Professional Documents
Culture Documents
1 - 7UT6 Diff - Principles
1 - 7UT6 Diff - Principles
I1
I2
I4
I3
I1 + I2 + I3 + I4 = 0 Æ ∑ I =
0
Definition:
Currents, which flow into the knot (protected object), are counted positive.
Currents which flow out of the knot (protected object)
Currents, object), are counted negative
negative.
Protection objects:
Line, Transformer, Generator/Motor, Bus bar
Ct 1: Ct 2:
IP1 ε1= - 5% ε2 = +5% IP2 = -IP1
Protected IF
object
IS1= IS2=
00.95
95·IIP1 IDiff = 0.1·IP1
1.05·I
0 IP2
∆I
IS2=
IS1= 1.05·IP2
0.95·IP1
IDiff= │IS1+ IS2│
IDiff
IDiff = 0.1·IP1
L1
L2
L3
Diff.
Diff
Rest. current
Conventional
Differential Protection
Different current values of the CT- sets on the high voltage side (HV)
and on the low voltage side (LV)
Transient currents
Inrush
CT-saturation
I2*L3
I1L1ku/√3
I1L1
5·30°
I2*L2
I1L2ku /√3
I1L3 I1L2
-I1L1ku /√3
I2*L1
Principles Transf. Diff 8
3-phase Transformer : secondary values
SN I
I L1sec = ⋅ NCT1sec
3 ⋅ U N I NCTlprim
100MVA 1A
I1L1sec = ⋅ = 0.7A
3 ⋅110kV 750A I1L1sec= 0.7A , 0°
100MVA 1A
I2L1sec = ⋅ = 0.96A
3 ⋅ 20kV
k 3000A
L3
0.96A 0.7A
29 Wdg. 23
Diff.
IR Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq.
q current handling
g
nominal Load (no fault): 0.70A ·23Wdg = 0.555A ·29Wdg, IR = 0.555·√3 = 0.96A
~ L2
~ L3
3I0
IL1(S2) = -IL1(S1) , IL3(S2) = IL1(S1)
I L1(S2) IL3(S2) IL1(S1)
1 2 3
+
Differential Protection
zero sequence I0
I0 elimination nessesary
Principles Transf. Diff 11
Vector group and current value adaptation in case of (2/2)
conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A
~ L1
13655A
~ L2
~ L3
3I0
IP=
4.55A 5.73A 4300A
29 Wdg. 23
Diff.
IR Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
I Diff
InO
3.0
2.5
Trip
p
slope 2
Total error
2.0
45° Block
1.5
CT error
CT-
1.0
slope 1 Tap changer error
0.5
IDiff>
Transf. magnetising current
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 I Rest InO
i1 I2 = 0
-T2
t=0
Inrush -T2 t = 0 t
1P 2P 3P t
I2har
IDiff block Cross-block = Yes ((blocking
g of all p
phases))
L1-block
Setting
15 %
value L2-block OR IDiff > trip blocking
≥1 for an adjustable time
L3-block
no block
0
0 t
recognise inrush condition by evaluating the ratio 2nd harmonic I2har to basic wave IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
T i off a short
Trip h t circuit
i it after
ft the
th sett time
ti d l
delay.
recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to basic wave
Principles Transf. Diff 17
Demonstration of Inrush with evolving fault
Internal
fault
IDiff>>
Inrush
IDiff>
3 cycles
Cross Blocking
i1 i2
i1 i2
i1 I2 ≈ 0
6
Trip
45° Block
5
D
C
4
3
Add-on
Stabilisation
2
B Begin of saturation
IDiff>
0 14 I Rest
0 2 4 6 8 10 12 16
A
InO
Block
45°
Trip
Add-Stabilisation
≥1
I / InO
iDiff IDiff>>
k·IDiff>>
ms ms
SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A
IP2 = 2750A IP1 = 500A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1
O1 = 525A
measured
IS2 = -0.916A
0 916A 7UT6 IS1 = 0.66A
0 66A secondary currents
7UM62
IDiff = ?
IRest = ?
SN
1. Calculation of the transformer nominal current I nO =
3 ⋅ UN
I NCT
2 Correction factor
2. kW =
I nO
4. Calculation of the differential and IDiff = |I1* + I2*| IRest = |I1*| + |I2*|
restraint current
Calculation example: