
deff = 400 mm
ρw (50% of As provided) = 0.014
Mm = 33.1 kNm
φVcy = 87.03 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C5
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 101
Critical Analysis Load Combination : 125
[25] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 520.73 kN
Muxt = 47.63 kNm
Muyt = -3.5 kNm
Vuxt = 130.58 kN
Vuyt = 20.79 kN
Pub = 540.37 kN
Muxb = 99.6 kNm
Muyb = -329.87 kNm
Vuxb = 130.58 kN
Vuyb = 20.79 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = 47.63 kNm
M2 = 99.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.26
7.32 < 28.26, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -3.5 kNm
M2 = -329.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.87
7.32 < 33.87, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1708.09 kN
Muy = 71.16 kNm
Vuy = -89.7678 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -388.42 kNm
φVcy = 512.5 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C5
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 201
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 518.37 kN
Muxt = 41.33 kNm
Muyt = 214.21 kNm
Vuxt = 144.75 kN
Vuyt = -29.77 kN
Pub = 552.93 kN
Muxb = -89.62 kNm
Muyb = -422.54 kNm
Vuxb = 144.75 kN
Vuyb = -29.77 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 41.33 kNm
M2 = -89.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.53
19.05 < 39.53, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = 214.21 kNm
M2 = -422.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1341.95 kN
Muy = 145.59 kNm
Vuy = -112.6867 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -215.48 kNm
φVcy = 484.1 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C5
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 303
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 882.04 kN
Muxt = 95.32 kNm
Muyt = -226.71 kNm
Vuxt = -137.04 kN
Vuyt = -59.05 kN
Pub = 934.52 kN
Muxb = -93.58 kNm
Muyb = 211.69 kNm
Vuxb = -137.04 kN
Vuyb = -59.05 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -93.58 kNm
M2 = 95.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = 211.69 kNm
M2 = -226.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 882.04 kN
Mux = 95.32 kNm
Muy = -226.71 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 932 kN
Muy = 160.23 kNm
Vuy = -97.8155 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -90.54 kNm
φVcy = 450.18 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C5
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 403
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 541.08 kN
Muxt = 92.68 kNm
Muyt = -196.44 kNm
Vuxt = -96.66 kN
Vuyt = -46.84 kN
Pub = 579.64 kN
Muxb = -57.18 kNm
Muyb = 112.78 kNm
Vuxb = -96.66 kN
Vuyb = -46.84 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -57.18 kNm
M2 = 92.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = 112.78 kNm
M2 = -196.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 567.02 kN
Muy = 153.49 kNm
Vuy = -71.5333 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = 22.19 kNm
φVcy = 250.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C5
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 503
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 221.38 kN
Muxt = 78.08 kNm
Muyt = -103.9 kNm
Vuxt = -51.24 kN
Vuyt = -38.61 kN
Pub = 243.07 kN
Muxb = -45.46 kNm
Muyb = 60.03 kNm
Vuxb = -51.24 kN
Vuyb = -38.61 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = -45.46 kNm
M2 = 78.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = 60.03 kNm
M2 = -103.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.54 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 227.45 kN
Muy = 103.63 kNm
Vuy = -47.1764 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 63.76 kNm
φVcy = 96.36 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C6
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 106
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 1929.47 kN
Muxt = -15.41 kNm
Muyt = -10.14 kNm
Vuxt = -46.72 kN
Vuyt = 135.38 kN
Pub = 1970.47 kN
Muxb = 322.96 kNm
Muyb = 106.62 kNm
Vuxb = -46.72 kN
Vuyb = 135.38 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 733.518 No Beam No Beam - - 1
5280 x 400 x 5260 x 400 x
Top 733.518 296.247 297.374 2.64
800 800
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major
= 0.87
Axis
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -15.41 kNm
M2 = 322.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.57
7.32 < 34.57, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -10.14 kNm
M2 = 106.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.14
7.32 < 35.14, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 888.52 kN
Muy = 333.08 kNm
Vuy = 136.5575 kN
λ = 1
φ = 0.6
deff = 644 mm
ρw (50% of As provided) = 0.016
Mm = 93.62 kNm
φVcy = 266.77 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C6
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 206
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 1653.07 kN
Muxt = -176.5 kNm
Muyt = -92.04 kNm
Vuxt = -55.17 kN
Vuyt = 131.55 kN
Pub = 1725.24 kN
Muxb = 402.14 kNm
Muyb = 150.63 kNm
Vuxb = -55.17 kN
Vuyb = 131.55 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = -176.5 kNm
M2 = 402.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.27
19.05 < 39.27, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = -92.04 kNm
M2 = 150.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -176.5 - -176.5
Major Axis Mux (bottom) 402.14 - 402.14
Minor Axis Muy (top) -92.04 - -92.04
Minor Axis Muy (bottom) 150.63 - 150.63
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 114
[14] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 1191.38 kN
Muy = 390.8 kNm
Vuy = -128.2926 kN
λ = 1
φ = 0.6
deff = 644 mm
ρw (50% of As provided) = 0.016
Mm = 69.73 kNm
φVcy = 284.66 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C6
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 310
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 1164.76 kN
Muxt = -44.33 kNm
Muyt = -227.61 kNm
Vuxt = -135.19 kN
Vuyt = 28.88 kN
Pub = 1217.24 kN
Muxb = 48.06 kNm
Muyb = 204.87 kNm
Vuxb = -135.19 kN
Vuyb = 28.88 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -44.33 kNm
M2 = 48.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = 204.87 kNm
M2 = -227.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 1164.76 kN
Mux = -44.33 kNm
Muy = -227.61 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 1346.08 kN
Muy = 7.66 kNm
Vuy = 6.093 kN
λ = 1
φ = 0.6
deff = 644 mm
ρw (50% of As provided) = 0.016
Mm = -355.11 kNm
φVcy = 481.81 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C6
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 410
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 722.84 kN
Muxt = -165.22 kNm
Muyt = -78.7 kNm
Vuxt = -40.43 kN
Vuyt = 76.77 kN
Pub = 761.4 kN
Muxb = 80.37 kNm
Muyb = 50.65 kNm
Vuxb = -40.43 kN
Vuyb = 76.77 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 80.37 kNm
M2 = -165.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.84
15.59 < 39.84, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = 50.65 kNm
M2 = -78.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 836.29 kN
Muy = 24.41 kNm
Vuy = 12.0176 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.022
Mm = -169.61 kNm
φVcy = 336.7 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C6
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 510
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 339.34 kN
Muxt = -98.79 kNm
Muyt = -56.11 kNm
Vuxt = -27.25 kN
Vuyt = 45.43 kN
Pub = 361.03 kN
Muxb = 46.54 kNm
Muyb = 31.08 kNm
Vuxb = -27.25 kN
Vuyb = 45.43 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 18.71
M1 = 46.54 kNm
M2 = -98.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.65
18.71 < 39.65, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 144.34 mm
Klux /r = 15.79
M1 = 31.08 kNm
M2 = -56.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.79 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 392.1 kN
Muy = 29.53 kNm
Vuy = 15.0694 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.032
Mm = -46.74 kNm
φVcy = 213.51 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C7
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 113
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 717.11 kN
Muxt = -0.48 kNm
Muyt = -3.64 kNm
Vuxt = 33.02 kN
Vuyt = 132.08 kN
Pub = 736.75 kN
Muxb = 329.63 kNm
Muyb = -86.17 kNm
Vuxb = 33.02 kN
Vuyb = 132.08 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -0.48 kNm
M2 = 329.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.02
7.32 < 34.02, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -3.64 kNm
M2 = -86.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.49
7.32 < 33.49, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.48 - -0.48
Major Axis Mux (bottom) 329.63 - 329.63
Minor Axis Muy (top) -3.64 - -3.64
Minor Axis Muy (bottom) -86.17 - -86.17
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 753.66 kN
Muy = 329.24 kNm
Vuy = -132.741 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 126.45 kNm
φVcy = 240.24 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C7
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 213
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 635.89 kN
Muxt = -172.35 kNm
Muyt = 60.27 kNm
Vuxt = 39.86 kN
Vuyt = 130.41 kN
Pub = 670.44 kN
Muxb = 401.3 kNm
Muyb = -115.05 kNm
Vuxb = 39.86 kN
Vuyb = 130.41 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = -172.35 kNm
M2 = 401.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.15
19.05 < 39.15, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = 60.27 kNm
M2 = -115.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 670.44 kN
Mux = 401.3 kNm
Muy = -115.05 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 670.44 kN
Muy = 401.3 kNm
Vuy = 130.4086 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 220.91 kNm
φVcy = 222.36 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C7
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 317
Critical Analysis Load Combination : 125
[25] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 448.61 kN
Muxt = -61.84 kNm
Muyt = 180.24 kNm
Vuxt = 106 kN
Vuyt = 39.48 kN
Pub = 473.74 kN
Muxb = 64.45 kNm
Muyb = -158.88 kNm
Vuxb = 106 kN
Vuyb = 39.48 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -61.84 kNm
M2 = 64.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = -158.88 kNm
M2 = 180.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 1231.71 kN
Muy = 19.47 kNm
Vuy = 12.7385 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -311.94 kNm
φVcy = 475.22 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C7
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 417
Critical Analysis Load Combination : 125
[25] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 277.4 kN
Muxt = -52.52 kNm
Muyt = 143.29 kNm
Vuxt = 67.23 kN
Vuyt = 25.49 kN
Pub = 295.86 kN
Muxb = 29.03 kNm
Muyb = -71.81 kNm
Vuxb = 67.23 kN
Vuyb = 25.49 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 29.03 kNm
M2 = -52.52 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -71.81 kNm
M2 = 143.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 772.29 kN
Muy = 6.12 kNm
Vuy = 4.8399 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = -172.71 kNm
φVcy = 333.61 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C7
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 517
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 301.29 kN
Muxt = 30.45 kNm
Muyt = -78.68 kNm
Vuxt = -37.06 kN
Vuyt = -13.68 kN
Pub = 322.97 kN
Muxb = -13.31 kNm
Muyb = 39.89 kNm
Vuxb = -37.06 kN
Vuyb = -13.68 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = -13.31 kNm
M2 = 30.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.24
20.78 < 39.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = 39.89 kNm
M2 = -78.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.54 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 30.45 - 30.45
Major Axis Mux (bottom) -13.31 - -13.31
Minor Axis Muy (top) -78.68 - -78.68
Minor Axis Muy (bottom) 39.89 - 39.89
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 355.75 kN
Muy = 5.06 kNm
Vuy = -2.5952 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = -57.31 kNm
φVcy = 175.23 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C8
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 119
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 364.15 kN
Muxt = -98.41 kNm
Muyt = 12.88 kNm
Vuxt = -29.97 kN
Vuyt = -74.37 kN
Pub = 383.78 kN
Muxb = -284.28 kNm
Muyb = 87.78 kNm
Vuxb = -29.97 kN
Vuyb = -74.37 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -98.41 kNm
M2 = -284.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 29.85
7.32 < 29.85, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = 12.88 kNm
M2 = 87.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.24
7.32 < 32.24, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 150 mm
B/4 = 175 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 150 mm
General Data
Column No. : C8
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 219
Critical Analysis Load Combination : 124
[24] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 422.88 kN
Muxt = 23.81 kNm
Muyt = -169.77 kNm
Vuxt = -115.15 kN
Vuyt = -28.97 kN
Pub = 457.43 kN
Muxb = -103.63 kNm
Muyb = 336.76 kNm
Vuxb = -115.15 kN
Vuyb = -28.97 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 23.81 kNm
M2 = -103.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.76
19.05 < 36.76, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = -169.77 kNm
M2 = 336.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1199.51 kN
Muy = 116.37 kNm
Vuy = 102.9355 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -206.38 kNm
φVcy = 472.59 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C8
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 323
Critical Analysis Load Combination : 125
[25] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 363.26 kN
Muxt = -44.86 kNm
Muyt = 165.88 kNm
Vuxt = 96.15 kN
Vuyt = 27.95 kN
Pub = 388.4 kN
Muxb = 44.56 kNm
Muyb = -141.71 kNm
Vuxb = 96.15 kN
Vuyb = 27.95 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = 44.56 kNm
M2 = -44.86 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = -141.71 kNm
M2 = 165.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 839.91 kN
Muy = 43.69 kNm
Vuy = 29.8245 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -182.3 kNm
φVcy = 442.2 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C8
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 423
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 477 kN
Muxt = -66.14 kNm
Muyt = 125.78 kNm
Vuxt = 57.63 kN
Vuyt = 32.22 kN
Pub = 515.56 kN
Muxb = 36.93 kNm
Muyb = -58.57 kNm
Vuxb = 57.63 kN
Vuyb = 32.22 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 36.93 kNm
M2 = -66.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -58.57 kNm
M2 = 125.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.59
15.3 < 39.59, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 523.74 kN
Muy = 43.61 kNm
Vuy = 23.8273 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = -77.67 kNm
φVcy = 312.34 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C8
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 523
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 201.66 kN
Muxt = -50.07 kNm
Muyt = -69.39 kNm
Vuxt = -32.77 kN
Vuyt = 23.75 kN
Pub = 223.35 kN
Muxb = 25.91 kNm
Muyb = 35.45 kNm
Vuxb = -32.77 kN
Vuyb = 23.75 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 25.91 kNm
M2 = -50.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = 35.45 kNm
M2 = -69.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.54 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 223.39 kN
Muy = 48.54 kNm
Vuy = 24.9344 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 9.38 kNm
φVcy = 142.19 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 150 mm
B/4 = 112.5 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 102
Critical Analysis Load Combination : 123
[23] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 548.77 kN
Muxt = 48.95 kNm
Muyt = 18.33 kNm
Vuxt = -126.55 kN
Vuyt = 12.74 kN
Pub = 568.41 kN
Muxb = 80.79 kNm
Muyb = 334.62 kNm
Vuxb = -126.55 kN
Vuyb = 12.74 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = 48.95 kNm
M2 = 80.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.73
7.32 < 26.73, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = 18.33 kNm
M2 = 334.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.34
7.32 < 33.34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1568.53 kN
Muy = 75.42 kNm
Vuy = -88.802 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -346.61 kNm
φVcy = 501.86 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C9
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 202
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 515.29 kN
Muxt = 44.48 kNm
Muyt = 217.49 kNm
Vuxt = 144.94 kN
Vuyt = -36.47 kN
Pub = 549.85 kN
Muxb = -115.92 kNm
Muyb = -420.09 kNm
Vuxb = 144.94 kN
Vuyb = -36.47 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 44.48 kNm
M2 = -115.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.6
19.05 < 38.6, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = 217.49 kNm
M2 = -420.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 1174.32 kN
Muy = 33.64 kNm
Vuy = -14.2072 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -282.33 kNm
φVcy = 470.52 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C9
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 304
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 357.53 kN
Muxt = 43.96 kNm
Muyt = 212.5 kNm
Vuxt = 126.18 kN
Vuyt = -25.32 kN
Pub = 382.66 kN
Muxb = -37.05 kNm
Muyb = -191.16 kNm
Vuxb = 126.18 kN
Vuyb = -25.32 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -37.05 kNm
M2 = 43.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = -191.16 kNm
M2 = 212.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 836.97 kN
Muy = 43.92 kNm
Vuy = -27.6921 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -181.28 kNm
φVcy = 441.94 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C9
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 404
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 473.09 kN
Muxt = 63.29 kNm
Muyt = 171.9 kNm
Vuxt = 81.11 kN
Vuyt = -29.82 kN
Pub = 511.65 kN
Muxb = -32.11 kNm
Muyb = -87.58 kNm
Vuxb = 81.11 kN
Vuyb = -29.82 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -32.11 kNm
M2 = 63.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = -87.58 kNm
M2 = 171.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 521.15 kN
Muy = 42.73 kNm
Vuy = -23.2248 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = -77.95 kNm
φVcy = 312.11 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C9
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 504
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 199.44 kN
Muxt = 55.31 kNm
Muyt = 86.72 kNm
Vuxt = 40.53 kN
Vuyt = -25.98 kN
Pub = 221.12 kN
Muxb = -27.79 kNm
Muyb = -42.93 kNm
Vuxb = 40.53 kN
Vuyb = -25.98 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = -27.79 kNm
M2 = 55.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = -42.93 kNm
M2 = 86.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.94
17.54 < 39.94, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 220.41 kN
Muy = 52.84 kNm
Vuy = -27.3917 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 14.2 kNm
φVcy = 124.77 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C10
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 107
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 264.97 kN
Muxt = -42.62 kNm
Muyt = -7.76 kNm
Vuxt = -44.87 kN
Vuyt = 157.98 kN
Pub = 284.61 kN
Muxb = 352.23 kNm
Muyb = 104.38 kNm
Vuxb = -44.87 kN
Vuyb = 157.98 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -42.62 kNm
M2 = 352.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.45
7.32 < 35.45, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -7.76 kNm
M2 = 104.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.89
7.32 < 34.89, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 1092.58 kN
Muy = 358.1 kNm
Vuy = 165.4142 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 64.13 kNm
φVcy = 299.75 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C10
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 207
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 239.88 kN
Muxt = -233.14 kNm
Muyt = -90.33 kNm
Vuxt = -54.2 kN
Vuyt = 158.93 kN
Pub = 274.44 kN
Muxb = 465.97 kNm
Muyb = 148.09 kNm
Vuxb = -54.2 kN
Vuyb = 158.93 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = -233.14 kNm
M2 = 465.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = -90.33 kNm
M2 = 148.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 811.02 kN
Muy = 440.48 kNm
Vuy = -148.3025 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 222.27 kNm
φVcy = 225.35 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 125
[25] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +0.3 (LOAD 1: EX) -(LOAD 2: kN
EZ)
Nu = 525.59 kN
Mux = 376.97 kNm
Vux = 128.6576 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 235.56 kNm
φVcx = 220.65 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C10
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 311
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 198.78 kN
Muxt = -226.23 kNm
Muyt = -92.09 kNm
Vuxt = -55.96 kN
Vuyt = 142.82 kN
Pub = 223.92 kN
Muxb = 230.67 kNm
Muyb = 86.93 kNm
Vuxb = -55.96 kN
Vuyb = 142.82 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -226.23 kNm
M2 = 230.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = 86.93 kNm
M2 = -92.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 698.99 kN
Muy = 237.33 kNm
Vuy = 150.3714 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 49.26 kNm
φVcy = 318.15 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C10
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 411
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 456.26 kN
Muxt = -211.04 kNm
Muyt = -85.27 kNm
Vuxt = -42.69 kN
Vuyt = 102.51 kN
Pub = 494.81 kN
Muxb = 116.9 kNm
Muyb = 51.29 kNm
Vuxb = -42.69 kN
Vuyb = 102.51 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 116.9 kNm
M2 = -211.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = 51.29 kNm
M2 = -85.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -211.04 - -211.04
Major Axis Mux (bottom) 116.9 - 116.9
Minor Axis Muy (top) -85.27 - -85.27
Minor Axis Muy (bottom) 51.29 - 51.29
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 148.49 kN
Muy = 195.93 kNm
Vuy = 94.1326 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = 161.55 kNm
φVcy = 163.68 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C10
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 511
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 223.18 kN
Muxt = -114.28 kNm
Muyt = -34.64 kNm
Vuxt = -17.91 kN
Vuyt = 54.37 kN
Pub = 244.87 kN
Muxb = 59.66 kNm
Muyb = 22.65 kNm
Vuxb = -17.91 kN
Vuyb = 54.37 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 59.66 kNm
M2 = -114.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = 22.65 kNm
M2 = -34.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.54 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 153.04 kN
Muy = 106.84 kNm
Vuy = 50.4427 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 80.01 kNm
φVcy = 93.75 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C11
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 110
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 999.92 kN
Muxt = 117.36 kNm
Muyt = 15.87 kNm
Vuxt = 18.5 kN
Vuyt = -104.37 kN
Pub = 1020.84 kN
Muxb = -143.5 kNm
Muyb = -30.35 kNm
Vuxb = 18.5 kN
Vuyb = -104.37 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.7
r = 144.34 mm
Kluy /r = 8.24
M1 = 117.36 kNm
M2 = -143.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.24 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.75
r = 144.34 mm
Klux /r = 8.83
M1 = 15.87 kNm
M2 = -30.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.83 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 387.71 kN
Muy = 141.9 kNm
Vuy = 102.5417 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.032
Mm = 66.49 kNm
φVcy = 147.56 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C11
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 210
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -70.39 kN
Muxt = -185.48 kNm
Muyt = -16.19 kNm
Vuxt = -11.56 kN
Vuyt = 94.19 kN
Pub = -52.76 kN
Muxb = 228.87 kNm
Muyb = 34.64 kNm
Vuxb = -11.56 kN
Vuyb = 94.19 kN
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 693.82 kN
Muy = 225.77 kNm
Vuy = -92.3271 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.032
Mm = 90.82 kNm
φVcy = 130.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C11
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 314
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -8.69 kN
Muxt = -190.61 kNm
Muyt = -14.17 kNm
Vuxt = -7.82 kN
Vuyt = 128.95 kN
Pub = 4.13 kN
Muxb = 221.92 kNm
Muyb = 10.86 kNm
Vuxb = -7.82 kN
Vuyb = 128.95 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 18.71
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
18.71 > 0,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 144.34 mm
Klux /r = 19.05
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
19.05 > 0, Column slender along B
Moment Magnification:
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD
Critical Load Combination = kN
6: LL2) +(LOAD 1: EX) -0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 289.51 kN
Muy = 223.92 kNm
Vuy = 130.0569 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.032
Mm = 167.61 kNm
φVcy = 122.77 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C11
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 414
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 196.21 kN
Muxt = -170.08 kNm
Muyt = 20.18 kNm
Vuxt = 10.8 kN
Vuyt = 97.43 kN
Pub = 222.99 kN
Muxb = 141.6 kNm
Muyb = -14.38 kNm
Vuxb = 10.8 kN
Vuyb = 97.43 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 298.345 No Beam No Beam - - 1.988
2140 x 400 x 3140 x 400 x
Top 298.345 178.449 121.618 1.646
500 500
User Defined Effective Length Factor = 1
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 18.71
M1 = 141.6 kNm
M2 = -170.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 144.34 mm
Klux /r = 19.05
M1 = -14.38 kNm
M2 = 20.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 301.35 kN
Muy = 159.46 kNm
Vuy = -90.9919 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.032
Mm = 100.85 kNm
φVcy = 126.85 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C11
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 514
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 109.94 kN
Muxt = -93.73 kNm
Muyt = 17.81 kNm
Vuxt = 8.33 kN
Vuyt = 50.45 kN
Pub = 131.63 kN
Muxb = 67.67 kNm
Muyb = -8.85 kNm
Vuxb = 8.33 kN
Vuyb = 50.45 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 129.9 mm
Kluy /r = 17.25
M1 = 67.67 kNm
M2 = -93.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.25 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = -8.85 kNm
M2 = 17.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.96
21.17 < 39.96, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 36.35 kN
Muy = 91.74 kNm
Vuy = 49.1191 kN
λ = 1
φ = 0.6
deff = 394 mm
ρw (50% of As provided) = 0.04
Mm = 85.35 kNm
φVcy = 94.52 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C12
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 114
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -112.47 kN
Muxt = 34.14 kNm
Muyt = -8.68 kNm
Vuxt = -41.21 kN
Vuyt = -152.25 kN
Pub = -92.83 kN
Muxb = -346.38 kNm
Muyb = 94.33 kNm
Vuxb = -41.21 kN
Vuyb = -152.25 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 92.83 kN
Muy = 346.38 kNm
Vuy = -152.2483 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 321.4 kNm
φVcy = 217.83 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C12
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 214
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -27.59 kN
Muxt = 238.84 kNm
Muyt = -85.61 kNm
Vuxt = -50.34 kN
Vuyt = -159.23 kN
Pub = 6.97 kN
Muxb = -461.6 kNm
Muyb = 135.82 kNm
Vuxb = -50.34 kN
Vuyb = -159.23 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 833.543 No Beam No Beam - - 1.524
5260 x 450 x 2140 x 450 x
Top 833.543 108.711 267.205 5.265
550 550
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
19.05 > 0,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 18.81
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
18.81 > 0, Column slender along B
Moment Magnification:
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 178.78 kN
Muy = 463.34 kNm
Vuy = -159.7904 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 415.23 kNm
φVcy = 214.37 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C12
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 318
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 485.97 kN
Muxt = 259.68 kNm
Muyt = -129.37 kNm
Vuxt = -80.26 kN
Vuyt = -165.54 kN
Pub = 538.45 kN
Muxb = -269.9 kNm
Muyb = 127.39 kNm
Vuxb = -80.26 kN
Vuyb = -165.54 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = 259.68 kNm
M2 = -269.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.11
M1 = 127.39 kNm
M2 = -129.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.11 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 485.97 kN
Muy = 259.68 kNm
Vuy = -165.5396 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 128.93 kNm
φVcy = 249.35 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
Load Data
Analysis Reference No. = 418
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 365.2 kN
Muxt = 221.7 kNm
Muyt = -112.97 kNm
Vuxt = -58.88 kN
Vuyt = -108.34 kN
Pub = 403.76 kN
Muxb = -124.89 kNm
Muyb = 75.39 kNm
Vuxb = -58.88 kN
Vuyb = -108.34 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -124.89 kNm
M2 = 221.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.3
M1 = 75.39 kNm
M2 = -112.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.3 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C12
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 518
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 200.11 kN
Muxt = 97.27 kNm
Muyt = -59.97 kNm
Vuxt = -31.86 kN
Vuyt = -47.47 kN
Pub = 221.8 kN
Muxb = -54.6 kNm
Muyb = 41.95 kNm
Vuxb = -31.86 kN
Vuyb = -47.47 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 129.9 mm
Kluy /r = 17.67
M1 = -54.6 kNm
M2 = 97.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.67 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.83
r = 129.9 mm
Klux /r = 16.93
M1 = 41.95 kNm
M2 = -59.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.93 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 200.11 kN
Muy = 97.27 kNm
Vuy = -47.4717 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 62.19 kNm
φVcy = 96.92 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C13
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 120
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 643.82 kN
Muxt = -29.39 kNm
Muyt = -8.12 kNm
Vuxt = 31.32 kN
Vuyt = 149.68 kN
Pub = 663.46 kN
Muxb = 344.72 kNm
Muyb = -86.39 kNm
Vuxb = 31.32 kN
Vuyb = 149.68 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -29.39 kNm
M2 = 344.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.02
7.32 < 35.02, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -8.12 kNm
M2 = -86.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.87
7.32 < 32.87, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 1143.1 kN
Muy = 347.22 kNm
Vuy = 151.3436 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 39.66 kNm
φVcy = 347.87 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 2.5m To 4.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1800 mm
Clear Floor Height @ luy = 1800 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 221
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 593.89 kN
Muxt = 136.96 kNm
Muyt = -33.3 kNm
Vuxt = 43.61 kN
Vuyt = 127.19 kN
Pub = 611.16 kN
Muxb = 416.7 kNm
Muyb = -129.22 kNm
Vuxb = 43.61 kN
Vuyb = 127.19 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 8.91
M1 = 136.96 kNm
M2 = 416.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.06
8.91 < 30.06, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 8.91
M1 = -33.3 kNm
M2 = -129.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.91
8.91 < 30.91, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 1399.52 kN
Muy = 427.61 kNm
Vuy = 132.7118 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 51.05 kNm
φVcy = 300.54 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1600 mm
Clear Floor Height @ luy = 1750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 220
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 1336.48 kN
Muxt = -189.82 kNm
Muyt = 95.48 kNm
Vuxt = 57.59 kN
Vuyt = 148.61 kN
Pub = 1372.56 kN
Muxb = 137.04 kNm
Muyb = -31.19 kNm
Vuxb = 57.59 kN
Vuyb = 148.61 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 8.66
M1 = 137.04 kNm
M2 = -189.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.66 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 7.92
M1 = -31.19 kNm
M2 = 95.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.92
7.92 < 37.92, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 571.29 kN
Muy = 173.44 kNm
Vuy = 142.1468 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 19.73 kNm
φVcy = 418.06 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Load Data
Analysis Reference No. = 324
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 994.09 kN
Muxt = -0.99 kNm
Muyt = -10.94 kNm
Vuxt = 86.76 kN
Vuyt = 53.76 kN
Pub = 1020.33 kN
Muxb = 85 kNm
Muyb = -149.71 kNm
Vuxb = 86.76 kN
Vuyb = 53.76 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 5.94
M1 = -0.99 kNm
M2 = 85 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.14
5.94 < 34.14, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 5.94
M1 = -10.94 kNm
M2 = -149.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.12
5.94 < 33.12, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 1105.23 kN
Muy = 2.99 kNm
Vuy = 34.9902 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -294.39 kNm
φVcy = 464.81 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 150 mm
B/4 = 175 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 150 mm
General Data
Column No. : C13
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1050 mm
Clear Floor Height @ luy = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 325
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 955.8 kN
Muxt = -88.27 kNm
Muyt = 221.05 kNm
Vuxt = 145.24 kN
Vuyt = 54.58 kN
Pub = 982.04 kN
Muxb = -0.96 kNm
Muyb = -11.27 kNm
Vuxb = 145.24 kN
Vuyb = 54.58 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 5.69
M1 = -0.96 kNm
M2 = -88.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.87
5.69 < 33.87, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 5.2
M1 = -11.27 kNm
M2 = 221.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.61
5.2 < 34.61, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 1065.41 kN
Muy = 54.21 kNm
Vuy = 35.9129 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = -232.45 kNm
φVcy = 461.49 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 424
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 557.42 kN
Muxt = -39.54 kNm
Muyt = -3.07 kNm
Vuxt = 8.25 kN
Vuyt = 85.15 kN
Pub = 576.7 kN
Muxb = 96.66 kNm
Muyb = -16.27 kNm
Vuxb = 8.25 kN
Vuyb = 85.15 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.93
M1 = -39.54 kNm
M2 = 96.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.91
6.93 < 38.91, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.93
M1 = -3.07 kNm
M2 = -16.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.74
6.93 < 31.74, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 652.36 kN
Muy = 4.67 kNm
Vuy = 27.9585 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = -146.39 kNm
φVcy = 323.52 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1050 mm
Clear Floor Height @ luy = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 425
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 526.1 kN
Muxt = -191.31 kNm
Muyt = 67.6 kNm
Vuxt = 44.2 kN
Vuyt = 94 kN
Pub = 545.38 kN
Muxb = -40.94 kNm
Muyb = -3.11 kNm
Vuxb = 44.2 kN
Vuyb = 94 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.64
M1 = -40.94 kNm
M2 = -191.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.43
6.64 < 31.43, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 6.06
M1 = -3.11 kNm
M2 = 67.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.55
6.06 < 34.55, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 526.1 kN
Muy = 191.31 kNm
Vuy = 94.0048 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = 69.49 kNm
φVcy = 189.02 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 524
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 213.52 kN
Muxt = -97.98 kNm
Muyt = 26.16 kNm
Vuxt = 12.64 kN
Vuyt = 45.49 kN
Pub = 235.21 kN
Muxb = 47.56 kNm
Muyb = -14.27 kNm
Vuxb = 12.64 kN
Vuyb = 45.49 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 195.744 No Beam No Beam - - 5.651
2920 x 300 x 5260 x 400 x
Top 195.744 71.505 72.601 1.358
450 500
User Defined Effective Length Factor = 1
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 21.17
M1 = 47.56 kNm
M2 = -97.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.82
21.17 < 39.82, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 129.9 mm
Klux /r = 17.54
M1 = -14.27 kNm
M2 = 26.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.54 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 213.52 kN
Muy = 97.98 kNm
Vuy = 45.4942 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.033
Mm = 60.55 kNm
φVcy = 96.64 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C14
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 123
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 949.04 kN
Muxt = 28.17 kNm
Muyt = -65.77 kNm
Vuxt = 60.76 kN
Vuyt = 29.29 kN
Pub = 969.12 kN
Muxb = -45.03 kNm
Muyb = 86.09 kNm
Vuxb = 60.76 kN
Vuyb = 29.29 kN
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = 28.17 kNm
M2 = -45.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 115.47 mm
Klux /r = 10.6
M1 = -65.77 kNm
M2 = 86.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.6 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 548.51 kN
Muy = 37.46 kNm
Vuy = 55.703 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.017
Mm = -89.38 kNm
φVcy = 226.2 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 2.5m To 4.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1800 mm
Clear Floor Height @ luy = 1800 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 226
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 659.42 kN
Muxt = -18.14 kNm
Muyt = 13.17 kNm
Vuxt = 49.82 kN
Vuyt = 22.37 kN
Pub = 677.09 kN
Muxb = -67.34 kNm
Muyb = 122.75 kNm
Vuxb = 49.82 kN
Vuyb = 22.37 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 10.39
M1 = -18.14 kNm
M2 = -67.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.77
10.39 < 30.77, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.81
r = 115.47 mm
Klux /r = 12.63
M1 = 13.17 kNm
M2 = 122.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.71
12.63 < 32.71, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1750 mm
Clear Floor Height @ luy = 1750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 225
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = -62.82 kN
Muxt = -8.41 kNm
Muyt = 45.6 kNm
Vuxt = -28.94 kN
Vuyt = -12.51 kN
Pub = -54.36 kN
Muxb = 19.1 kNm
Muyb = -18.05 kNm
Vuxb = -28.94 kN
Vuyb = -12.51 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 629.7 kN
Muy = 49.04 kNm
Vuy = 30.638 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -96.58 kNm
φVcy = 232.78 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 329
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 421.38 kN
Muxt = -4.74 kNm
Muyt = -3.19 kNm
Vuxt = 36.45 kN
Vuyt = 13.54 kN
Pub = 434.24 kN
Muxb = -26.39 kNm
Muyb = 55.12 kNm
Vuxb = 36.45 kN
Vuyb = 13.54 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
5260 x 300 x
Bottom 412.432 No Beam - 39.695 17.972
450
1350 x 200 x
Top 412.432 No Beam - 72.416 11.392
400
User Defined Effective Length Factor = 1
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.93
M1 = -4.74 kNm
M2 = -26.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.85
6.93 < 31.85, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 10.39
M1 = -3.19 kNm
M2 = 55.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.69
10.39 < 34.69, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 446.03 kN
Muy = 5.08 kNm
Vuy = 12.7129 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -98.06 kNm
φVcy = 217.62 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C14
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1150 mm
Clear Floor Height @ luy = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 330
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 421.14 kN
Muxt = 59.6 kNm
Muyt = -51.78 kNm
Vuxt = 30.24 kN
Vuyt = 40.5 kN
Pub = 433.99 kN
Muxb = -5.19 kNm
Muyb = -3.4 kNm
Vuxb = 30.24 kN
Vuyb = 40.5 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.64
M1 = -5.19 kNm
M2 = 59.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.04
6.64 < 35.04, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 9.96
M1 = -3.4 kNm
M2 = -51.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.21
9.96 < 33.21, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 421.14 kN
Muy = 59.6 kNm
Vuy = 40.5013 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -37.79 kNm
φVcy = 215.48 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 429
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 230.61 kN
Muxt = -13.43 kNm
Muyt = -15.02 kNm
Vuxt = 40.92 kN
Vuyt = -0.7 kN
Pub = 243.46 kN
Muxb = -12.31 kNm
Muyb = 50.43 kNm
Vuxb = 40.92 kN
Vuyb = -0.7 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 6.93
M1 = -12.31 kNm
M2 = -13.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 23
6.93 < 23, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 10.39
M1 = -15.02 kNm
M2 = 50.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.57
10.39 < 37.57, Column not slender along B
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 241.7 kN
Muy = 8.71 kNm
Vuy = 1.9395 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -47.18 kNm
φVcy = 199.4 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1150 mm
Clear Floor Height @ luy = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 430
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = -5.32 kN
Muxt = 10.6 kNm
Muyt = 53.84 kNm
Vuxt = -25.88 kN
Vuyt = 10.27 kN
Pub = 0.84 kN
Muxb = -5.82 kNm
Muyb = 12.44 kNm
Vuxb = -25.88 kN
Vuyb = 10.27 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 216.8 kN
Muy = 33.43 kNm
Vuy = 26.3249 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -16.7 kNm
φVcy = 197.06 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 527
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 90.4 kN
Muxt = 45.62 kNm
Muyt = -49.85 kNm
Vuxt = 23.11 kN
Vuyt = 17.62 kN
Pub = 116.11 kN
Muxb = -10.75 kNm
Muyb = 24.1 kNm
Vuxb = 23.11 kN
Vuyb = 17.62 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -10.75 kNm
M2 = 45.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.83
15.88 < 36.83, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 24.1 kNm
M2 = -49.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.8
23.82 < 39.8, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 105
[5] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 90.4 kN
Muy = 45.62 kNm
Vuy = 17.6209 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 24.72 kNm
φVcy = 106.84 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Load Data
Analysis Reference No. = 111
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -132.2 kN
Muxt = -100.6 kNm
Muyt = 26.48 kNm
Vuxt = 24.81 kN
Vuyt = 94.52 kN
Pub = -122.19 kN
Muxb = 135.63 kNm
Muyb = -35.52 kNm
Vuxb = 24.81 kN
Vuyb = 94.52 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 122.19 kN
Muy = 135.63 kNm
Vuy = 94.5161 kN
λ = 1
φ = 0.6
deff = 447.5 mm
ρw (50% of As provided) = 0.02
Mm = 111.92 kNm
φVcy = 115.69 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C15
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 211
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -62.88 kN
Muxt = -151.87 kNm
Muyt = 24.07 kNm
Vuxt = 15.67 kN
Vuyt = 81.52 kN
Pub = -45.25 kN
Muxb = 206.71 kNm
Muyb = -44.87 kNm
Vuxb = 15.67 kN
Vuyb = 81.52 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 746.31 kN
Muy = 206.13 kNm
Vuy = -79.6137 kN
λ = 1
φ = 0.6
deff = 447.5 mm
ρw (50% of As provided) = 0.02
Mm = 61.29 kNm
φVcy = 124.98 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C15
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 315
Critical Analysis Load Combination : 120
[20] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 7.48 kN
Muxt = -134.92 kNm
Muyt = 19.82 kNm
Vuxt = 11.57 kN
Vuyt = 93.26 kN
Pub = 20.3 kN
Muxb = 163.45 kNm
Muyb = -17.21 kNm
Vuxb = 11.57 kN
Vuyb = 93.26 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 19.05
M1 = -134.92 kNm
M2 = 163.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 144.34 mm
Klux /r = 19.05
M1 = -17.21 kNm
M2 = 19.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
Critical Load Combination = kN
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 574.12 kN
Muy = 141.62 kNm
Vuy = -80.5241 kN
λ = 1
φ = 0.6
deff = 450 mm
ρw (50% of As provided) = 0.011
Mm = 30.38 kNm
φVcy = 129.56 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C15
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 415
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = 70.44 kN
Muxt = -125.12 kNm
Muyt = -26.95 kNm
Vuxt = -14.7 kN
Vuyt = 67.55 kN
Pub = 83.26 kN
Muxb = 91 kNm
Muyb = 20.08 kNm
Vuxb = -14.7 kN
Vuyb = 67.55 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 19.05
M1 = 91 kNm
M2 = -125.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 144.34 mm
Klux /r = 19.05
M1 = 20.08 kNm
M2 = -26.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.05 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 300.94 kN
Muy = 106.3 kNm
Vuy = -55.9579 kN
λ = 1
φ = 0.6
deff = 450 mm
ρw (50% of As provided) = 0.011
Mm = 48 kNm
φVcy = 112.43 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C15
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 515
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 126.9 kN
Muxt = -85.34 kNm
Muyt = -23.59 kNm
Vuxt = -11.27 kN
Vuyt = 42.43 kN
Pub = 148.59 kN
Muxb = 50.42 kNm
Muyb = 12.47 kNm
Vuxb = -11.27 kN
Vuyb = 42.43 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 21.17
M1 = 50.42 kNm
M2 = -85.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = 12.47 kNm
M2 = -23.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 156.08 kN
Muy = 1.4 kNm
Vuy = 1.9138 kN
λ = 1
φ = 0.6
deff = 400 mm
ρw (50% of As provided) = 0.014
Mm = -25.91 kNm
φVcy = 158.76 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C16
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 115
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 1262.16 kN
Muxt = -47.46 kNm
Muyt = -32.02 kNm
Vuxt = -27.84 kN
Vuyt = 64.22 kN
Pub = 1283.08 kN
Muxb = 113.05 kNm
Muyb = 37.56 kNm
Vuxb = -27.84 kN
Vuyb = 64.22 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 190.941 No Beam No Beam - - 1
2140 x 400 x
Top 190.941 No Beam - 730.928 0.558
800
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major
= 0.73
Axis
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.73
r = 144.34 mm
Kluy /r = 8.6
M1 = -47.46 kNm
M2 = 113.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.04
8.6 < 39.04, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.7
r = 144.34 mm
Klux /r = 8.24
M1 = -32.02 kNm
M2 = 37.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.24 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 115
[15] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 65.69 kN
Muy = 112.11 kNm
Vuy = -63.0239 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.026
Mm = 99.33 kNm
φVcy = 114.13 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C16
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3800 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 215
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 749.02 kN
Muxt = -33.59 kNm
Muyt = -171.16 kNm
Vuxt = -84.2 kN
Vuyt = 20.26 kN
Pub = 785.83 kN
Muxb = 55.53 kNm
Muyb = 199.23 kNm
Vuxb = -84.2 kN
Vuyb = 20.26 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.82
r = 144.34 mm
Kluy /r = 22.72
M1 = -33.59 kNm
M2 = 55.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.72 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.69
r = 144.34 mm
Klux /r = 18.17
M1 = -171.16 kNm
M2 = 199.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 43.4 kN
Muy = 156.75 kNm
Vuy = -57.3208 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.026
Mm = 148.31 kNm
φVcy = 107.69 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Load Data
Analysis Reference No. = 319
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 523.82 kN
Muxt = -28.13 kNm
Muyt = -195.47 kNm
Vuxt = -127.4 kN
Vuyt = 18.63 kN
Pub = 550.6 kN
Muxb = 31.48 kNm
Muyb = 212.11 kNm
Vuxb = -127.4 kN
Vuyb = 18.63 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 19.4
M1 = -28.13 kNm
M2 = 31.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.4 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.86
r = 144.34 mm
Klux /r = 15.79
M1 = -195.47 kNm
M2 = 212.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.79 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD
Critical Load Combination = kN
6: LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 636.56 kN
Muy = 79.13 kNm
Vuy = 53.0454 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.026
Mm = -44.68 kNm
φVcy = 233.39 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
General Data
Column No. : C16
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 500 mm
Column D = 500 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 419
Critical Analysis Load Combination : 123
[23] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Top Joint
Put = 158.56 kN
Muxt = -29.39 kNm
Muyt = -164.99 kNm
Vuxt = -97.63 kN
Vuyt = 14.87 kN
Pub = 171.38 kN
Muxb = 18.19 kNm
Muyb = 147.33 kNm
Vuxb = -97.63 kN
Vuyb = 14.87 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 144.34 mm
Kluy /r = 19.4
M1 = 18.19 kNm
M2 = -29.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.4 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 144.34 mm
Klux /r = 18.36
M1 = 147.33 kNm
M2 = -164.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.36 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 365.02 kN
Muy = 78.93 kNm
Vuy = 39.2089 kN
λ = 1
φ = 0.6
deff = 444 mm
ρw (50% of As provided) = 0.026
Mm = 7.93 kNm
φVcy = 211.19 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 250 mm
Load Data
Analysis Reference No. = 519
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 112.04 kN
Muxt = 23.43 kNm
Muyt = 90.27 kNm
Vuxt = 51.06 kN
Vuyt = -10.41 kN
Pub = 133.73 kN
Muxb = -9.88 kNm
Muyb = -73.09 kNm
Vuxb = 51.06 kN
Vuyb = -10.41 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 21.55
M1 = -9.88 kNm
M2 = 23.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.06
21.55 < 39.06, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.8
r = 129.9 mm
Klux /r = 16.32
M1 = -73.09 kNm
M2 = 90.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.32 < 40, Column not slender along B
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 137.1 kN
Muy = 48.21 kNm
Vuy = 19.26 kN
λ = 1
φ = 0.6
deff = 394 mm
ρw (50% of As provided) = 0.032
Mm = 24.12 kNm
φVcy = 96.39 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C17
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 103
Critical Analysis Load Combination : 123
[23] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 280.12 kN
Muxt = 14.9 kNm
Muyt = -109.42 kNm
Vuxt = -138.65 kN
Vuyt = 19.99 kN
Pub = 294.54 kN
Muxb = 64.88 kNm
Muyb = 237.11 kNm
Vuxb = -138.65 kN
Vuyb = 19.99 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = 14.9 kNm
M2 = 64.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.24
8.54 < 31.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 173.2 mm
Klux /r = 8.54
M1 = -109.42 kNm
M2 = 237.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.54
8.54 < 39.54, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
Critical Load Combination = kN
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1281.05 kN
Muy = 14.2 kNm
Vuy = -85.071 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = -282.44 kNm
φVcy = 373.38 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C17
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 203
Critical Analysis Load Combination : 123
[23] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 299.02 kN
Muxt = -23.37 kNm
Muyt = -171.82 kNm
Vuxt = -108.76 kN
Vuyt = 22.21 kN
Pub = 324.41 kN
Muxb = 74.33 kNm
Muyb = 306.61 kNm
Vuxb = -108.76 kN
Vuyb = 22.21 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.23
M1 = -23.37 kNm
M2 = 74.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.77
22.23 < 37.77, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 22.81
M1 = -171.82 kNm
M2 = 306.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1016.19 kN
Muy = 263.54 kNm
Vuy = -89.2748 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 28.23 kNm
φVcy = 223.58 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C17
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 305
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 576.12 kN
Muxt = 76.41 kNm
Muyt = -210.9 kNm
Vuxt = -121.86 kN
Vuyt = -46.19 kN
Pub = 614.68 kN
Muxb = -71.38 kNm
Muyb = 178.95 kNm
Vuxb = -121.86 kN
Vuyb = -46.19 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -71.38 kNm
M2 = 76.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.88
M1 = 178.95 kNm
M2 = -210.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 661.51 kN
Muy = 147.93 kNm
Vuy = -88.0656 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = -5.25 kNm
φVcy = 324.3 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C17
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 405
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 352.9 kN
Muxt = 43.98 kNm
Muyt = -112.3 kNm
Vuxt = -59.71 kN
Vuyt = -23.07 kN
Pub = 374.59 kN
Muxb = -29.83 kNm
Muyb = 78.73 kNm
Vuxb = -59.71 kN
Vuyb = -23.07 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 618.648 No Beam No Beam - - 17.035
5260 x 400 x
Top 618.648 No Beam 72.601 - 11.212
500
User Defined Effective Length Factor = 1
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -29.83 kNm
M2 = 43.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.88
M1 = 78.73 kNm
M2 = -112.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 408.54 kN
Muy = 40.87 kNm
Vuy = -22.7282 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = -53.73 kNm
φVcy = 301.98 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Load Data
Analysis Reference No. = 505
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 135.93 kN
Muxt = 54.14 kNm
Muyt = -121.3 kNm
Vuxt = -68.24 kN
Vuyt = -30.91 kN
Pub = 157.62 kN
Muxb = -44.74 kNm
Muyb = 97 kNm
Vuxb = -68.24 kN
Vuyb = -30.91 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = -44.74 kNm
M2 = 54.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.78 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = 97 kNm
M2 = -121.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 156.57 kN
Muy = 89 kNm
Vuy = -46.0869 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = 61.55 kNm
φVcy = 92.28 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 112.5 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 108
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 505.93 kN
Muxt = -14.44 kNm
Muyt = -2.13 kNm
Vuxt = -41.61 kN
Vuyt = 148.87 kN
Pub = 525.57 kN
Muxb = 357.65 kNm
Muyb = 101.88 kNm
Vuxb = -41.61 kN
Vuyb = 148.87 kN
Along B
Q = 0.005
0.005< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = -14.44 kNm
M2 = 357.65 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.48
7.32 < 34.48, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = -2.13 kNm
M2 = 101.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.25
7.32 < 34.25, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 113
[13] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 972.6 kN
Muy = 343.86 kNm
Vuy = 146.7002 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 82.18 kNm
φVcy = 268.85 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C18
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 208
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 437.02 kN
Muxt = -218.81 kNm
Muyt = -53.57 kNm
Vuxt = -41.22 kN
Vuyt = 156.96 kN
Pub = 471.57 kN
Muxb = 471.63 kNm
Muyb = 127.75 kNm
Vuxb = -41.22 kN
Vuyb = 156.96 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = -218.81 kNm
M2 = 471.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.57
19.05 < 39.57, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 19.55
M1 = -53.57 kNm
M2 = 127.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.03
19.55 < 39.03, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 645.82 kN
Muy = 452.9 kNm
Vuy = -149.4561 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 279.13 kNm
φVcy = 220.23 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C18
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 312
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = 314.48 kN
Muxt = -197.87 kNm
Muyt = -50.04 kNm
Vuxt = -25.22 kN
Vuyt = 121.9 kN
Pub = 339.62 kN
Muxb = 192.1 kNm
Muyb = 30.65 kNm
Vuxb = -25.22 kN
Vuyb = 121.9 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = 192.1 kNm
M2 = -197.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.61
M1 = 30.65 kNm
M2 = -50.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.61 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 419.06 kN
Muy = 186.31 kNm
Vuy = -114.319 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 73.56 kNm
φVcy = 259.86 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C18
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 412
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 493.66 kN
Muxt = -176.19 kNm
Muyt = -67.49 kNm
Vuxt = -32.72 kN
Vuyt = 81.15 kN
Pub = 532.21 kN
Muxb = 83.44 kNm
Muyb = 37.18 kNm
Vuxb = -32.72 kN
Vuyb = 81.15 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = 83.44 kNm
M2 = -176.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.68
15.59 < 39.68, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.88
M1 = 37.18 kNm
M2 = -67.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 493.66 kN
Muy = 176.19 kNm
Vuy = 81.1534 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 61.87 kNm
φVcy = 177.31 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C18
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 512
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 219.87 kN
Muxt = 70.81 kNm
Muyt = -63.77 kNm
Vuxt = -33.16 kN
Vuyt = -29.63 kN
Pub = 241.56 kN
Muxb = -23.99 kNm
Muyb = 42.32 kNm
Vuxb = -33.16 kN
Vuyb = -29.63 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = -23.99 kNm
M2 = 70.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.07
20.78 < 38.07, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = 42.32 kNm
M2 = -63.77 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 252.43 kN
Muy = 6.7 kNm
Vuy = 4.3262 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = -37.55 kNm
φVcy = 166.43 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C19
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 116
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 377.55 kN
Muxt = 2.65 kNm
Muyt = 31.27 kNm
Vuxt = 50.18 kN
Vuyt = -142.21 kN
Pub = 397.19 kN
Muxb = -352.78 kNm
Muyb = -94.14 kNm
Vuxb = 50.18 kN
Vuyb = -142.21 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 202.07 mm
Kluy /r = 7.32
M1 = 2.65 kNm
M2 = -352.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.09
7.32 < 34.09, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 202.07 mm
Klux /r = 7.32
M1 = 31.27 kNm
M2 = -94.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.99
7.32 < 37.99, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 1111.26 kN
Muy = 353.4 kNm
Vuy = -142.5928 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 54.4 kNm
φVcy = 301.36 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C19
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3850 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 216
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 289.66 kN
Muxt = 204.96 kNm
Muyt = 59.37 kNm
Vuxt = 39.75 kN
Vuyt = -151.34 kN
Pub = 324.22 kN
Muxb = -460.75 kNm
Muyb = -115.5 kNm
Vuxb = 39.75 kN
Vuyb = -151.34 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 19.05
M1 = 204.96 kNm
M2 = -460.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.34
19.05 < 39.34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 19.55
M1 = 59.37 kNm
M2 = -115.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.55 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 113
[13] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 723.36 kN
Muy = 427.39 kNm
Vuy = 138.9481 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 232.77 kNm
φVcy = 222.62 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C19
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 700 mm
Column D = 700 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 320
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 119.13 kN
Muxt = 69.71 kNm
Muyt = 190.02 kNm
Vuxt = 106.82 kN
Vuyt = -42.18 kN
Pub = 144.26 kN
Muxb = -65.23 kNm
Muyb = -151.71 kNm
Vuxb = 106.82 kN
Vuyb = -42.18 kN
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 202.07 mm
Kluy /r = 13.36
M1 = -65.23 kNm
M2 = 69.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 202.07 mm
Klux /r = 13.61
M1 = -151.71 kNm
M2 = 190.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
13.61 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 115
[15] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 401.5 kN
Muy = 185.99 kNm
Vuy = -114.2419 kN
λ = 1
φ = 0.6
deff = 647.5 mm
ρw (50% of As provided) = 0.013
Mm = 77.97 kNm
φVcy = 256.4 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C19
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 420
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 95.62 kN
Muxt = 64.1 kNm
Muyt = 153.56 kNm
Vuxt = 74.67 kN
Vuyt = -29.43 kN
Pub = 114.08 kN
Muxb = -30.06 kNm
Muyb = -85.3 kNm
Vuxb = 74.67 kN
Vuyb = -29.43 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.59
M1 = -30.06 kNm
M2 = 64.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.63
15.59 < 39.63, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.88
M1 = -85.3 kNm
M2 = 153.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 497.64 kN
Muy = 39.28 kNm
Vuy = 16.9038 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = -75.96 kNm
φVcy = 310.02 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C19
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 520
Critical Analysis Load Combination : 123
[23] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Top Joint
Put = 88.79 kN
Muxt = -22.05 kNm
Muyt = -79.55 kNm
Vuxt = -38.87 kN
Vuyt = 8.44 kN
Pub = 99.18 kN
Muxb = 4.94 kNm
Muyb = 44.82 kNm
Vuxb = -38.87 kN
Vuyb = 8.44 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 20.78
M1 = 4.94 kNm
M2 = -22.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.69
20.78 < 36.69, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.84
r = 129.9 mm
Klux /r = 17.78
M1 = 44.82 kNm
M2 = -79.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.78 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 88.79 kN
Mux = -22.05 kNm
Muy = -79.55 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 189.47 kN
Muy = 7.3 kNm
Vuy = -4.7555 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = -25.91 kNm
φVcy = 160.82 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C20
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 121
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 433.19 kN
Muxt = -103.4 kNm
Muyt = -34.26 kNm
Vuxt = -34.17 kN
Vuyt = 136.98 kN
Pub = 447.61 kN
Muxb = 238.94 kNm
Muyb = 51.13 kNm
Vuxb = -34.17 kN
Vuyb = 136.98 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = -103.4 kNm
M2 = 238.94 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.19
8.54 < 39.19, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 173.2 mm
Klux /r = 8.54
M1 = -34.26 kNm
M2 = 51.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.54 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 447.61 kN
Muy = 238.94 kNm
Vuy = 136.9752 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 135.29 kNm
φVcy = 169.83 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C20
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 223
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2)
Load Combination =
+(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 404.22 kN
Muxt = -160.64 kNm
Muyt = -43.66 kNm
Vuxt = -24.32 kN
Vuyt = 108.92 kN
Pub = 429.6 kN
Muxb = 318.47 kNm
Muyb = 63.34 kNm
Vuxb = -24.32 kN
Vuyb = 108.92 kN
Along B
Q = 0.019
0.019< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.81
M1 = -160.64 kNm
M2 = 318.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.81 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 22.81
M1 = -43.66 kNm
M2 = 63.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.81 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 549.71 kN
Muy = 285.34 kNm
Vuy = -94.2323 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 158.05 kNm
φVcy = 159.42 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C20
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 327
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 743.88 kN
Muxt = -104.39 kNm
Muyt = -221.12 kNm
Vuxt = -129.69 kN
Vuyt = 61.69 kN
Pub = 782.43 kN
Muxb = 92.96 kNm
Muyb = 193.79 kNm
Vuxb = -129.69 kN
Vuyb = 61.69 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 618.648 No Beam No Beam - - 5.926
2920 x 300 x 5260 x 400 x
Top 618.648 71.505 72.601 7.512
450 500
User Defined Effective Length Factor = 1
Along B
Q = 0.015
0.015< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 92.96 kNm
M2 = -104.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 173.2 mm
Klux /r = 15.88
M1 = 193.79 kNm
M2 = -221.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 268.71 kN
Muy = 176.08 kNm
Vuy = 102.5024 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.014
Mm = 113.86 kNm
φVcy = 167.02 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 300 mm
General Data
Column No. : C20
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 427
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 430.75 kN
Muxt = -113.05 kNm
Muyt = -62.87 kNm
Vuxt = -35.11 kN
Vuyt = 58.3 kN
Pub = 452.44 kN
Muxb = 73.45 kNm
Muyb = 49.45 kNm
Vuxb = -35.11 kN
Vuyb = 58.3 kN
Along B
Q = 0.012
0.012< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 73.45 kNm
M2 = -113.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = 49.45 kNm
M2 = -62.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 102
[2] : 1.4 (LOAD 3: DL1) +1.4 (LOAD 4:
Critical Load Combination = DL2) +1.6 (LOAD 5: LL1) +1.6 (LOAD kN
6: LL2) +0.5 (LOAD 7: LLR)
Nu = 553.01 kN
Muy = 32.37 kNm
Vuy = 18.1557 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.018
Mm = -95.69 kNm
φVcy = 248.03 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C20
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 450 mm
Column D = 450 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 525
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 152.8 kN
Muxt = -107.17 kNm
Muyt = -65.04 kNm
Vuxt = -40.27 kN
Vuyt = 58.67 kN
Pub = 174.49 kN
Muxb = 80.53 kNm
Muyb = 63.81 kNm
Vuxb = -40.27 kN
Vuyb = 58.67 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 129.9 mm
Kluy /r = 21.17
M1 = 80.53 kNm
M2 = -107.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 129.9 mm
Klux /r = 21.17
M1 = 63.81 kNm
M2 = -65.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.17 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 119
[19] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) +(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 59.26 kN
Muy = 89.51 kNm
Vuy = 47.44 kN
λ = 1
φ = 0.6
deff = 397.5 mm
ρw (50% of As provided) = 0.025
Mm = 79.12 kNm
φVcy = 89.58 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 225 mm
General Data
Column No. : C21
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 124
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 928.3 kN
Muxt = -34.73 kNm
Muyt = -64.59 kNm
Vuxt = 61.3 kN
Vuyt = -28.69 kN
Pub = 948.39 kN
Muxb = 36.98 kNm
Muyb = 88.62 kNm
Vuxb = 61.3 kN
Vuyb = -28.69 kN
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.75
r = 173.2 mm
Kluy /r = 7.36
M1 = -34.73 kNm
M2 = 36.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
7.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 115.47 mm
Klux /r = 10.6
M1 = -64.59 kNm
M2 = 88.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.6 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 118
[18] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -0.3 (LOAD 1: EX) -(LOAD 2: kN
EZ)
Nu = 429.12 kN
Muy = 115.25 kNm
Vuy = 72.3283 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = 16.01 kNm
φVcy = 208.25 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C21
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 228
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 6.18 kN
Muxt = 4.79 kNm
Muyt = 55.6 kNm
Vuxt = -37.87 kN
Vuyt = 5.29 kN
Pub = 23.11 kN
Muxb = -18.48 kNm
Muyb = -110.99 kNm
Vuxb = -37.87 kN
Vuyb = 5.29 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.84
r = 173.2 mm
Kluy /r = 19.16
M1 = 4.79 kNm
M2 = -18.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.11
19.16 < 37.11, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.81
r = 115.47 mm
Klux /r = 27.71
M1 = 55.6 kNm
M2 = -110.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.71 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 124
[24] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -0.3 (LOAD 1: EX) +(LOAD 2: kN
EZ)
Nu = 101.48 kN
Muy = 172.37 kNm
Vuy = -59.0092 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 148.91 kNm
φVcy = 102.37 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C21
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 332
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 475.2 kN
Muxt = -37.04 kNm
Muyt = -60.47 kNm
Vuxt = 35.85 kN
Vuyt = -24.07 kN
Pub = 500.91 kN
Muxb = 39.97 kNm
Muyb = 54.22 kNm
Vuxb = 35.85 kN
Vuyb = -24.07 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -37.04 kNm
M2 = 39.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 54.22 kNm
M2 = -60.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 270.17 kN
Muy = 97.88 kNm
Vuy = -56.4201 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 35.41 kNm
φVcy = 119.25 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Load Data
Analysis Reference No. = 432
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 278.72 kN
Muxt = -36.77 kNm
Muyt = -64.44 kNm
Vuxt = 35.01 kN
Vuyt = -22.92 kN
Pub = 304.42 kN
Muxb = 36.55 kNm
Muyb = 47.57 kNm
Vuxb = 35.01 kN
Vuyb = -22.92 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 36.55 kNm
M2 = -36.77 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 47.57 kNm
M2 = -64.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C21
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 528
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX)
+(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 82.9 kN
Muxt = -85.36 kNm
Muyt = -27.34 kNm
Vuxt = 12.74 kN
Vuyt = -39.05 kN
Pub = 108.61 kN
Muxb = 39.56 kNm
Muyb = 13.43 kNm
Vuxb = 12.74 kN
Vuyb = -39.05 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 39.56 kNm
M2 = -85.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.56
15.88 < 39.56, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 13.43 kNm
M2 = -27.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.9
23.82 < 39.9, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 102.91 kN
Muy = 20.57 kNm
Vuy = 3.3773 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -3.22 kNm
φVcy = 186.01 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C22
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 104
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -102.66 kN
Muxt = 58.28 kNm
Muyt = 19.2 kNm
Vuxt = -21.16 kN
Vuyt = 83.72 kN
Pub = -93.04 kN
Muxb = -150.97 kNm
Muyb = -33.68 kNm
Vuxb = -21.16 kN
Vuyb = 83.72 kN
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 155.23 kN
Muy = 149.77 kNm
Vuy = 82.3524 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = 113.87 kNm
φVcy = 114.63 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C22
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 204
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -8.43 kN
Muxt = 69.21 kNm
Muyt = 23.16 kNm
Vuxt = -15.06 kN
Vuyt = 55.77 kN
Pub = 8.49 kN
Muxb = -176.13 kNm
Muyb = -43.11 kNm
Vuxb = -15.06 kN
Vuyb = 55.77 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.81
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
22.81 > 0,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.85
r = 115.47 mm
Klux /r = 29.08
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
29.08 > 0, Column slender along B
Moment Magnification:
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -0.3 (LOAD 1: EX) -(LOAD 2: kN
EZ)
Nu = 8.49 kN
Muy = 176.13 kNm
Vuy = 55.7726 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 174.16 kNm
φVcy = 101.3 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C22
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 306
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 266.29 kN
Muxt = 16.7 kNm
Muyt = 63.16 kNm
Vuxt = -36.82 kN
Vuyt = 6.77 kN
Pub = 291.99 kN
Muxb = -4.97 kNm
Muyb = -54.63 kNm
Vuxb = -36.82 kN
Vuyb = 6.77 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -4.97 kNm
M2 = 16.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.57
15.88 < 37.57, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = -54.63 kNm
M2 = 63.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C22
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 406
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 169.01 kN
Muxt = 25.3 kNm
Muyt = 72.72 kNm
Vuxt = -38.98 kN
Vuyt = 9.57 kN
Pub = 194.72 kN
Muxb = -5.31 kNm
Muyb = -51.98 kNm
Vuxb = -38.98 kN
Vuyb = 9.57 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -5.31 kNm
M2 = 25.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.52
15.88 < 36.52, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = -51.98 kNm
M2 = 72.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 205.59 kN
Muy = 17.37 kNm
Vuy = -10.339 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -30.18 kNm
φVcy = 196 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C22
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 506
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) -0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 69.8 kN
Muxt = -0.24 kNm
Muyt = 70.26 kNm
Vuxt = -31.82 kN
Vuyt = -4.85 kN
Pub = 95.5 kN
Muxb = 15.29 kNm
Muyb = -31.53 kNm
Vuxb = -31.82 kN
Vuyb = -4.85 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -0.24 kNm
M2 = 15.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.19
15.88 < 34.19, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = -31.53 kNm
M2 = 70.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.39
23.82 < 39.39, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 91.81 kN
Muy = 52.87 kNm
Vuy = -17.4574 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 31.63 kNm
φVcy = 104.56 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 91.81 kN
Mux = 43.54 kNm
Vux = -22.5036 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.012
Mm = 29.2 kNm
φVcx = 99.3 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C23
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 109
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 821.35 kN
Muxt = -21.34 kNm
Muyt = -66.01 kNm
Vuxt = 62.79 kN
Vuyt = -27.3 kN
Pub = 841.43 kN
Muxb = 46.9 kNm
Muyb = 90.92 kNm
Vuxb = 62.79 kN
Vuyb = -27.3 kN
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = -21.34 kNm
M2 = 46.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.46
8.54 < 39.46, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 115.47 mm
Klux /r = 10.45
M1 = -66.01 kNm
M2 = 90.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.45 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 370.55 kN
Muy = 139.8 kNm
Vuy = 79.3371 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.037
Mm = 53.83 kNm
φVcy = 162.18 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C23
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 209
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 622.65 kN
Muxt = -28 kNm
Muyt = -65.04 kNm
Vuxt = 42.07 kN
Vuyt = -19.94 kN
Pub = 657.99 kN
Muxb = 59.72 kNm
Muyb = 120.01 kNm
Vuxb = 42.07 kN
Vuyb = -19.94 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 299.95 No Beam No Beam - - 1.081
3000 x 300 x
Top 299.95 No Beam 69.598 - 10.227
450
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.81
M1 = -28 kNm
M2 = 59.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.63
22.81 < 39.63, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.8
r = 115.47 mm
Klux /r = 27.37
M1 = -65.04 kNm
M2 = 120.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.37 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 743.53 kN
Muy = 71.93 kNm
Vuy = -55.1231 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.029
Mm = -100.57 kNm
φVcy = 239.06 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C23
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 313
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 453.55 kN
Muxt = -23.62 kNm
Muyt = -69.3 kNm
Vuxt = 40.17 kN
Vuyt = -12.53 kN
Pub = 479.26 kN
Muxb = 16.48 kNm
Muyb = 59.2 kNm
Vuxb = 40.17 kN
Vuyb = -12.53 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 16.48 kNm
M2 = -23.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 59.2 kNm
M2 = -69.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 533.35 kN
Muy = 57.38 kNm
Vuy = -29.1984 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.029
Mm = -66.36 kNm
φVcy = 222.5 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Load Data
Analysis Reference No. = 413
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 283.18 kN
Muxt = -30.24 kNm
Muyt = -74.15 kNm
Vuxt = 41.09 kN
Vuyt = -14.79 kN
Pub = 308.88 kN
Muxb = 17.08 kNm
Muyb = 57.3 kNm
Vuxb = 41.09 kN
Vuyb = -14.79 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 17.08 kNm
M2 = -30.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 57.3 kNm
M2 = -74.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C23
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 513
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 118.96 kN
Muxt = -19.52 kNm
Muyt = -60.28 kNm
Vuxt = 27.56 kN
Vuyt = -7.03 kN
Pub = 144.66 kN
Muxb = 2.97 kNm
Muyb = 27.87 kNm
Vuxb = 27.56 kN
Vuyb = -7.03 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 2.97 kNm
M2 = -19.52 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.83
15.88 < 35.83, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 27.87 kNm
M2 = -60.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.55
23.82 < 39.55, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 133.41 kN
Muy = 45.72 kNm
Vuy = -14.8769 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = 14.87 kNm
φVcy = 121.48 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C24
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 117
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 786.55 kN
Muxt = -18.55 kNm
Muyt = -58.86 kNm
Vuxt = 58.55 kN
Vuyt = -23.15 kN
Pub = 806.64 kN
Muxb = 39.32 kNm
Muyb = 87.47 kNm
Vuxb = 58.55 kN
Vuyb = -23.15 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = -18.55 kNm
M2 = 39.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.66
8.54 < 39.66, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 115.47 mm
Klux /r = 10.45
M1 = -58.86 kNm
M2 = 87.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.45 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 117
[17] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) +0.3 (LOAD 1: EX) -(LOAD 2: kN
EZ)
Nu = 201.13 kN
Muy = 127.96 kNm
Vuy = 72.9527 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.04
Mm = 81.3 kNm
φVcy = 139.31 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C24
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 217
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 610.46 kN
Muxt = -21.76 kNm
Muyt = -62.37 kNm
Vuxt = 40.45 kN
Vuyt = -15.55 kN
Pub = 645.8 kN
Muxb = 46.64 kNm
Muyb = 115.55 kNm
Vuxb = 40.45 kN
Vuyb = -15.55 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.81
M1 = -21.76 kNm
M2 = 46.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.6
22.81 < 39.6, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.8
r = 115.47 mm
Klux /r = 27.37
M1 = -62.37 kNm
M2 = 115.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.37 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 732.61 kN
Muy = 66.08 kNm
Vuy = -50.8842 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = -103.34 kNm
φVcy = 240.86 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C24
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 321
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 446.44 kN
Muxt = -19.99 kNm
Muyt = -68.16 kNm
Vuxt = 39.44 kN
Vuyt = -11.45 kN
Pub = 472.15 kN
Muxb = 16.65 kNm
Muyb = 58.01 kNm
Vuxb = 39.44 kN
Vuyb = -11.45 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 16.65 kNm
M2 = -19.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 58.01 kNm
M2 = -68.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 527.5 kN
Muy = 55 kNm
Vuy = -28.2926 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = -66.99 kNm
φVcy = 224.47 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C24
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 421
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 280.32 kN
Muxt = -25.23 kNm
Muyt = -74.25 kNm
Vuxt = 40.96 kN
Vuyt = -13.05 kN
Pub = 306.02 kN
Muxb = 16.53 kNm
Muyb = 56.79 kNm
Vuxb = 40.96 kN
Vuyb = -13.05 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 16.53 kNm
M2 = -25.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 56.79 kNm
M2 = -74.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -25.23 - -25.23
Major Axis Mux (bottom) 16.53 - 16.53
Minor Axis Muy (top) -74.25 - -74.25
Minor Axis Muy (bottom) 56.79 - 56.79
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 324.22 kN
Muy = 69.89 kNm
Vuy = -33.4981 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = -5.08 kNm
φVcy = 206.95 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Load Data
Analysis Reference No. = 521
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 118.27 kN
Muxt = -20.26 kNm
Muyt = -56.85 kNm
Vuxt = 26.07 kN
Vuyt = -8.16 kN
Pub = 143.97 kN
Muxb = 5.86 kNm
Muyb = 26.54 kNm
Vuxb = 26.07 kN
Vuyb = -8.16 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 5.86 kNm
M2 = -20.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.47
15.88 < 37.47, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 26.54 kNm
M2 = -56.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.6
23.82 < 39.6, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C25
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 122
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 454.34 kN
Muxt = -18.73 kNm
Muyt = -79.67 kNm
Vuxt = 70.89 kN
Vuyt = -20.74 kN
Pub = 474.43 kN
Muxb = 33.12 kNm
Muyb = 97.5 kNm
Vuxb = 70.89 kN
Vuyb = -20.74 kN
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 173.2 mm
Kluy /r = 8.54
M1 = -18.73 kNm
M2 = 33.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.69
r = 115.47 mm
Klux /r = 10.16
M1 = -79.67 kNm
M2 = 97.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.16 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
Critical Load Combination = kN
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 763.19 kN
Muy = 48.45 kNm
Vuy = -65.8302 kN
λ = 1
φ = 0.6
deff = 544 mm
ρw (50% of As provided) = 0.04
Mm = -128.61 kNm
φVcy = 240.56 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 400 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C25
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 224
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 372.08 kN
Muxt = -16.94 kNm
Muyt = -88.92 kNm
Vuxt = 51.55 kN
Vuyt = -11.95 kN
Pub = 407.43 kN
Muxb = 35.64 kNm
Muyb = 137.83 kNm
Vuxb = 51.55 kN
Vuyb = -11.95 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 22.81
M1 = -16.94 kNm
M2 = 35.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.7
22.81 < 39.7, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.78
r = 115.47 mm
Klux /r = 26.68
M1 = -88.92 kNm
M2 = 137.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
26.68 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 630.36 kN
Muy = 27.07 kNm
Vuy = -19.7762 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = -118.7 kNm
φVcy = 232.83 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C25
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 328
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 283.18 kN
Muxt = -18.06 kNm
Muyt = -100.26 kNm
Vuxt = 61.04 kN
Vuyt = -11.33 kN
Pub = 308.89 kN
Muxb = 18.17 kNm
Muyb = 95.01 kNm
Vuxb = 61.04 kN
Vuyb = -11.33 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = -18.06 kNm
M2 = 18.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 95.01 kNm
M2 = -100.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 448.61 kN
Muy = 53.68 kNm
Vuy = -27.7761 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = -50.07 kNm
φVcy = 217.84 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C25
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 428
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 185.43 kN
Muxt = -21.16 kNm
Muyt = -100.5 kNm
Vuxt = 57.56 kN
Vuyt = -12.07 kN
Pub = 211.13 kN
Muxb = 17.45 kNm
Muyb = 83.64 kNm
Vuxb = 57.56 kN
Vuyb = -12.07 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 17.45 kNm
M2 = -21.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 83.64 kNm
M2 = -100.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 271.42 kN
Muy = 64.65 kNm
Vuy = -30.6089 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = 1.89 kNm
φVcy = 202.15 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C25
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 526
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 82.09 kN
Muxt = -25.34 kNm
Muyt = -89.08 kNm
Vuxt = 45.17 kN
Vuyt = -11.36 kN
Pub = 107.79 kN
Muxb = 11.01 kNm
Muyb = 55.42 kNm
Vuxb = 45.17 kN
Vuyb = -11.36 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 11.01 kNm
M2 = -25.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.21
15.88 < 39.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 55.42 kNm
M2 = -89.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.82 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -0.3 (LOAD 1: EX) +(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 112.22 kN
Muy = 46.48 kNm
Vuy = -15.4317 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.02
Mm = 20.53 kNm
φVcy = 115.33 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C26
Level : 0m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 125
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -203.24 kN
Muxt = 8.41 kNm
Muyt = 52.28 kNm
Vuxt = -54.76 kN
Vuyt = 12.32 kN
Pub = -193.62 kN
Muxb = -22.38 kNm
Muyb = -84.59 kNm
Vuxb = -54.76 kN
Vuyb = 12.32 kN
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 108
[8] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) +(LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 699.17 kN
Muy = 40.01 kNm
Vuy = -58.6194 kN
λ = 1
φ = 0.6
deff = 547.5 mm
ρw (50% of As provided) = 0.03
Mm = -121.89 kNm
φVcy = 237.18 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C26
Level : 4.7m To 6.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 229
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = -119.54 kN
Muxt = 4.36 kNm
Muyt = 54.95 kNm
Vuxt = -37.42 kN
Vuyt = 4.7 kN
Pub = -102.62 kN
Muxb = -16.3 kNm
Muyb = -109.64 kNm
Vuxb = -37.42 kN
Vuyb = 4.7 kN
Along B
Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame
(Braced)
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C26
Level : 8.5m To 10.1m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 333
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = -73.57 kN
Muxt = 2.19 kNm
Muyt = 51.65 kNm
Vuxt = -30.19 kN
Vuyt = 1 kN
Pub = -61.26 kN
Muxb = -1.02 kNm
Muyb = -44.92 kNm
Vuxb = -30.19 kN
Vuyb = 1 kN
Along B
Q = 0.02
0.02< 0.05, Column shall be designed as non-sway frame (Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 352.35 kN
Muy = 14.44 kNm
Vuy = -9.6527 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -67.04 kNm
φVcy = 209.46 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C26
Level : 11.7m To 13.3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 433
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = -34.96 kN
Muxt = 2.66 kNm
Muyt = 58.91 kNm
Vuxt = -30.51 kN
Vuyt = 1.48 kN
Pub = -22.65 kN
Muxb = -2.07 kNm
Muyb = -38.69 kNm
Vuxb = -30.51 kN
Vuyb = 1.48 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 206.05 kN
Muy = 18.61 kNm
Vuy = -10.9764 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = -29.04 kNm
φVcy = 196.05 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C26
Level : 14.9m To 16.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 600 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 529
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Top Joint
Put = 73.99 kN
Muxt = -23.94 kNm
Muyt = -48.93 kNm
Vuxt = 21.29 kN
Vuyt = -11.32 kN
Pub = 99.7 kN
Muxb = 12.28 kNm
Muyb = 19.18 kNm
Vuxb = 21.29 kN
Vuyb = -11.32 kN
Along B
Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 173.2 mm
Kluy /r = 15.88
M1 = 12.28 kNm
M2 = -23.94 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 23.82
M1 = 19.18 kNm
M2 = -48.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.7
23.82 < 38.7, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 73.99 kN
Muy = 23.94 kNm
Vuy = -11.3222 kN
λ = 1
φ = 0.6
deff = 550 mm
ρw (50% of As provided) = 0.011
Mm = 6.83 kNm
φVcy = 120.14 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 104
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +(LOAD 1: EX) +0.3 (LOAD 2:
EZ) +0.5 (LOAD 7: LLR)
Nu = 73.99 kN
Mux = 48.93 kNm
Vux = 21.2884 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.012
Mm = 37.37 kNm
φVcx = 97.5 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 200 mm
General Data
Column No. : C27
Level : 2.5m To 4.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1800 mm
Clear Floor Height @ luy = 1800 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 222
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = 0.66 kNm
Muyt = 0.74 kNm
Vuxt = 0.18 kN
Vuyt = 22.38 kN
Pub = 48.35 kN
Muxb = -48.55 kNm
Muyb = 1.14 kNm
Vuxb = 0.18 kN
Vuyb = 22.38 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.74
r = 115.47 mm
Kluy /r = 11.54
M1 = 0.66 kNm
M2 = -48.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.16
11.54 < 34.16, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.7
r = 57.74 mm
Klux /r = 21.82
M1 = 0.74 kNm
M2 = 1.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.23
21.82 < 26.23, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD
Critical Load Combination = 4: DL2) -0.3 (LOAD 1: EX) -(LOAD 2: kN
EZ)
Nu = 16.83 kN
Muy = 42.79 kNm
Vuy = 19.7784 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 40.16 kNm
φVcy = 34.11 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C28
Level : 2.5m To 4.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1800 mm
Clear Floor Height @ luy = 1800 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 227
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = -0.66 kNm
Muyt = 0.71 kNm
Vuxt = 0.69 kN
Vuyt = 18.66 kN
Pub = 48.35 kN
Muxb = -41.7 kNm
Muyb = 2.22 kNm
Vuxb = 0.69 kN
Vuyb = 18.66 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.74
r = 115.47 mm
Kluy /r = 11.54
M1 = -0.66 kNm
M2 = -41.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.81
11.54 < 33.81, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.7
r = 57.74 mm
Klux /r = 21.82
M1 = 0.71 kNm
M2 = 2.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.17
21.82 < 30.17, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.66 - -0.66
Major Axis Mux (bottom) -41.7 - -41.7
Minor Axis Muy (top) 0.71 - 0.71
Minor Axis Muy (bottom) 2.22 - 2.22
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 48.35 kN
Muy = 41.7 kNm
Vuy = 18.6563 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 34.14 kNm
φVcy = 34.47 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C29
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 307
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 35.34 kN
Muxt = 8.66 kNm
Muyt = 0.34 kNm
Vuxt = 1.48 kN
Vuyt = -71.55 kN
Pub = 39.63 kN
Muxb = -105.79 kNm
Muyb = -2.02 kNm
Vuxb = 1.48 kN
Vuyb = -71.55 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = 8.66 kNm
M2 = -105.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.98
8 < 34.98, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 0.34 kNm
M2 = -2.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 36
14.76 < 36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 113
[13] : 1.12 (LOAD 3: DL1) +1.12
Critical Load Combination = (LOAD 4: DL2) +(LOAD 1: EX) -0.3 kN
(LOAD 2: EZ)
Nu = 23.05 kN
Muy = 75.52 kNm
Vuy = 48.8375 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 71.92 kNm
φVcy = 35.36 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C30
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 302
Critical Analysis Load Combination : 118
[18] : 1.12 (LOAD 3: DL1) +1.12 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 8.62 kN
Muxt = -3.59 kNm
Muyt = 3.76 kNm
Vuxt = 23.57 kN
Vuyt = 8.39 kN
Pub = 11.99 kN
Muxb = 9.83 kNm
Muyb = -33.94 kNm
Vuxb = 23.57 kN
Vuyb = 8.39 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -3.59 kNm
M2 = 9.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.38
8 < 38.38, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 3.76 kNm
M2 = -33.94 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.33
14.76 < 35.33, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 16.14 kN
Muy = 26.31 kNm
Vuy = 21.8648 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 23.79 kNm
φVcy = 36.98 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C31
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 308
Critical Analysis Load Combination : 116
[16] : 1.12 (LOAD 3: DL1) +1.12 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) +(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 19.67 kN
Muxt = -1.86 kNm
Muyt = 3.49 kNm
Vuxt = -9.58 kN
Vuyt = -2.56 kN
Pub = 23.05 kN
Muxb = -5.95 kNm
Muyb = 18.82 kNm
Vuxb = -9.58 kN
Vuyb = -2.56 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -1.86 kNm
M2 = -5.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.24
8 < 30.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 3.49 kNm
M2 = 18.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.77
14.76 < 31.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 115
[15] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 23.05 kN
Muy = 42.32 kNm
Vuy = -22.1085 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 38.72 kNm
φVcy = 34.64 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C32
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 326
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = 1.02 kNm
Muyt = 0.03 kNm
Vuxt = 0.83 kN
Vuyt = 64.07 kN
Pub = 46.74 kN
Muxb = -101.46 kNm
Muyb = 1.36 kNm
Vuxb = 0.83 kN
Vuyb = 64.07 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 115.47 mm
Kluy /r = 7.9
M1 = 1.02 kNm
M2 = -101.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.12
7.9 < 34.12, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 57.74 mm
Klux /r = 14.96
M1 = 0.03 kNm
M2 = 1.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.77
14.96 < 33.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42
(LOAD 4: DL2) +0.5 (LOAD 5: LL1)
Critical Load Combination = kN
+(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Nu = 46.74 kN
Muy = 101.46 kNm
Vuy = 64.0666 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 94.16 kNm
φVcy = 35.37 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C33
Level : 6.9m To 8.5m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 331
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = -1.02 kNm
Muyt = 0.15 kNm
Vuxt = 0.7 kN
Vuyt = 46.03 kN
Pub = 46.74 kN
Muxb = -74.65 kNm
Muyb = 1.27 kNm
Vuxb = 0.7 kN
Vuyb = 46.03 kN
Along B
Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 115.47 mm
Kluy /r = 7.9
M1 = -1.02 kNm
M2 = -74.65 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.84
7.9 < 33.84, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 57.74 mm
Klux /r = 14.96
M1 = 0.15 kNm
M2 = 1.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.57
14.96 < 32.57, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42
(LOAD 4: DL2) +0.5 (LOAD 5: LL1)
Critical Load Combination = kN
+(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Nu = 46.74 kN
Muy = 74.65 kNm
Vuy = 46.0318 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 67.35 kNm
φVcy = 35.39 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C34
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 407
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 35.34 kN
Muxt = 9 kNm
Muyt = 0.12 kNm
Vuxt = 0.91 kN
Vuyt = -70.57 kN
Pub = 39.63 kN
Muxb = -103.89 kNm
Muyb = -1.34 kNm
Vuxb = 0.91 kN
Vuyb = -70.57 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = 9 kNm
M2 = -103.89 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.04
8 < 35.04, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 0.12 kNm
M2 = -1.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.1
14.76 < 35.1, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 39.63 kN
Mux = -103.89 kNm
Muy = -1.34 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 122
[22] : 0.68 (LOAD 3: DL1) +0.68
Critical Load Combination = (LOAD 4: DL2) -(LOAD 1: EX) -0.3 kN
(LOAD 2: EZ)
Nu = 13.99 kN
Muy = 81.88 kNm
Vuy = -54.7458 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 79.69 kNm
φVcy = 35.42 kN
Vuy > φVcy Hence, Shear links required
General Data
Column No. : C35
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 402
Critical Analysis Load Combination : 126
[26] : 0.68 (LOAD 3: DL1) +0.68 (LOAD 4: DL2) -0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 5.23 kN
Muxt = -2.75 kNm
Muyt = 2.91 kNm
Vuxt = 21.24 kN
Vuyt = 7.57 kN
Pub = 7.28 kN
Muxb = 9.35 kNm
Muyb = -31.06 kNm
Vuxb = 21.24 kN
Vuyb = 7.57 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -2.75 kNm
M2 = 9.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.54
8 < 37.54, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 2.91 kNm
M2 = -31.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.12
14.76 < 35.12, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 107
[7] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) -0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 16.14 kN
Muy = 30.34 kNm
Vuy = 24.5724 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 27.82 kNm
φVcy = 36.74 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C36
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 408
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 35.34 kN
Muxt = -9 kNm
Muyt = 0.36 kNm
Vuxt = -2.73 kN
Vuyt = -29.91 kN
Pub = 39.63 kN
Muxb = -56.84 kNm
Muyb = 4.73 kNm
Vuxb = -2.73 kN
Vuyb = -29.91 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -9 kNm
M2 = -56.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.1
8 < 32.1, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 0.36 kNm
M2 = 4.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.09
14.76 < 33.09, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 39.63 kN
Mux = -56.84 kNm
Muy = 4.73 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 115
[15] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) -0.3 (LOAD 2: kN
EZ)
Nu = 23.05 kN
Muy = 46.42 kNm
Vuy = -24.6669 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 42.82 kNm
φVcy = 34.67 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C37
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 426
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = 1.34 kNm
Muyt = -0.19 kNm
Vuxt = 1.16 kN
Vuyt = 62.23 kN
Pub = 46.74 kN
Muxb = -98.2 kNm
Muyb = 1.66 kNm
Vuxb = 1.16 kN
Vuyb = 62.23 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 115.47 mm
Kluy /r = 7.9
M1 = 1.34 kNm
M2 = -98.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.16
7.9 < 34.16, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 57.74 mm
Klux /r = 14.96
M1 = -0.19 kNm
M2 = 1.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.36
14.96 < 35.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42
(LOAD 4: DL2) +0.5 (LOAD 5: LL1)
Critical Load Combination = kN
+(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Nu = 46.74 kN
Muy = 98.2 kNm
Vuy = 62.2292 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 90.9 kNm
φVcy = 35.4 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C38
Level : 10.1m To 11.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 431
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 42.46 kN
Muxt = -1.34 kNm
Muyt = -0.14 kNm
Vuxt = 0.95 kN
Vuyt = 41.5 kN
Pub = 46.74 kN
Muxb = -67.71 kNm
Muyb = 1.38 kNm
Vuxb = 0.95 kN
Vuyb = 41.5 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 115.47 mm
Kluy /r = 7.9
M1 = -1.34 kNm
M2 = -67.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.76
7.9 < 33.76, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.72
r = 57.74 mm
Klux /r = 14.96
M1 = -0.14 kNm
M2 = 1.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.26
14.96 < 35.26, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.42 (LOAD 3: DL1) +1.42
(LOAD 4: DL2) +0.5 (LOAD 5: LL1)
Critical Load Combination = kN
+(LOAD 6: LL2) +0.3 (LOAD 1: EX) -
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Nu = 46.74 kN
Muy = 67.71 kNm
Vuy = 41.4959 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 60.41 kNm
φVcy = 35.42 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C39
Level : 13.3m To 14.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 507
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 35.34 kN
Muxt = 7.96 kNm
Muyt = -0.46 kNm
Vuxt = 0.69 kN
Vuyt = -59.88 kN
Pub = 39.63 kN
Muxb = -87.82 kNm
Muyb = -1.56 kNm
Vuxb = 0.69 kN
Vuyb = -59.88 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = 7.96 kNm
M2 = -87.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.09
8 < 35.09, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = -0.46 kNm
M2 = -1.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.49
14.76 < 30.49, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 7.96 - 7.96
Major Axis Mux (bottom) -87.82 - -87.82
Minor Axis Muy (top) -0.46 - -0.46
Minor Axis Muy (bottom) -1.56 - -1.56
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 121
[21] : 0.68 (LOAD 3: DL1) +0.68
Critical Load Combination = (LOAD 4: DL2) -(LOAD 1: EX) +0.3 kN
(LOAD 2: EZ)
Nu = 13.99 kN
Muy = 70.76 kNm
Vuy = -47.3144 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 68.58 kNm
φVcy = 35.44 kN
Vuy > φVcy Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm
General Data
Column No. : C40
Level : 13.3m To 14.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 502
Critical Analysis Load Combination : 117
[17] : 1.12 (LOAD 3: DL1) +1.12 (LOAD 4: DL2) +0.3
Load Combination =
(LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 8.62 kN
Muxt = -3.33 kNm
Muyt = 1.82 kNm
Vuxt = 15.99 kN
Vuyt = 5.19 kN
Pub = 11.99 kN
Muxb = 4.96 kNm
Muyb = -23.75 kNm
Vuxb = 15.99 kN
Vuyb = 5.19 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Beam Sizes Beam Stiffness ψ
Stiffness Beam 1 Beam 2 Beam 1 Beam 2
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 61.101 No Beam No Beam - - 1
1500 x 200 x
Top 61.101 No Beam 65.174 - 0.939
400
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major
= 0.77
Axis
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -3.33 kNm
M2 = 4.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = 1.82 kNm
M2 = -23.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.92
14.76 < 34.92, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
4: DL2) +0.5 (LOAD 5: LL1) +(LOAD 6:
Critical Load Combination = kN
LL2) -(LOAD 1: EX) +0.3 (LOAD 2: EZ)
+0.5 (LOAD 7: LLR)
Nu = 16.14 kN
Muy = 25.36 kNm
Vuy = 21.0468 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 22.84 kNm
φVcy = 37 kN
Vuy < φVcy
Link For Shear Design Along D are not required
General Data
Column No. : C41
Level : 13.3m To 14.9m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (fy) = Fy410 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 200 mm
Column D = 400 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 1200 mm
Clear Floor Height @ luy = 1200 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 508
Critical Analysis Load Combination : 106
[6] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination = (LOAD 5: LL1) +(LOAD 6: LL2) -(LOAD 1: EX) +0.3
(LOAD 2: EZ) +0.5 (LOAD 7: LLR)
Critical Location = Bottom Joint
Put = 35.34 kN
Muxt = -7.96 kNm
Muyt = -0.21 kNm
Vuxt = -3 kN
Vuyt = -26.77 kN
Pub = 39.63 kN
Muxb = -50.78 kNm
Muyb = 4.59 kNm
Vuxb = -3 kN
Vuyb = -26.77 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 8
M1 = -7.96 kNm
M2 = -50.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.12
8 < 32.12, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 57.74 mm
Klux /r = 14.76
M1 = -0.21 kNm
M2 = 4.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.55
14.76 < 34.55, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 114
[14] : 1.12 (LOAD 3: DL1) +1.12 (LOAD
Critical Load Combination = 4: DL2) -(LOAD 1: EX) +0.3 (LOAD 2: kN
EZ)
Nu = 23.05 kN
Muy = 42.36 kNm
Vuy = -22.5404 kN
λ = 1
φ = 0.6
deff = 350 mm
ρw (50% of As provided) = 0.027
Mm = 38.76 kNm
φVcy = 34.71 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 12 mm
> Max. longitudinal bar dia / 4
=5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 576 mm
Provided spacing = 100 mm