SADARAH 380/230kV BSP IN JIC-2


SCADA POINT LIST
(SIEMENS SAS)
PVK
BY

01-03-2012
DATE
NO.

REVISIONS
DESIGNED

BY:- PVK
DATE:- 20-02-12

CHECKED

BY:- IAL
DATE:- 24-02-12

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE


THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OR
SCADA POINT LIST
FOR ORDERING
SADARAH 380/230kV BSP IN JIC-2
A NA524 EA-191055 A
MATERIALS UNTIL
CERTIFIED AND
DATED SAUDI ARABIA JOB ORDER NO. 3-1133008-01 DWG. CONT. SHT. EE-190812

1 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address

BUS 1A & 1B SIDE

1 SDRA BS1 D801 DISC D801 COMMAND EXECUTE CLOSE / OPEN D801ISOLATOR OFF ON
2 SDRA BS1 K801 ESWS K801 COMMAND EXECUTE CLOSE / OPEN K816 EARTHSWITCH OFF ON
3 SDRA BS1 K802 ESWS K802 COMMAND EXECUTE CLOSE / OPEN K817 EARTHSWITCH OFF ON
4 SDRA BS1 PROTECTION IN/OUT IN/OUT OFF ON

BUS 2A & 2B SIDE


4 SDRA BS2 D802 DISC D802 COMMAND EXECUTE CLOSE / OPEN D802 ISOLATOR OFF ON
5 SDRA BS2 K803 ESWS K803 COMMAND EXECUTE CLOSE / OPEN K803 EARTHSWITCH OFF ON
6 SDRA BS2 K804 ESWS K804 COMMAND EXECUTE CLOSE / OPEN K804 EARTHSWITCH OFF ON
7 SDRA BS2 PROTECTION IN/OUT IN/OUT OFF ON

BAY C2.A COMMANDS


8 SDRA A804_C2.A A804 CB A804 COMMAND EXECUTE CLOSE / OPEN A804 BREAKER OFF ON
9 SDRA A804_C2.A D811 DISC D811 COMMAND EXECUTE CLOSE / OPEN D811 ISOLATOR OFF ON
10 SDRA A804_C2.A D812 DISC D812 COMMAND EXECUTE CLOSE / OPEN D812 ISOLATOR OFF ON
11 SDRA A804_C2.A D817 DISC D817 COMMAND EXECUTE CLOSE / OPEN D817 ISOLATOR OFF ON
12 SDRA A804_C2.A K815 ESWS D815 COMMAND EXECUTE CLOSE / OPEN D815 EARTHSWITCH OFF ON
13 SDRA A804_C2.A K816 ESWS D816 COMMAND EXECUTE CLOSE / OPEN D816 EARTHSWITCH OFF ON
14 SDRA A805_C2.B K819 ESWS K819 COMMAND EXECUTE CLOSE / OPEN K819 EARTHSWITCH OFF ON
15 SDRA A805_C2.B PROTECTION IN/OUT IN/OUT OFF ON

BAY C2.B COMMANDS


16 SDRA A805_C2.B A805 CB A805 COMMAND EXECUTE CLOSE / OPEN A805 BREAKER OFF ON
17 SDRA A805_C2.B D813 DISC D813 COMMAND EXECUTE CLOSE / OPEN D813 ISOLATOR OFF ON
18 SDRA A805_C2.B D814 DISC D814 COMMAND EXECUTE CLOSE / OPEN D814 ISOLATOR OFF ON
19 SDRA A805_C2.B K818 ESWS K818 COMMAND EXECUTE CLOSE / OPEN K818 EARTHSWITCH OFF ON
20 SDRA A805_C2.B K819 ESWS K819 COMMAND EXECUTE CLOSE / OPEN K819 EARTHSWITCH OFF ON
21 SDRA A805_C2.B PROTECTION IN/OUT IN/OUT OFF ON

BAY C2.C COMMANDS


22 SDRA A806_C2.C A806 CB A607 COMMAND EXECUTE CLOSE / OPEN A607 BREAKER OFF ON
23 SDRA A806_C2.C D815 DISC D815 COMMAND EXECUTE CLOSE / OPEN D815 ISOLATOR OFF ON
24 SDRA A806_C2.C D816 DISC D816 COMMAND EXECUTE CLOSE / OPEN D816 ISOLATOR OFF ON
25 SDRA A806_C2.C D818 DISC D818 COMMAND EXECUTE CLOSE / OPEN D818 ISOLATOR OFF ON
26 SDRA A806_C2.C K821 ESWS K821 COMMAND EXECUTE CLOSE / OPEN K821 EARTHSWITCH OFF ON
27 SDRA A806_C2.C K822 ESWS K822 COMMAND EXECUTE CLOSE / OPEN K822 EARTHSWITCH OFF ON
28 SDRA A806_C2.C K820 ESWS K820 COMMAND EXECUTE CLOSE / OPEN K820 EARTHSWITCH OFF ON
29 SDRA A806_C2.C PROTECTION IN/OUT IN/OUT OFF ON

2 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
BAY C3.A COMMANDS
30 SDRA A807_C3.A A807 CB A807 COMMAND EXECUTE CLOSE / OPEN A807 BREAKER OFF ON
31 SDRA A807_C3.A D819 DISC D819 COMMAND EXECUTE CLOSE / OPEN D819 ISOLATOR OFF ON
32 SDRA A807_C3.A D820 DISC D820 COMMAND EXECUTE CLOSE / OPEN D820 ISOLATOR OFF ON
33 SDRA A807_C3.A D825 DISC D825 COMMAND EXECUTE CLOSE / OPEN D825 ISOLATOR OFF ON
34 SDRA A807_C3.A K825 ESWS K825 COMMAND EXECUTE CLOSE / OPEN K825 EARTHSWITCH OFF ON
35 SDRA A807_C3.A K826 ESWS K826 COMMAND EXECUTE CLOSE / OPEN K826 EARTHSWITCH OFF ON
36 SDRA A807_C3.A K820 ESWS K820 COMMAND EXECUTE CLOSE / OPEN K820 EARTHSWITCH OFF ON
37 SDRA A807_C3.A PROTECTION IN/OUT IN/OUT OFF ON

BAY C3.B COMMANDS


38 QRYT A808_C3.B A808 CB A808 COMMAND EXECUTE CLOSE / OPEN A808 BREAKER OFF ON
39 QRYT A808_C3.B D821 DISC D821 COMMAND EXECUTE CLOSE / OPEN D821 ISOLATOR OFF ON
40 QRYT A808_C3.B D822 DISC D822 COMMAND EXECUTE CLOSE / OPEN D822 ISOLATOR OFF ON
41 QRYT A808_C3.B K828 ESWS K828 COMMAND EXECUTE CLOSE / OPEN K828 EARTHSWITCH OFF ON
SDRA A810_C4.A K837 ESWS K837 COMMAND EXECUTE CLOSE / OPEN K837 EARTHSWITCH
SDRA A810_C4.A PROTECTION IN/OUT IN/OUT

BAY C3.C COMMANDS


42 SDRA A809_C3.C A809 CB A809 COMMAND EXECUTE CLOSE / OPEN A809 BREAKER OFF ON
43 SDRA A809_C3.C D823 DISC D823 COMMAND EXECUTE CLOSE / OPEN D823 ISOLATOR OFF ON
44 SDRA A809_C3.C D824 DISC D824 COMMAND EXECUTE CLOSE / OPEN D824 ISOLATOR OFF ON
45 SDRA A809_C3.C D826 DISC D826 COMMAND EXECUTE CLOSE / OPEN D826 ISOLATOR OFF ON
46 SDRA A809_C3.C K831 ESWS K831 COMMAND EXECUTE CLOSE / OPEN K831 EARTHSWITCH OFF ON
47 SDRA A809_C3.C K832 ESWS K832 COMMAND EXECUTE CLOSE / OPEN K832 EARTHSWITCH OFF ON
48 SDRA A810_C4.A K837 ESWS K837 COMMAND EXECUTE CLOSE / OPEN K837 EARTHSWITCH
49 SDRA A810_C4.A PROTECTION IN/OUT IN/OUT

BAY C4.A COMMANDS


50 SDRA A810_C4.A A810 CB A810 COMMAND EXECUTE CLOSE / OPEN A810 BREAKER OFF ON
51 SDRA A810_C4.A D827 DISC D827 COMMAND EXECUTE CLOSE / OPEN D827 ISOLATOR OFF ON
52 SDRA A810_C4.A D828 DISC D828 COMMAND EXECUTE CLOSE / OPEN D828 ISOLATOR OFF ON
53 SDRA A810_C4.A D833 DISC D833 COMMAND EXECUTE CLOSE / OPEN D833 ISOLATOR OFF ON
54 SDRA A810_C4.A K835 ESWS K835 COMMAND EXECUTE CLOSE / OPEN K835 EARTHSWITCH OFF ON
56 SDRA A810_C4.A K836 ESWS K836 COMMAND EXECUTE CLOSE / OPEN K836 EARTHSWITCH
57 SDRA A810_C4.A K837 ESWS K837 COMMAND EXECUTE CLOSE / OPEN K837 EARTHSWITCH
58 SDRA A810_C4.A PROTECTION IN/OUT IN/OUT

BAY C4.B COMMANDS


59 SDRA A811_C4.B A811 CB A811 COMMAND EXECUTE CLOSE / OPEN A811 BREAKER OFF ON
60 SDRA A811_C4.B D829 DISC D829 COMMAND EXECUTE CLOSE / OPEN D829 ISOLATOR OFF ON
61 SDRA A811_C4.B D830 DISC D830 COMMAND EXECUTE CLOSE / OPEN D830 ISOLATOR OFF ON
62 SDRA A811_C4.B K838 ESWS K838 COMMAND EXECUTE CLOSE / OPEN K838 EARTHSWITCH OFF ON
63 SDRA A811_C4.B K839 ESWS K839 COMMAND EXECUTE CLOSE / OPEN K839 EARTHSWITCH OFF ON
64 SDRA A811_C4.B PROTECTION IN/OUT IN/OUT OFF ON

3 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
BAY C4.C COMMANDS
65 SDRA A812_C4.C A812 CB A812 COMMAND EXECUTE CLOSE / OPEN A812 BREAKER OFF ON
66 SDRA A812_C4.C D831 DISC D831 COMMAND EXECUTE CLOSE / OPEN D831 ISOLATOR OFF ON
67 SDRA A812_C4.C D832 DISC D832 COMMAND EXECUTE CLOSE / OPEN D828 ISOLATOR OFF ON
68 SDRA A812_C4.C D834 DISC D834 COMMAND EXECUTE CLOSE / OPEN D834 ISOLATOR OFF ON
69 SDRA A812_C4.C K841 ESWS K841 COMMAND EXECUTE CLOSE / OPEN K841 EARTHSWITCH OFF ON
70 SDRA A812_C4.C K842 ESWS K842 COMMAND EXECUTE CLOSE / OPEN K842 EARTHSWITCH OFF ON
71 SDRA A812_C4.C K840 ESWS K840 COMMAND EXECUTE CLOSE / OPEN K840 EARTHSWITCH OFF ON
72 SDRA A812_C4.C PROTECTION IN/OUT IN/OUT OFF ON

BAY C5.A COMMANDS


73 SDRA A813_C5.A A813 CB A813 COMMAND EXECUTE CLOSE / OPEN A813 BREAKER OFF ON
74 SDRA A813_C5.A D845 DISC D845 COMMAND EXECUTE CLOSE / OPEN D845 ISOLATOR OFF ON
75 SDRA A813_C5.A D846 DISC D846 COMMAND EXECUTE CLOSE / OPEN D846 ISOLATOR OFF ON
76 SDRA A813_C5.A D841 DISC D841 COMMAND EXECUTE CLOSE / OPEN D841 ISOLATOR OFF ON
77 SDRA A813_C5.A K845 ESWS K845 COMMAND EXECUTE CLOSE / OPEN K845 EARTHSWITCH OFF ON
78 SDRA A813_C5.A K846 ESWS K846 COMMAND EXECUTE CLOSE / OPEN K846 EARTHSWITCH OFF ON
79 SDRA A813_C5.A K847 ESWS K847 COMMAND EXECUTE CLOSE / OPEN K847 EARTHSWITCH OFF ON
80 SDRA A813_C5.A PROTECTION IN/OUT IN/OUT OFF ON

BAY C5.B COMMANDS


81 SDRA A814_C5.B A814 CB A814 COMMAND EXECUTE CLOSE / OPEN A814 BREAKER OFF ON
82 SDRA A814_C5.B D837 DISC D837 COMMAND EXECUTE CLOSE / OPEN D837 ISOLATOR OFF ON
83 SDRA A814_C5.B D838 DISC D838 COMMAND EXECUTE CLOSE / OPEN D838 ISOLATOR OFF ON
84 SDRA A814_C5.B K848 ESWS K848 COMMAND EXECUTE CLOSE / OPEN K848 EARTHSWITCH OFF ON
85 SDRA A814_C5.B K849 ESWS K849 COMMAND EXECUTE CLOSE / OPEN K849 EARTHSWITCH OFF ON
86 SDRA A814_C5.B PROTECTION IN/OUT IN/OUT OFF ON

BAY C5.C COMMANDS


87 SDRA A815_C5.C A815 CB A815 COMMAND EXECUTE CLOSE / OPEN A815 BREAKER OFF ON
88 SDRA A815_C5.C D839 DISC D839 COMMAND EXECUTE CLOSE / OPEN D839 ISOLATOR OFF ON
89 SDRA A815_C5.C D840 DISC D840 COMMAND EXECUTE CLOSE / OPEN D840 ISOLATOR OFF ON
90 SDRA A815_C5.C D842 DISC D842 COMMAND EXECUTE CLOSE / OPEN D842 ISOLATOR OFF ON
91 SDRA A815_C5.C K851 ESWS K851 COMMAND EXECUTE CLOSE / OPEN K851 EARTHSWITCH OFF ON
92 SDRA A815_C5.C K852 ESWS K852 COMMAND EXECUTE CLOSE / OPEN K852 EARTHSWITCH OFF ON
93 SDRA A815_C5.C K850 ESWS K850 COMMAND EXECUTE CLOSE / OPEN K850 EARTHSWITCH OFF ON
94 SDRA A815_C5.C PROTECTION IN/OUT IN/OUT OFF ON

AUTOMATIC VOLTAGE CONTROL (T801)


95 SDRA A804_C2.A TAPCON 260 T801 AVR TAP RAISE/LOWER T801 AVR RAISE LOWER
96 SDRA A804_C2.A TAPCON 260 T801 AVR AUTO/MANUAL T801 AVR AUTO MANUAL
97 SDRA A804_C2.A TAPCON 260 T801 AVR MASTER/FOLLOWER T801 AVR MASTER FOLLOWER
98 SDRA A804_C2.A TAPCON 260 T801 AVRSINGLE/PARALLEL T801 AVR SINGLE PARALLEL

4 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
AUTOMATIC VOLTAGE CONTROL (T802)
99 SDRA A812_C4.C TAPCON 260 T802 AVR TAP RAISE/LOWER T802 AVR RAISE LOWER
100 SDRA A812_C4.C TAPCON 260 T802 AVR AUTO/MANUAL T802 AVR AUTO MANUAL
101 SDRA A812_C4.C TAPCON 260 T802 AVR MASTER/FOLLOWER T802 AVR MASTER FOLLOWER
102 SDRA A812_C4.C TAPCON 260 T802 AVRSINGLE/PARALLEL T802 AVR SINGLE PARALLEL

FUTURE AUTOMATIC VOLTAGE CONTROL (T803)


103 SDRA A815_C5.C T803 AVR TAP RAISE/LOWER T803 AVR RAISE LOWER
104 SDRA A815_C5.C T803 AVR AUTO/MANUAL T803 AVR AUTO MANUAL
105 SDRA A815_C5.C T803 AVR MASTER/FOLLOWER T803 AVR MASTER FOLLOWER
106 SDRA A815_C5.C T803 AVRSINGLE/PARALLEL T803 AVR SINGLE PARALLEL

34.5 KV O/G FDR CB COMMANDS


107 SDRA A401_INC A401 CB A401 COMMAND EXECUTE CLOSE / OPEN A401 BREAKER OFF ON
108 SDRA A401_INC K401 ESWS K401 COMMAND EXECUTE CLOSE / OPEN K401 EARTHSWITCH OFF ON
109 SDRA A401_INC K402 ESWS K402 COMMAND EXECUTE CLOSE / OPEN K402 EARTHSWITCH OFF ON

13.8 KV O/G FDR CB COMMANDS


110 SDRA A301_INC A301 CB A301 COMMAND EXECUTE CLOSE / OPEN A301 BREAKER OFF ON
111 SDRA A301_INC K301 ESWS K301 COMMAND EXECUTE CLOSE / OPEN K301 EARTHSWITCH OFF ON
112 SDRA A301_INC K302 ESWS K302 COMMAND EXECUTE CLOSE / OPEN K302 EARTHSWITCH OFF ON

13.8 KV O/G FDR CB COMMANDS


113 SDRA A302_INC A302 CB A302 COMMAND EXECUTE CLOSE / OPEN A302 BREAKER OFF ON
114 SDRA A302_INC K302 ESWS K303 COMMAND EXECUTE CLOSE / OPEN K303 EARTHSWITCH OFF ON
115 SDRA A302_INC K302 ESWS K304 COMMAND EXECUTE CLOSE / OPEN K304 EARTHSWITCH OFF ON

5 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
BAY C2 - SIGNALS
1 POSTION INDICATIONS
SDRA C2.A_T801 A804 CB A804 POSITION INDICATION A804 BREAKER OPEN CLOSE
SDRA C2.B A805 CB A805 POSITION INDICATION A805 BREAKER OPEN CLOSE
SDRA C2.C_JUBL LINE-1 A806 CB A806 POSITION INDICATION A806 BREAKER OPEN CLOSE
SDRA C2 D811 DISC D811 POSITION INDICATION D811 ISOLATOR OPEN CLOSE
SDRA C2 D812 DISC D812 POSITION INDICATION D812 ISOLATOR OPEN CLOSE
SDRA C2 D817 DISC D817 POSITION INDICATION D817 ISOLATOR OPEN CLOSE
SDRA C2 D813 DISC D813 POSITION INDICATION D813 ISOLATOR OPEN CLOSE
SDRA C2 D814 DISC D814 POSITION INDICATION D814 ISOLATOR OPEN CLOSE
SDRA C2 D815 DISC D815 POSITION INDICATION D815 ISOLATOR OPEN CLOSE
SDRA C2 D816 DISC D816 POSITION INDICATION D816 ISOLATOR OPEN CLOSE
SDRA C2 D818 DISC D818 POSITION INDICATION D818 ISOLATOR OPEN CLOSE
SDRA C2 K815 ESW K815 POSITION INDICATION K815 ISOLATOR OPEN CLOSE
SDRA C2 K816 ESW K816 POSITION INDICATION K816 ISOLATOR OPEN CLOSE
SDRA C2 K817 ESW K817 POSITION INDICATION K817 ISOLATOR OPEN CLOSE
SDRA C2 K823 ESW K823 POSITION INDICATION K823 ISOLATOR OPEN CLOSE
SDRA C2 K818 ESW K818 POSITION INDICATION K818 ISOLATOR OPEN CLOSE
SDRA C2 K819 ESW K819 POSITION INDICATION K819 ISOLATOR OPEN CLOSE
SDRA C2 K820 ESW K820 POSITION INDICATION K820 ISOLATOR OPEN CLOSE
SDRA C2 K824 ESW K824 POSITION INDICATION K824 ISOLATOR OPEN CLOSE
SDRA C2 K821 ESW K821 POSITION INDICATION K821 ISOLATOR OPEN CLOSE
SDRA C2 K822 ESW K822 POSITION INDICATION K822 ISOLATOR OPEN CLOSE
SDRA C2 K823 ESW K823 POSITION INDICATION K823 ISOLATOR OPEN CLOSE
C2 VT805 T801 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
C2 VT806 JUBL LINE1 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE

BAY C3 - SIGNALS
2 POSTION INDICATIONS
SDRA C3.A A807 CB A807 POSITION INDICATION A807 BREAKER OPEN CLOSE
SDRA C3.B A808 CB A808 POSITION INDICATION A808 BREAKER OPEN CLOSE
SDRA C3.C A809 CB A809 POSITION INDICATION A809 BREAKER OPEN CLOSE
SDRA C3 D819 DISC D819 POSITION INDICATION D819 ISOLATOR OPEN CLOSE
SDRA C3 D820 DISC D820 POSITION INDICATION D820 ISOLATOR OPEN CLOSE
SDRA C3 D825 DISC D825 POSITION INDICATION D825 ISOLATOR OPEN CLOSE
SDRA C3 D821 DISC D821 POSITION INDICATION D821 ISOLATOR OPEN CLOSE
SDRA C3 D822 DISC D822 POSITION INDICATION D822 ISOLATOR OPEN CLOSE
SDRA C3 D823 DISC D823 POSITION INDICATION D823 ISOLATOR OPEN CLOSE
SDRA C3 D824 DISC D824 POSITION INDICATION D824 ISOLATOR OPEN CLOSE
SDRA C3 D826 DISC D826 POSITION INDICATION D826 ISOLATOR OPEN CLOSE
SDRA C3 K825 ESW K825 POSITION INDICATION K825 ISOLATOR OPEN CLOSE
SDRA C3 K826 ESW K826 POSITION INDICATION K826 ISOLATOR OPEN CLOSE
SDRA C3 K827 ESW K827 POSITION INDICATION K827 ISOLATOR OPEN CLOSE
SDRA C3 K833 ESW K833 POSITION INDICATION K833 ISOLATOR OPEN CLOSE
SDRA C3 K828 ESW K828 POSITION INDICATION K828 ISOLATOR OPEN CLOSE
SDRA C3 K829 ESW K829 POSITION INDICATION K829 ISOLATOR OPEN CLOSE
SDRA C3 K831 ESW K831 POSITION INDICATION K831 ISOLATOR OPEN CLOSE
SDRA C3 K832 ESW K832 POSITION INDICATION K832 ISOLATOR OPEN CLOSE
SDRA C3 K830 ESW K830 POSITION INDICATION K830 ISOLATOR OPEN CLOSE
SDRA C3 K834 ESW K834 POSITION INDICATION K834 ISOLATOR OPEN CLOSE
SDRA C3 VT807 JUBL LINE 2 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
SDRA C3 VT808 JUBL COMMUNITY2 LINE2 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE

BAY C4 - SIGNALS
3 POSTION INDICATIONS
SDRA C4.A A810 CB A810 POSITION INDICATION A810 BREAKER OPEN CLOSE
SDRA C4.B A811 CB A811 POSITION INDICATION A811 BREAKER OPEN CLOSE
SDRA C4.C A812 CB A812 POSITION INDICATION A812 BREAKER OPEN CLOSE
SDRA C4 D827 DISC D827 POSITION INDICATION D827 ISOLATOR OPEN CLOSE
SDRA C4 D828 DISC D828 POSITION INDICATION D828 ISOLATOR OPEN CLOSE
SDRA C4 D833 DISC D833 POSITION INDICATION D833 ISOLATOR OPEN CLOSE
SDRA C4 D829 DISC D829 POSITION INDICATION D829 ISOLATOR OPEN CLOSE
SDRA C4 D830 DISC D830 POSITION INDICATION D830 ISOLATOR OPEN CLOSE
SDRA C4 D831 DISC D831 POSITION INDICATION D831 ISOLATOR OPEN CLOSE
SDRA C4 D832 DISC D832 POSITION INDICATION D832 ISOLATOR OPEN CLOSE

6 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4 D834 DISC D834 POSITION INDICATION D834 ISOLATOR OPEN CLOSE

7 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4 K835 ESW K835 POSITION INDICATION K835 ISOLATOR OPEN CLOSE
SDRA C4 K836 ESW K836 POSITION INDICATION K836 ISOLATOR OPEN CLOSE
SDRA C4 K837 ESW K837 POSITION INDICATION K837 ISOLATOR OPEN CLOSE
SDRA C4 K843 ESW K843 POSITION INDICATION K843 ISOLATOR OPEN CLOSE
SDRA C4 K838 ESW K838 POSITION INDICATION K838 ISOLATOR OPEN CLOSE
SDRA C4 K839 ESW K839 POSITION INDICATION K839 ISOLATOR OPEN CLOSE
SDRA C4 K841 ESW K841 POSITION INDICATION K841 ISOLATOR OPEN CLOSE
SDRA C4 K842 ESW K842 POSITION INDICATION K842 ISOLATOR OPEN CLOSE
SDRA C4 K840 ESW K840 POSITION INDICATION K840 ISOLATOR OPEN CLOSE
SDRA C4 K837 ESW K844 POSITION INDICATION K844 ISOLATOR OPEN CLOSE
SDRA C4 VT809 JUBL COMMUNITY2 LINE 1 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
SDRA C4 VT810 T802 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE

BAY C5 (FUTURE) - SIGNALS


4 POSTION INDICATIONS
SDRA C5.A A813 CB A813 POSITION INDICATION A813 BREAKER OPEN CLOSE
SDRA C5.B A814 CB A814 POSITION INDICATION A814 BREAKER OPEN CLOSE
SDRA C5.C A815 CB A815 POSITION INDICATION A815 BREAKER OPEN CLOSE
SDRA C5 D835 DISC D835 POSITION INDICATION D835 ISOLATOR OPEN CLOSE
SDRA C5 D836 DISC D836 POSITION INDICATION D836 ISOLATOR OPEN CLOSE
SDRA C5 D841 DISC D841 POSITION INDICATION D841 ISOLATOR OPEN CLOSE
SDRA C5 D837 DISC D837 POSITION INDICATION D837 ISOLATOR OPEN CLOSE
SDRA C5 D838 DISC D838 POSITION INDICATION D838 ISOLATOR OPEN CLOSE
SDRA C5 D839 DISC D839 POSITION INDICATION D839 ISOLATOR OPEN CLOSE
SDRA C5 D840 DISC D840 POSITION INDICATION D840 ISOLATOR OPEN CLOSE
SDRA C5 D842 DISC D842 POSITION INDICATION D842 ISOLATOR OPEN CLOSE
SDRA C5 K845 ESW K845 POSITION INDICATION K845 ISOLATOR OPEN CLOSE
SDRA C5 K846 ESW K846 POSITION INDICATION K846 ISOLATOR OPEN CLOSE
SDRA C5 K847 ESW K847 POSITION INDICATION K847 ISOLATOR OPEN CLOSE
SDRA C5 K853 ESW K853 POSITION INDICATION K853 ISOLATOR OPEN CLOSE
SDRA C5 K848 ESW K848 POSITION INDICATION K848 ISOLATOR OPEN CLOSE
SDRA C5 K849 ESW K849 POSITION INDICATION K849 ISOLATOR OPEN CLOSE
SDRA C5 K851 ESW K851 POSITION INDICATION K851 ISOLATOR OPEN CLOSE
SDRA C5 K852 ESW K852 POSITION INDICATION K852 ISOLATOR OPEN CLOSE
SDRA C5 K850 ESW K850 POSITION INDICATION K850 ISOLATOR OPEN CLOSE
SDRA C5 K854 ESW K854 POSITION INDICATION K854 ISOLATOR OPEN CLOSE
SDRA C5 VT811 JUBL COMMUNITY2 LINE 1 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
SDRA C5 VT812 T802 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE

BUS
5 POSTION INDICATIONS
SDRA BUS A D801 CB D801 POSITION INDICATION D801 BREAKER OPEN CLOSE
SDRA BUS B D802 CB D802 POSITION INDICATION D802 BREAKER OPEN CLOSE
SDRA BUS-1A K801 ESW K801 POSITION INDICATION K801 BREAKER OPEN CLOSE
SDRA BUS-1B K802 ESW K802 POSITION INDICATION K802 ISOLATOR OPEN CLOSE
SDRA BUS-2A K803 ESW K803 POSITION INDICATION K803 ISOLATOR OPEN CLOSE
SDRA BUS-2B K804 ESW K804 POSITION INDICATION K804 ISOLATOR OPEN CLOSE

CIRCUIT BREAKER BAY 380kV


6 CB NORMAL/ABNORMAL (A804) A804 BREAKER ABNORMAL NORMAL
SDRA C2.A_T801 A804 CB A804 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C2.A_T801 A804 CB A804 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C2.A_T801 A804 CB A804 CLOSING SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 OPERATING MECHANISM SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 CONTROL SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C2.A_T801 A804 CB A804 MOTOR SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 PUMP SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 BREAKER FAIL RELAY FAIL
SDRA C2.A_T801 A804 CB A804 MOTOR THERMAL FAULT
SDRA C2.A_T801 A804 A804 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C2.A_T801 A804 A804 BAY DS/ES CONTROL SUPPLY FAIL

7 TRIP CIRCUIT FAULTY A804 TRIP CIRCUIT FAULTY NORMAL

8 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C2.A_T801 A804 CB A804 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C2.A_T801 A804 CB A804 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

8 CIRCUIT BREAKER GAS PRESSURE LOW A804 GAS PRESSURE LOW ALARM NORMAL
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 2

9 GIS GAS DENSITY ALARM A804 GAS DESITY ALARM ALARM NORMAL
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C2.A_T801 A804 GIS GAS PRESSURE HIGH

10 BAY CONTROL SUPPLY FAIL A804 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C2.A_T801 A804 CB A804 OPERATING MECH. SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 CONTROL SUPPLY DC FAIL
SDRA C2.A_T801 A804 CB A804 MOTOR SUPPLY AC FAIL
SDRA C2.A_T801 A804 DS/ES CONTROL SUPPLY FAIL
SDRA C2.A_T801 A804 DS/ES MOTOR SUPPLY FAIL
SDRA C2.A_T801 A804 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C2.A_T801 A804 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

11 CIRCUIT BREAKER LOCKOUT A804 CB LOCKOUT OPERATE NORMAL


SDRA C2.A_T801 A804 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C2.A_T801 A804 SF6 GAS LOW STAGE-2
SDRA C2.A_T801 A804 POLE DISCREPANCY OPERATED STAGE-1
SDRA C2.A_T801 A804 POLE DISCREPANCY OPERATED STAGE-2

12 CIRCUIT BREAKER POLE DISCREPANCY A804 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C2.A_T801 A804 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C2.A_T801 A804 POLE DISCREPANCY RELAY OPERATED STAGE-2

13 SYNCHROCHECK RELAY FAULT A804 SYNC CHK FAULTY NORMAL


SDRA C2.A_T801 A804 DC FAIL OPERATED
SDRA C2.A_T801 A804 SELF SUPERVISION OPERATED
SDRA C2.A_T801 A804 SYNCROCHECK FUSE FAILURE OPERATED

14 ALARM SUPPLY FAIL A804 ALARM SUPPLY FAILED NORMAL


SDRA C2.A_T801 A804 ALARM INDICATION SUPPLY FAIL
SDRA C2.A_T801 A804 ANNUNCIATION DC SUPPLY FAIL
SDRA C2.A_T801 A804 ANNUNCIATION AC BACKUP SUPPLY FAIL

15 CBF PROTECTION OPERATED A804 CBF PROTECTION FAULTY FAULTY NORMAL


SDRA C2.A_T801 A804 50BF CBF FAULTY
SDRA C2.A_T801 A804 BAY UNIT COMM. ERROR
SDRA C2.A_T801 A804 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C2.A_T801 A804 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C2.A_T801 A804 CBF 94BF-2 TRIP RELAY FAULTY

89 GIS GAS DENSITY ALARM A809 GAS DESITY ALARM ALARM NORMAL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 GIS GAS PRESSURE HIGH

90 BAY CONTROL SUPPLY FAIL A809 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 OPERATING MECH. SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 CONTROL SUPPLY DC FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 MOTOR SUPPLY AC FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 DS/ES CONTROL SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 DS/ES MOTOR SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

91 CIRCUIT BREAKER LOCKOUT A809 CB LOCKOUT OPERATE NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 SF6 GAS LOW STAGE-2

9 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY OPERATED STAGE-1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY OPERATED STAGE-2

92 CIRCUIT BREAKER POLE DISCREPANCY A809 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY RELAY OPERATED STAGE-2

93 SYNCHROCHECK RELAY FAULT A809 SYNC CHK FAULTY NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 DC FAIL OPERATED
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 SELF SUPERVISION OPERATED
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 SYNCROCHECK FUSE FAILURE OPERATED

94 ALARM SUPPLY FAIL A809 ALARM SUPPLY FAILED NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 ALARM INDICATION SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 ANNUNCIATION DC SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 ANNUNCIATION AC BACKUP SUPPLY FAIL

95 CBF PROTECTION OPERATED A809 CBF PROTECTION FAULTY FAULTY NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 50BF CBF FAULTY
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 BAY UNIT COMM. ERROR
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CBF 86BF-2 TRIP RELAY FAULTY

96 CONTROL SELECTOR SWITCH POS. A809 CONTROL SEL. OFF LOCAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 A809 BAY CONTROL SELECTOR SWITCH LOCAL
97 CONTROL SELECTOR SWITCH POS. A809 CONTROL SEL. OFF REMOTE
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 A809 BAY CONTROL SELECTOR SWITCH REMOTE
98 CONTROL SELECTOR SWITCH POS. A809 CONTROL SEL. OFF BCU
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 A809 BAY CONTROL SELECTOR SWITCH BCU

99 GIS SF6 STAGE-2 ALARM A809 GIS SF6 2 ALARM NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 A809 GIS SF6 GAS Pressure Low Stage-2

100 CLOSING SUPPLY FAIL A809 CLOSE CIRCUIT FAULTY NORMAL


SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 Closing coil DC fail
101 INTERLOCK BYPASS A809 INTL BYPASS ON OFF
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB SECTION A809 INTERLOCK BYPASS

102 CB ABNORMAL (A810) A810 BREAKER ABNORMAL NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 CLOSING SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 OPERATING MECHANISM SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 CONTROL SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 MOTOR SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 PUMP SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 BREAKER FAIL RELAY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 MOTOR THERMAL FAULT
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY DS/ES CONTROL SUPPLY FAIL

103 TRIP CIRCUIT FAULTY A810 TRIP CIRCUIT FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

104 CIRCUIT BREAKER GAS PRESSURE LOW A810 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 2

105 GIS GAS DENSITY ALARM A810 GAS DESITY ALARM ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 2

10 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 GIS GAS PRESSURE HIGH

106 BAY CONTROL SUPPLY FAIL A810 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 OPERATING MECH. SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 CONTROL SUPPLY DC FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 MOTOR SUPPLY AC FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 DS/ES CONTROL SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 DS/ES MOTOR SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

107 CIRCUIT BREAKER LOCKOUT A810 CB LOCKOUT OPERATE NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 SF6 GAS LOW STAGE-2
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY OPERATED STAGE-1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY OPERATED STAGE-2

108 CIRCUIT BREAKER POLE DISCREPANCY A810 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY RELAY OPERATED STAGE-2

109 SYNCHROCHECK RELAY FAULT A810 SYNC CHK FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 DC FAIL OPERATED
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 SELF SUPERVISION OPERATED
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 SYNCROCHECK FUSE FAILURE OPERATED

110 ALARM SUPPLY FAIL A810 ALARM SUPPLY FAILED NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 ALARM INDICATION SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 ANNUNCIATION DC SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 ANNUNCIATION AC BACKUP SUPPLY FAIL

111 CBF PROTECTION OPERATED A810 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 50BF CBF FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 BAY UNIT COMM. ERROR
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 86BF-2 TRIP RELAY FAULTY

112 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF LOCAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH LOCAL
113 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF REMOTE
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH REMOTE
114 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF BCU
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH BCU

115 GIS SF6 STAGE-2 ALARM A810 GIS SF6 2 ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 GIS SF6 GAS Pressure Low Stage-2

116 CLOSING SUPPLY FAIL A810 CLOSE CIRCUIT FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 Closing coil DC fail
117 INTERLOCK BYPASS A810 INTL BYPASS ON OFF
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SECTION A810 INTERLOCK BYPASS

118 CB ABNORMAL (A811) A811 BREAKER ABNORMAL NORMAL


SDRA C4.B A811 CB A811 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C4.B A811 CB A811 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C4.B A811 CB A811 CLOSING SUPPLY FAIL
SDRA C4.B A811 CB A811 OPERATING MECHANISM SUPPLY FAIL
SDRA C4.B A811 CB A811 CONTROL SUPPLY FAIL
SDRA C4.B A811 CB A811 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C4.B A811 CB A811 MOTOR SUPPLY FAIL
SDRA C4.B A811 CB A811 PUMP SUPPLY FAIL
SDRA C4.B A811 CB A811 BREAKER FAIL RELAY FAIL
SDRA C4.B A811 CB A811 MOTOR THERMAL FAULT

11 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.B A811 A811 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C4.B A811 A811 BAY DS/ES CONTROL SUPPLY FAIL

119 TRIP CIRCUIT FAULTY A811 TRIP CIRCUIT FAULTY NORMAL


SDRA C4.B A811 CB A811 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C4.B A811 CB A811 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

120 CIRCUIT BREAKER GAS PRESSURE LOW A811 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 2

121 GIS GAS DENSITY ALARM A811 GAS DESITY ALARM ALARM NORMAL
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C4.B A811 GIS GAS PRESSURE HIGH

122 BAY CONTROL SUPPLY FAIL A811 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.B A811 CB A811 OPERATING MECH. SUPPLY FAIL
SDRA C4.B A811 CB A811 CONTROL SUPPLY DC FAIL
SDRA C4.B A811 CB A811 MOTOR SUPPLY AC FAIL
SDRA C4.B A811 DS/ES CONTROL SUPPLY FAIL
SDRA C4.B A811 DS/ES MOTOR SUPPLY FAIL
SDRA C4.B A811 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.B A811 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

123 CIRCUIT BREAKER LOCKOUT A811 CB LOCKOUT OPERATE NORMAL


SDRA C4.B A811 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C4.B A811 SF6 GAS LOW STAGE-2
SDRA C4.B A811 POLE DISCREPANCY OPERATED STAGE-1
SDRA C4.B A811 POLE DISCREPANCY OPERATED STAGE-2

124 CIRCUIT BREAKER POLE DISCREPANCY A811 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.B A811 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.B A811 POLE DISCREPANCY RELAY OPERATED STAGE-2

125 SYNCHROCHECK RELAY FAULT A811 SYNC CHK FAULTY NORMAL


SDRA C4.B A811 DC FAIL OPERATED
SDRA C4.B A811 SELF SUPERVISION OPERATED
SDRA C4.B A811 SYNCROCHECK FUSE FAILURE OPERATED

126 ALARM SUPPLY FAIL A811 ALARM SUPPLY FAILED NORMAL


SDRA C4.B A811 ALARM INDICATION SUPPLY FAIL
SDRA C4.B A811 ANNUNCIATION DC SUPPLY FAIL
SDRA C4.B A811 ANNUNCIATION AC BACKUP SUPPLY FAIL

127 CBF PROTECTION OPERATED A811 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.B A811 50BF CBF FAULTY
SDRA C4.B A811 BAY UNIT COMM. ERROR
SDRA C4.B A811 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 86BF-2 TRIP RELAY FAULTY

128 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF LOCAL
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH LOCAL
129 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF REMOTE
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH REMOTE
130 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF BCU
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH BCU

131 GIS SF6 STAGE-2 ALARM A811 GIS SF6 2 ALARM NORMAL
SDRA C4.B A811 A811 GIS SF6 GAS Pressure Low Stage-2

132 CLOSING SUPPLY FAIL A811 CLOSE CIRCUIT FAULTY NORMAL


SDRA C4.B A811 CB A811 Closing coil DC fail

12 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
133 INTERLOCK BYPASS A811 INTL BYPASS ON OFF
SDRA C4.B A811 CB SECTION A811 INTERLOCK BYPASS

134 CB ABNORMAL (A812) A812 BREAKER ABNORMAL NORMAL


SDRA C4.C_T802 A812 CB A812 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C4.C_T802 A812 CB A812 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C4.C_T802 A812 CB A812 CLOSING SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 OPERATING MECHANISM SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 CONTROL SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C4.C_T802 A812 CB A812 MOTOR SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 PUMP SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 BREAKER FAIL RELAY FAIL
SDRA C4.C_T802 A812 CB A812 MOTOR THERMAL FAULT
SDRA C4.C_T802 A812 A812 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C4.C_T802 A812 A812 BAY DS/ES CONTROL SUPPLY FAIL

135 TRIP CIRCUIT FAULTY A812 TRIP CIRCUIT FAULTY NORMAL


SDRA C4.C_T802 A812 CB A812 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C4.C_T802 A812 CB A812 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

136 CIRCUIT BREAKER GAS PRESSURE LOW A812 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 2

137 GIS GAS DENSITY ALARM A812 GAS DESITY ALARM ALARM NORMAL
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C4.C_T802 A812 GIS GAS PRESSURE HIGH

138 BAY CONTROL SUPPLY FAIL A812 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.C_T802 A812 CB A812 OPERATING MECH. SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 CONTROL SUPPLY DC FAIL
SDRA C4.C_T802 A812 CB A812 MOTOR SUPPLY AC FAIL
SDRA C4.C_T802 A812 DS/ES CONTROL SUPPLY FAIL
SDRA C4.C_T802 A812 DS/ES MOTOR SUPPLY FAIL
SDRA C4.C_T802 A812 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.C_T802 A812 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

139 CIRCUIT BREAKER LOCKOUT A812 CB LOCKOUT OPERATE NORMAL


SDRA C4.C_T802 A812 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C4.C_T802 A812 SF6 GAS LOW STAGE-2
SDRA C4.C_T802 A812 POLE DISCREPANCY OPERATED STAGE-1
SDRA C4.C_T802 A812 POLE DISCREPANCY OPERATED STAGE-2

140 CIRCUIT BREAKER POLE DISCREPANCY A812 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.C_T802 A812 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.C_T802 A812 POLE DISCREPANCY RELAY OPERATED STAGE-2

141 SYNCHROCHECK RELAY FAULT A812 SYNC CHK FAULTY NORMAL


SDRA C4.C_T802 A812 DC FAIL OPERATED
SDRA C4.C_T802 A812 SELF SUPERVISION OPERATED
SDRA C4.C_T802 A812 SYNCROCHECK FUSE FAILURE OPERATED

142 ALARM SUPPLY FAIL A812 ALARM SUPPLY FAILED NORMAL


SDRA C4.C_T802 A812 ALARM INDICATION SUPPLY FAIL
SDRA C4.C_T802 A812 ANNUNCIATION DC SUPPLY FAIL
SDRA C4.C_T802 A812 ANNUNCIATION AC BACKUP SUPPLY FAIL

143 CBF PROTECTION OPERATED A812 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.C_T802 A812 50BF CBF FAULTY
SDRA C4.C_T802 A812 BAY UNIT COMM. ERROR
SDRA C4.C_T802 A812 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.C_T802 A812 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.C_T802 A812 CBF 94BF-2 TRIP RELAY FAULTY

13 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.C_T802 A812 CBF 86BF-2 TRIP RELAY FAULTY

144 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF LOCAL
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH LOCAL
145 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF REMOTE
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH REMOTE
146 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF BCU
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH BCU

147 GIS SF6 STAGE-2 ALARM A812 GIS SF6 2 ALARM NORMAL
SDRA C4.C_T802 A812 A812 GIS SF6 GAS Pressure Low Stage-2

148 CLOSING SUPPLY FAIL A812 CLOSE CIRCUIT FAULTY NORMAL


SDRA C4.C_T802 A812 CB A812 Closing coil DC fail
149 INTERLOCK BYPASS A812 INTL BYPASS ON OFF
SDRA C4.C_T802 A812 CB SECTION A812 INTERLOCK BYPASS

150 CB ABNORMAL (FUTURE A813) FUTURE A813 BREAKER ABNORMAL NORMAL


SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 CLOSING SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 OPERATING MECHANISM SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 CONTROL SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 MOTOR SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 PUMP SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 BREAKER FAIL RELAY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 MOTOR THERMAL FAULT
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY DS/ES CONTROL SUPPLY FAIL

151 TRIP CIRCUIT FAULTY FUTURE A813 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

152 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A813 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 2

153 GIS GAS DENSITY ALARM FUTURE A813 GAS DESITY ALARM ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.A_FUTURE LINE FUTURE A813 GIS GAS PRESSURE HIGH

154 BAY CONTROL SUPPLY FAIL FUTURE A813 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 OPERATING MECH. SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 CONTROL SUPPLY DC FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 MOTOR SUPPLY AC FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 DS/ES CONTROL SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 DS/ES MOTOR SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

155 CIRCUIT BREAKER LOCKOUT FUTURE A813 CB LOCKOUT OPERATE NORMAL


SDRA C5.A_FUTURE LINE FUTURE A813 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C5.A_FUTURE LINE FUTURE A813 SF6 GAS LOW STAGE-2
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY OPERATED STAGE-1
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY OPERATED STAGE-2

156 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A813 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY RELAY OPERATED STAGE-2

157 SYNCHROCHECK RELAY FAULT FUTURE A813 SYNC CHK FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 DC FAIL OPERATED

14 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.A_FUTURE LINE FUTURE A813 SELF SUPERVISION OPERATED
SDRA C5.A_FUTURE LINE FUTURE A813 SYNCROCHECK FUSE FAILURE OPERATED

158 ALARM SUPPLY FAIL FUTURE A813 ALARM SUPPLY FAILED NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 ALARM INDICATION SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 ANNUNCIATION AC BACKUP SUPPLY FAIL

159 CBF PROTECTION OPERATED FUTURE A813 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 50BF CBF FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 BAY UNIT COMM. ERROR
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 86BF-2 TRIP RELAY FAULTY

160 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF LOCAL
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH LOCAL
161 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF REMOTE
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH REMOTE
162 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF BCU
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH BCU

163 GIS SF6 STAGE-2 ALARM FUTURE A813 GIS SF6 2 ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 GIS SF6 GAS Pressure Low Stage-2

164 CLOSING SUPPLY FAIL FUTURE A813 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 Closing coil DC fail
165 INTERLOCK BYPASS FUTURE A813 INTL BYPASS ON OFF
SDRA C5.A_FUTURE LINE FUTURE A813 CB SECTION FUTURE A813 INTERLOCK BYPASS

166 CB ABNORMAL (FUTURE A814) FUTURE A814 BREAKER ABNORMAL NORMAL


SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 CLOSING SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 OPERATING MECHANISM SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 CONTROL SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 MOTOR SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 PUMP SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 BREAKER FAIL RELAY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 MOTOR THERMAL FAULT
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY DS/ES CONTROL SUPPLY FAIL

167 TRIP CIRCUIT FAULTY FUTURE A814 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

168 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A814 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 2

169 GIS GAS DENSITY ALARM FUTURE A814 GAS DESITY ALARM ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.B_FUTURE LINE FUTURE A814 GIS GAS PRESSURE HIGH

170 BAY CONTROL SUPPLY FAIL FUTURE A814 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 OPERATING MECH. SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 CONTROL SUPPLY DC FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 MOTOR SUPPLY AC FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 DS/ES CONTROL SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 DS/ES MOTOR SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB TRIP CIRCUIT-1 DC SUPPLY FAIL

15 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.B_FUTURE LINE FUTURE A814 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

171 CIRCUIT BREAKER LOCKOUT FUTURE A814 CB LOCKOUT OPERATE NORMAL


SDRA C5.B_FUTURE LINE FUTURE A814 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C5.B_FUTURE LINE FUTURE A814 SF6 GAS LOW STAGE-2
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY OPERATED STAGE-1
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY OPERATED STAGE-2

172 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A814 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY RELAY OPERATED STAGE-2

173 SYNCHROCHECK RELAY FAULT FUTURE A814 SYNC CHK FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 DC FAIL OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 SELF SUPERVISION OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 SYNCROCHECK FUSE FAILURE OPERATED

174 ALARM SUPPLY FAIL FUTURE A814 ALARM SUPPLY FAILED NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 ALARM INDICATION SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 ANNUNCIATION AC BACKUP SUPPLY FAIL

175 CBF PROTECTION OPERATED FUTURE A814 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 50BF CBF FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 BAY UNIT COMM. ERROR
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 86BF-2 TRIP RELAY FAULTY

176 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF LOCAL
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH LOCAL
177 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF REMOTE
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH REMOTE
178 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF BCU
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH BCU

179 GIS SF6 STAGE-2 ALARM FUTURE A814 GIS SF6 2 ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 GIS SF6 GAS Pressure Low Stage-2

180 CLOSING SUPPLY FAIL FUTURE A814 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 Closing coil DC fail
181 INTERLOCK BYPASS FUTURE A814 INTL BYPASS ON OFF
SDRA C5.B_FUTURE LINE FUTURE A814 CB SECTION FUTURE A814 INTERLOCK BYPASS

182 CB ABNORMAL (FUTURE A815) FUTURE A815 BREAKER ABNORMAL NORMAL


SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 HYDRAULIC PRESSURE CLOSE LOCK
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 HYDRAULIC PRESSURE O-C-0 LOCK
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 CLOSING SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 OPERATING MECHANISM SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 CONTROL SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 PUMP/COMPR RUNNING TIME EXCEEDED
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 MOTOR SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 PUMP SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 BREAKER FAIL RELAY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 MOTOR THERMAL FAULT
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY DS/ES CONTROL SUPPLY FAIL

183 TRIP CIRCUIT FAULTY FUTURE A815 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED

184 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A815 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 1

16 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 2

185 GIS GAS DENSITY ALARM FUTURE A815 GAS DESITY ALARM ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.C_FUTURE LINE FUTURE A815 GIS GAS PRESSURE HIGH

186 BAY CONTROL SUPPLY FAIL FUTURE A815 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 OPERATING MECH. SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 CONTROL SUPPLY DC FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 MOTOR SUPPLY AC FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 DS/ES CONTROL SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 DS/ES MOTOR SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB TRIP CIRCUIT-2 DC SUPPLY FAIL

187 CIRCUIT BREAKER LOCKOUT FUTURE A815 CB LOCKOUT OPERATE NORMAL


SDRA C5.C_FUTURE LINE FUTURE A815 HYDRAULIC PRESSURE STAGE-2 LOCK
SDRA C5.C_FUTURE LINE FUTURE A815 SF6 GAS LOW STAGE-2
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY OPERATED STAGE-1
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY OPERATED STAGE-2

188 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A815 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY RELAY OPERATED STAGE-2

189 SYNCHROCHECK RELAY FAULT FUTURE A815 SYNC CHK FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 DC FAIL OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 SELF SUPERVISION OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 SYNCROCHECK FUSE FAILURE OPERATED

190 ALARM SUPPLY FAIL FUTURE A815 ALARM SUPPLY FAILED NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 ALARM INDICATION SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 ANNUNCIATION AC BACKUP SUPPLY FAIL

191 CBF PROTECTION OPERATED FUTURE A815 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 50BF CBF FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 BAY UNIT COMM. ERROR
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 86BF-2 TRIP RELAY FAULTY

192 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF LOCAL
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH LOCAL
193 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF REMOTE
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH REMOTE
194 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF BCU
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH BCU

195 GIS SF6 STAGE-2 ALARM FUTURE A815 GIS SF6 2 ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 GIS SF6 GAS Pressure Low Stage-2

196 CLOSING SUPPLY FAIL FUTURE A815 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 Closing coil DC fail
197 INTERLOCK BYPASS FUTURE A815 INTL BYPASS ON OFF
SDRA C5.C_FUTURE LINE FUTURE A815 CB SECTION FUTURE A815 INTERLOCK BYPASS

380kV FEEDER JUBAIL LINE-1


198 LINE PROTECTION MAIN-1 FAIL LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 CCVT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 REALY OPERATED
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 TRIP RELAY COIL FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION TRIP ISOLATED

17 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 R1 PROTN. LOSS OF AC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/DC-1 LOSS OF DC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-1 VT FUSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 98/25AR BUS VT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/94-1 SUPVN OPTD

199 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-A OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-B OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-C OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 94-1 TRIP RELAY OPTD

200 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 87L/21-1- RELAY TRIP

201 DC-1 SUPPLY FAIL DC-1 SUPPLY FAIL FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 DC FAIL

202 TRIP CIRCUIT-1 FAULTY TRIP CIRCUIT-1 FAULTY FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 TRIP CIRCUIT-1 FAULTY

203 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-2 CCVT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-2 REALY OPERATED
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 TRIP RELAY COIL FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION TRIP ISOLATED
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 R1 PROTN. LOSS OF AC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/DC-2 LOSS OF DC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-2 VT FUSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 98/25AR BUS VT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/94-2 SUPVN OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION IN/OUT

204 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-A OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-B OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-C OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 94-2 TRIP RELAY OPTD

205 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 87L/21-2- RELAY TRIP

206 DC-2 SUPPLY FAIL DC-2 SUPPLY FAIL FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-2 DC FAIL

207 TRIP CIRCUIT-2 FAULTY TRIP CIRCUIT-2 FAULTY FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 TRIP CIRCUIT-2 FAULTY

208 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 BKR FAIL RECV.
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 BKR CH-2 FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PD CH-2 FAIL

209 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 BKR FAIL CH-1 RECV.
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PD CH-1 RECV.
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 BKR FAIL CH-2 RECV
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PD CH-2 RECV.

210 AUTO RECLOSE IN SERVICE AR IN SERVICE FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 AUTO RECLOSE IN SERVICE

211 AUTO RECLOSE IN REMOTE AR IN REMOTE FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 AUTO RECLOSE IN REMOTE

18 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
212 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 AUTO RECLOSE FAIL

213 AUTO RECLOSE OPERATED AR IN OPTD FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 AUTO RECLOSE OPERATED

214 87L_M1 COMMUNICATION FAIL 87L_1M1 COMMUNICATION FAIL FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87-1 COMM. FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-1 DIST CH FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 67N-1 DEF CH FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-1 PSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 DTT CHNL FAULTY

215 87L_M2 COMMUNICATION FAIL 87L_2 M2 COMMUNICATION FAIL FAULTY NORMAL


SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87-2 COMM. FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-2 DIST CH FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 67N-2 DEF CH FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-2 PSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 DTT CHNL FAULTY

380kV FEEDER JUBAIL LINE-2


216 LINE PROTECTION MAIN-1 FAIL LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 CCVT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 REALY OPERATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 TRIP RELAY COIL FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/DC-1 LOSS OF DC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-1 VT FUSE FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 98/25AR BUS VT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/94-1 SUPVN OPTD

217 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-A OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-B OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-C OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 94-1 TRIP RELAY OPTD

218 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 87L/21-1- RELAY TRIP

219 DC-1 SUPPLY FAIL DC-1 SUPPLY FAIL FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 DC FAIL

220 TRIP CIRCUIT-1 FAULTY TRIP CIRCUIT-1 FAULTY FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 TRIP CIRCUIT-1 FAULTY

221 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-2 CCVT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-2 REALY OPERATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 TRIP RELAY COIL FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/DC-2 LOSS OF DC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-2 VT FUSE FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 98/25AR BUS VT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/94-2 SUPVN OPTD

222 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-A OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-B OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-C OPTD

19 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 94-2 TRIP RELAY OPTD

223 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 87L/21-2- RELAY TRIP

224 DC-2 SUPPLY FAIL DC-2 SUPPLY FAIL FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-2 DC FAIL

225 TRIP CIRCUIT-2 FAULTY TRIP CIRCUIT-2 FAULTY FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 TRIP CIRCUIT-2 FAULTY

226 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 BKR FAIL RECV.
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 BKR CH-2 FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PD CH-2 FAIL

227 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 BKR FAIL CH-1 RECV.
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PD CH-1 RECV.
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 BKR FAIL CH-2 RECV
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PD CH-2 RECV.

228 AUTO RECLOSE IN SERVICE AR IN SERVICE FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 AUTO RECLOSE IN SERVICE

229 AUTO RECLOSE IN REMOTE AR IN REMOTE FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 AUTO RECLOSE IN REMOTE

230 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 AUTO RECLOSE FAIL

231 AUTO RECLOSE OPERATED AR IN OPTD FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 AUTO RECLOSE OPERATED

232 87L_M1 COMMUNICATION FAIL 87L_1M1 COMMUNICATION FAIL FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87-1 COMM. FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-1 DIST CH FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 67N-1 DEF CH FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-1 PSE FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 DTT CHNL FAULTY

233 87L_M2 COMMUNICATION FAIL 87L_2 M2 COMMUNICATION FAIL FAULTY NORMAL


SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87-2 COMM. FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-2 DIST CH FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 67N-2 DEF CH FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-2 PSE FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 DTT CHNL FAULTY
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION IN/OUT

380kV FEEDER JUBAIL COMMUNITY2 LINE-1


234 LINE PROTECTION MAIN-1 FAIL LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 CCVT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 REALY OPERATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 TRIP RELAY COIL FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION TRIP ISOLATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 R1 PROTN. LOSS OF AC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/DC-1 LOSS OF DC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-1 VT FUSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 98/25AR BUS VT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/94-1 SUPVN OPTD

235 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-A OPTD

20 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-B OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-C OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 94-1 TRIP RELAY OPTD

236 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 87L/21-1- RELAY TRIP

237 DC-1 SUPPLY FAIL DC-1 SUPPLY FAIL FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 DC FAIL

238 TRIP CIRCUIT-1 FAULTY TRIP CIRCUIT-1 FAULTY FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 TRIP CIRCUIT-1 FAULTY

239 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-2 CCVT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-2 REALY OPERATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 TRIP RELAY COIL FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION TRIP ISOLATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 R1 PROTN. LOSS OF AC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/DC-2 LOSS OF DC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-2 VT FUSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 98/25AR BUS VT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/94-2 SUPVN OPTD

240 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-A OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-B OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-C OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 94-2 TRIP RELAY OPTD

241 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 87L/21-2- RELAY TRIP

242 DC-2 SUPPLY FAIL DC-2 SUPPLY FAIL FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-2 DC FAIL

243 TRIP CIRCUIT-2 FAULTY TRIP CIRCUIT-2 FAULTY FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 TRIP CIRCUIT-2 FAULTY

244 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 BKR FAIL RECV.
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 BKR CH-2 FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PD CH-2 FAIL

245 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 BKR FAIL CH-1 RECV.
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PD CH-1 RECV.
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 BKR FAIL CH-2 RECV
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PD CH-2 RECV.

246 AUTO RECLOSE IN SERVICE AR IN SERVICE FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 AUTO RECLOSE IN SERVICE

247 AUTO RECLOSE IN REMOTE AR IN REMOTE FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 AUTO RECLOSE IN REMOTE

248 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 AUTO RECLOSE FAIL

249 AUTO RECLOSE OPERATED AR IN OPTD FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 AUTO RECLOSE OPERATED

250 87L_M1 COMMUNICATION FAIL 87L_1M1 COMMUNICATION FAIL FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87-1 COMM. FAIL

21 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-1 DIST CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 67N-1 DEF CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-1 PSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 DTT CHNL FAULTY

251 87L_M2 COMMUNICATION FAIL 87L_2 M2 COMMUNICATION FAIL FAULTY NORMAL


SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87-2 COMM. FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-2 DIST CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 67N-2 DEF CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-2 PSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 DTT CHNL FAULTY
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION IN/OUT

380kV FEEDER JUBAIL COMMUNITY2 LINE-2


252 LINE PROTECTION MAIN-1 FAIL LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 CCVT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 REALY OPERATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP RELAY COIL FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/DC-1 LOSS OF DC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-1 VT FUSE FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 98/25AR BUS VT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/94-1 SUPVN OPTD

253 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-A OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-B OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-C OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 94-1 TRIP RELAY OPTD

254 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 87L/21-1- RELAY TRIP

255 DC-1 SUPPLY FAIL DC-1 SUPPLY FAIL FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 DC FAIL

256 TRIP CIRCUIT-1 FAULTY TRIP CIRCUIT-1 FAULTY FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP CIRCUIT-1 FAULTY

257 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-2 CCVT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-2 REALY OPERATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP RELAY COIL FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/DC-2 LOSS OF DC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-2 VT FUSE FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 98/25AR BUS VT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/94-2 SUPVN OPTD

258 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-A OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-B OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-C OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 94-2 TRIP RELAY OPTD

259 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 87L/21-2- RELAY TRIP

260 DC-2 SUPPLY FAIL DC-2 SUPPLY FAIL FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-2 DC FAIL

261 TRIP CIRCUIT-2 FAULTY TRIP CIRCUIT-2 FAULTY FAULTY NORMAL

22 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP CIRCUIT-2 FAULTY

262 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 BKR FAIL RECV.
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 BKR CH-2 FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PD CH-2 FAIL

263 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 BKR FAIL CH-1 RECV.
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PD CH-1 RECV.
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 BKR FAIL CH-2 RECV
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PD CH-2 RECV.

264 AUTO RECLOSE IN SERVICE AR IN SERVICE FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 AUTO RECLOSE IN SERVICE

265 AUTO RECLOSE IN REMOTE AR IN REMOTE FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 AUTO RECLOSE IN REMOTE

266 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 AUTO RECLOSE FAIL

267 AUTO RECLOSE OPERATED AR IN OPTD FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 AUTO RECLOSE OPERATED

268 87L_M1 COMMUNICATION FAIL 87L_1M1 COMMUNICATION FAIL FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87-1 COMM. FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-1 DIST CH FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 67N-1 DEF CH FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-1 PSE FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 DTT CHNL FAULTY

269 87L_M2 COMMUNICATION FAIL 87L_2 M2 COMMUNICATION FAIL FAULTY NORMAL


SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87-2 COMM. FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-2 DIST CH FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 67N-2 DEF CH FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-2 PSE FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 DTT CHNL FAULTY
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION IN/OUT

380kV FEEDER FUTURE LINE


270 LINE PROTECTION MAIN-1 FAIL LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 CCVT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 REALY OPERATED
SDRA C5.A_FUTURE LINE FUTURE LINE TRIP RELAY COIL FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION TRIP ISOLATED
SDRA C5.A_FUTURE LINE FUTURE LINE R1 PROTN. LOSS OF AC
SDRA C5.A_FUTURE LINE FUTURE LINE 74/DC-1 LOSS OF DC
SDRA C5.A_FUTURE LINE FUTURE LINE 21-1 VT FUSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 98/25AR BUS VT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 74/94-1 SUPVN OPTD

271 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-A OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-B OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-C OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 94-1 TRIP RELAY OPTD

272 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 87L/21-1- RELAY TRIP

273 DC-1 SUPPLY FAIL DC-1 SUPPLY FAIL FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 DC FAIL

23 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address

274 TRIP CIRCUIT-1 FAULTY TRIP CIRCUIT-1 FAULTY FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE TRIP CIRCUIT-1 FAULTY

275 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-2 CCVT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-2 REALY OPERATED
SDRA C5.A_FUTURE LINE FUTURE LINE TRIP RELAY COIL FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION TRIP ISOLATED
SDRA C5.A_FUTURE LINE FUTURE LINE R1 PROTN. LOSS OF AC
SDRA C5.A_FUTURE LINE FUTURE LINE 74/DC-2 LOSS OF DC
SDRA C5.A_FUTURE LINE FUTURE LINE 21-2 VT FUSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 98/25AR BUS VT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 74/94-2 SUPVN OPTD

276 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-A OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-B OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-C OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 94-2 TRIP RELAY OPTD

277 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 87L/21-2- RELAY TRIP

278 DC-2 SUPPLY FAIL DC-2 SUPPLY FAIL FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE SET-2 DC FAIL

279 TRIP CIRCUIT-2 FAULTY TRIP CIRCUIT-2 FAULTY FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE TRIP CIRCUIT-2 FAULTY

280 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE BKR FAIL RECV.
SDRA C5.A_FUTURE LINE FUTURE LINE BKR CH-2 FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE PD CH-2 FAIL

281 INTERTRIP RECEIVE INTERTRIP RECEIVE FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE BKR FAIL CH-1 RECV.
SDRA C5.A_FUTURE LINE FUTURE LINE PD CH-1 RECV.
SDRA C5.A_FUTURE LINE FUTURE LINE BKR FAIL CH-2 RECV
SDRA C5.A_FUTURE LINE FUTURE LINE PD CH-2 RECV.

282 AUTO RECLOSE IN SERVICE AR IN SERVICE FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE AUTO RECLOSE IN SERVICE

283 AUTO RECLOSE IN REMOTE AR IN REMOTE FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE AUTO RECLOSE IN REMOTE

284 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE AUTO RECLOSE FAIL

285 AUTO RECLOSE OPERATED AR IN OPTD FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE AUTO RECLOSE OPERATED

286 87L_M1 COMMUNICATION FAIL 87L_1M1 COMMUNICATION FAIL FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 87-1 COMM. FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 21-1 DIST CH FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 67N-1 DEF CH FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 21-1 PSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE DTT CHNL FAULTY

287 87L_M2 COMMUNICATION FAIL 87L_2 M2 COMMUNICATION FAIL FAULTY NORMAL


SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION SIGNALLING EQUIPMENT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 87-2 COMM. FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 21-2 DIST CH FAIL

24 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.A_FUTURE LINE FUTURE LINE 67N-2 DEF CH FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 21-2 PSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE DTT CHNL FAULTY
SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION IN/OUT

380kV TRANSFORMER T801


288 PRIMARY PROTECTION FAULTY PRIMARY PROTECTION FAULTY FAULTY NORMAL
SDRA C2.A_T801 T801 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C2.A_T801 T801 DC FAIL
SDRA C2.A_T801 T801 LOCK OUT RELAY FAIL
SDRA C2.A_T801 T801 24 HV OVER FLUXING RELAY FAIL
SDRA C2.A_T801 T801 24 MV OVER FLUXING RELAY FAIL
SDRA C2.A_T801 T801 HV FUSE FAIL OPERATED
SDRA C2.A_T801 T801 MV FUSE FAIL OPERATED

289 BACK-UP PROTECTION FAULTY BACK UP PROTECTION FAULTY FAULTY NORMAL


SDRA C2.A_T801 T801 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C2.A_T801 T801 DC FAIL
SDRA C2.A_T801 T801 LOCK OUT RELAY FAIL
SDRA C2.A_T801 T801 OVER CURRENT RELAY FAIL
SDRA C2.A_T801 T801 E/F RELAY FAIL

290 BUCHOLZ STAGE-1 OPERATED BUCHOLZ STAGE-1 OPERATED NORMAL OPERATE


SDRA C2.A_T801 T801 MAIN TRANSFORMER BUCHOLZ STG-1 OPERATED

291 BUCHOLZ STAGE-2 OPERATED BUCHOLZ STAGE-2 OPERATED NORMAL OPERATE


SDRA C2.A_T801 T801 MAIN TRANSFORMER BUCHOLZ STG-2 OPERATED

292 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C2.A_T801 T801 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1

293 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C2.A_T801 T801 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1

294 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C2.A_T801 T801 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2

295 OIL LEVEL LOW OIL LEVEL LOW NORMAL OPERATE


SDRA C2.A_T801 T801 MAIN TRANSFORMER OIL LEVEL LOW
SDRA C2.A_T801 T801 TAP CHANGER OIL LEVEL LOW

296 PRESSURE RELIEF OPERATED PRESSURE RELIEF OPERATED FAULTY NORMAL


SDRA C2.A_T801 T801 MAIN TRANSFORMER PRESSURE RELIEF TRIP
TAP CHANGER PRESSURE RELIEF TRIP

297 COOLING SYSTEM FAULTY COOLING SYSTEM FAULTY FAULTY NORMAL


SDRA C2.A_T801 T801 FAN MCB TRIP
SDRA C2.A_T801 T801 COOLER AC/DC SUPPLY FAIL
SDRA C2.A_T801 T801 AC SYSTEM VOLTAGE FAIL

298 TAP CHANGER FAULTY TAP CHANGER FAULTY FAULTY NORMAL


SDRA C2.A_T801 T801 TAP CHANGER DRIVE FAILURE
SDRA C2.A_T801 T801 OLTC PARALLEL OPERATION DISTURBED
SDRA C2.A_T801 T801 OLTC RAISE/LOWER LIMIT REACHED
SDRA C2.A_T801 T801 OLTC MOTOR CIRCUIT TRIPPED
SDRA C2.A_T801 T801 LOSS OF OLTC MOTOR SUPPLY
SDRA C2.A_T801 T801 OLTC OUT OF STEP
SDRA C2.A_T801 T801 AVR BLOCKED
SDRA C2.A_T801 T801 RTCC CONTROL SUPPLY FAIL

299 TRANSFORMER TRIP DISABLED TRANSFORMER TRIP DISABLED FAULTY NORMAL


SDRA C2.A_T801 T801 TRANSFORMER TRIP DISABLED

25 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
300 PRIMARY PROTECTION OPERATED PRIMARY PROTECTION OPERATED NORMAL OPERATE
SDRA C2.A_T801 T801 86-1 OPERATED
C2.A_T801 T801 HV OVER FLUXING OPERATED
C2.A_T801 T801 MV OVER FLUXING OPERATED
C2.A_T801 T801 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-1 OPERATED
C2.A_T801 T801 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-2 OPERATED
C2.A_T801 T801 OLTC SURGE RELAY TRIP
C2.A_T801 T801 67 OVER CURRENT OPERATED
C2.A_T801 T801 51 GT OPERATED
C2.A_T801 T801 GT OPERATED

301 BACK UP PROTECTION OPERATED BACK UP PROTECTION OPERATED FAULTY NORMAL


SDRA C2.A_T801 T801 BACK UP PROTECTION OPERATED

302 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL
SDRA C2.A_T801 T801 WINDING TEMP. STAGE-2 OPERATED

303 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C2.A_T801 T801 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED

304 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C2.A_T801 T801 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED

305 TRANSFORMER MECHANICAL PROTECTION OPERATED TRANSFORMER MECHANICAL PROTECTION OPERATED


FAULTY NORMAL
SDRA C2.A_T801 T801 MAIN T/F WINDING TEMP. HIGH STAGE-2
SDRA C2.A_T801 T801 GT T/F WINDING TEMP. STAGE-2
SDRA C2.A_T801 T801 OLTC PROTECTION RELAY TRIP
SDRA C2.A_T801 T801 MAIN TRANSFORMER BUCHOLZ STAGE-2
SDRA C2.A_T801 T801 GT BUCHOLZ STAGE-2
SDRA C2.A_T801 T801 86-2,86-4,86-5 OPERATED

380kV TRANSFORMER T802


306 PRIMARY PROTECTION FAULTY PRIMARY PROTECTION FAULTY FAULTY NORMAL
SDRA C4.C_T802 T802 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C4.C_T802 T802 DC FAIL
SDRA C4.C_T802 T802 LOCK OUT RELAY FAIL
SDRA C4.C_T802 T802 HV OVER FLUXING RELAY FAIL
SDRA C4.C_T802 T802 MV OVER FLUXING RELAY FAIL
SDRA C4.C_T802 T802 HV FUSE FAIL OPERATED
SDRA C4.C_T802 T802 MV FUSE FAIL OPERATED

307 BACK-UP PROTECTION FAULTY BACK UP PROTECTION FAULTY FAULTY NORMAL


SDRA C4.C_T802 T802 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C4.C_T802 T802 DC FAIL
SDRA C4.C_T802 T802 LOCK OUT RELAY FAIL
SDRA C4.C_T802 T802 OVER FLUXING RELAY FAIL
SDRA C4.C_T802 T802 E/F RELAY FAIL

308 BUCHOLZ STAGE-1 OPERATED BUCHOLZ STAGE-1 OPERATED NORMAL OPERATE


SDRA C4.C_T802 T802 MAIN TRANSFORMER BUCHOLZ STG-1 OPERATED

309 BUCHOLZ STAGE-2 OPERATED BUCHOLZ STAGE-2 OPERATED NORMAL OPERATE


SDRA C4.C_T802 T802 MAIN TRANSFORMER BUCHOLZ STG-2 OPERATED

310 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C4.C_T802 T802 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1

311 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1

312 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2

26 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
313 OIL LEVEL LOW OIL LEVEL LOW NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL LEVEL LOW
SDRA C4.C_T802 T802 TAP CHANGER OIL LEVEL LOW

314 PRESSURE RELIEF OPERATED PRESSURE RELIEF OPERATED FAULTY NORMAL


SDRA C4.C_T802 T802 MAIN TRANSFORMER PRESSURE RELIEF TRIP
TAP CHANGER PRESSURE RELIEF TRIP

315 COOLING SYSTEM FAULTY COOLING SYSTEM FAULTY FAULTY NORMAL


SDRA C4.C_T802 T802 FAN MCB TRIP
SDRA C4.C_T802 T802 COOLER AC/DC SUPPLY FAIL
SDRA C4.C_T802 T802 AC SYSTEM VOLTAGE FAIL

316 TAP CHANGER FAULTY TAP CHANGER FAULTY FAULTY NORMAL


SDRA C4.C_T802 T802 TAP CHANGER DRIVE FAILURE
SDRA C4.C_T802 T802 OLTC PARALLEL OPERATION DISTURBED
SDRA C4.C_T802 T802 OLTC RAISE/LOWER LIMIT REACHED
SDRA C4.C_T802 T802 OLTC MOTOR CIRCUIT TRIPPED
SDRA C4.C_T802 T802 LOSS OF OLTC MOTOR SUPPLY
SDRA C4.C_T802 T802 OLTC OUT OF STEP
SDRA C4.C_T802 T802 AVR BLOCKED
SDRA C4.C_T802 T802 RTCC CONTROL SUPPLY FAIL

317 TRANSFORMER TRIP DISABLED TRANSFORMER TRIP DISABLED FAULTY NORMAL


SDRA C4.C_T802 T802 TRANSFORMER TRIP DISABLED

318 PRIMARY PROTECTION OPERATED PRIMARY PROTECTION OPERATED NORMAL OPERATE


SDRA C4.C_T802 T802 86-1 OPERATED
C4.C_T802 T802 OVER FLUXING OPERATED
C4.C_T802 T802 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-1 OPERATED
C4.C_T802 T802 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-2 OPERATED
C4.C_T802 T802 OLTC SURGE RELAY TRIP
C4.C_T802 T802 67 OVER CURRENT OPERATED
C4.C_T802 T802 51 GT OPERATED
C4.C_T802 T802 GT OPERATED

319 BACK UP PROTECTION OPERATED BACK UP PROTECTION OPERATED FAULTY NORMAL


SDRA C4.C_T802 T802 BACK UP PROTECTION OPERATED

320 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL
SDRA C4.C_T802 T802 WINDING TEMP. STAGE-2 OPERATED

321 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C4.C_T802 T802 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED

322 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C4.C_T802 T802 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED

323 TRANSFORMER MECHANICAL PROTECTION OPERATED TRANSFORMER MECHANICAL PROTECTION OPERATED


FAULTY NORMAL
SDRA C4.C_T802 T802 MAIN T/F WINDING TEMP. HIGH STAGE-2
SDRA C4.C_T802 T802 GT T/F WINDING TEMP. STAGE-2
SDRA C4.C_T802 T802 OLTC PROTECTION RELAY TRIP
SDRA C4.C_T802 T802 MAIN TRANSFORMER BUCHOLZ STAGE-2
SDRA C4.C_T802 T802 GT BUCHOLZ STAGE-2
SDRA C4.C_T802 T802 86-2,86-4,86-5 OPERATED

380kV FUTURE TRANSFORMER T803


324 PRIMARY PROTECTION FAULTY PRIMARY PROTECTION FAULTY FAULTY NORMAL
SDRA C5.C_T803 T803 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C5.C_T803 T803 DC FAIL
SDRA C5.C_T803 T803 LOCK OUT RELAY FAIL
SDRA C5.C_T803 T803 HV OVER FLUXING RELAY FAIL
SDRA C5.C_T803 T803 MV OVER CURRENT RELAY FAIL
SDRA C5.C_T803 T803 HV FUSE FAIL OPERATED
SDRA C5.C_T803 T803 LV FUSE FAIL OPERATED

27 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address

325 BACK-UP PROTECTION FAULTY BACK UP PROTECTION FAULTY FAULTY NORMAL


SDRA C5.C_T803 T803 FIRST MAIN PROTECTION CT CKT. SUPERVISION RELAY
SDRA C5.C_T803 T803 DC FAIL
SDRA C5.C_T803 T803 LOCK OUT RELAY FAIL
SDRA C5.C_T803 T803 OVER FLUXING RELAY FAIL
SDRA C5.C_T803 T803 E/F RELAY FAIL

326 BUCHOLZ STAGE-1 OPERATED BUCHOLZ STAGE-1 OPERATED NORMAL OPERATE


SDRA C5.C_T803 T803 MAIN TRANSFORMER BUCHOLZ STG-1 OPERATED

327 BUCHOLZ STAGE-2 OPERATED BUCHOLZ STAGE-2 OPERATED NORMAL OPERATE


SDRA C5.C_T803 T803 MAIN TRANSFORMER BUCHOLZ STG-2 OPERATED

328 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C5.C_T803 T803 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1

329 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C5.C_T803 T803 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1

330 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C5.C_T803 T803 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2

331 OIL LEVEL LOW OIL LEVEL LOW NORMAL OPERATE


SDRA C5.C_T803 T803 MAIN TRANSFORMER OIL LEVEL LOW
SDRA C5.C_T803 T803 TAP CHANGER OIL LEVEL LOW

332 PRESSURE RELIEF OPERATED PRESSURE RELIEF OPERATED FAULTY NORMAL


SDRA C5.C_T803 T803 MAIN TRANSFORMER PRESSURE RELIEF TRIP
TAP CHANGER PRESSURE RELIEF TRIP

333 COOLING SYSTEM FAULTY COOLING SYSTEM FAULTY FAULTY NORMAL


SDRA C5.C_T803 T803 FAN MCB TRIP
SDRA C5.C_T803 T803 COOLER AC/DC SUPPLY FAIL
SDRA C5.C_T803 T803 AC SYSTEM VOLTAGE FAIL

334 TAP CHANGER FAULTY TAP CHANGER FAULTY FAULTY NORMAL


SDRA C5.C_T803 T803 TAP CHANGER DRIVE FAILURE
SDRA C5.C_T803 T803 OLTC PARALLEL OPERATION DISTURBED
SDRA C5.C_T803 T803 OLTC RAISE/LOWER LIMIT REACHED
SDRA C5.C_T803 T803 OLTC MOTOR CIRCUIT TRIPPED
SDRA C5.C_T803 T803 LOSS OF OLTC MOTOR SUPPLY
SDRA C5.C_T803 T803 OLTC OUT OF STEP
SDRA C5.C_T803 T803 AVR BLOCKED
SDRA C5.C_T803 T803 RTCC CONTROL SUPPLY FAIL

335 TRANSFORMER TRIP DISABLED TRANSFORMER TRIP DISABLED FAULTY NORMAL


SDRA C5.C_T803 T803 TRANSFORMER TRIP DISABLED

336 PRIMARY PROTECTION OPERATED PRIMARY PROTECTION OPERATED NORMAL OPERATE


SDRA C5.C_T803 T803 86-1 OPERATED
C5.C_T803 T803 OVER FLUXING OPERATED
C5.C_T803 T803 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-1 OPERATED
C5.C_T803 T803 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-2 OPERATED
C5.C_T803 T803 OLTC SURGE RELAY TRIP
C5.C_T803 T803 67 OVER CURRENT OPERATED
C5.C_T803 T803 51 GT OPERATED
C5.C_T803 T803 GT OPERATED

337 BACK UP PROTECTION OPERATED BACK UP PROTECTION OPERATED FAULTY NORMAL


SDRA C5.C_T803 T803 BACK UP PROTECTION OPERATED

338 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL

28 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.C_T803 T803 WINDING TEMP. STAGE-2 OPERATED

339 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C5.C_T803 T803 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED

340 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C5.C_T803 T803 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED

341 TRANSFORMER MECHANICAL PROTECTION OPERATED TRANSFORMER MECHANICAL PROTECTION OPERATED


FAULTY NORMAL
SDRA C5.C_T803 T803 MAIN T/F WINDING TEMP. HIGH STAGE-2
SDRA C5.C_T803 T803 GT T/F WINDING TEMP. STAGE-2
SDRA C5.C_T803 T803 OLTC PROTECTION RELAY TRIP
SDRA C5.C_T803 T803 MAIN TRANSFORMER BUCHOLZ STAGE-2
SDRA C5.C_T803 T803 GT BUCHOLZ STAGE-2
SDRA C5.C_T803 T803 86-2,86-4,86-5 OPERATED

AUTOMATIC VOLTAGE CONTROL (T801)


342 TAP CHAGER INCOMPLETE TAP CHANGER INCOMPLETE
SDRA C2.A_T801 T801 TAP CHANGER INCOMPLETE

343 TAP CHANGER FAULTY TAP CHANGER INCOMPLETE


SDRA C2.A_T801 T801 TAP CHANGER DRIVE FAILURE
C2.A_T801 T801 OLTC PARALLEL OPERATION DISTURBED
C2.A_T801 T801 OLTC RAISE/LOWER LIMIT REACHED
C2.A_T801 T801 OLTC MOTOR CIRCUIT TRIPPED
C2.A_T801 T801 LOSS OF OLTC MOTOR SUPPLY
C2.A_T801 T801 OLTC OUT OF STEP
C2.A_T801 T801 AVR BLOCKED (O/V,O/C,U/V)
C2.A_T801 T801 RTCC CONTROL SUPPLY FAIL
C2.A_T801 T801 VOLTAGE CONTROL FAIL
C2.A_T801 T801 TAP CHANGE MOTOR FAIL
C2.A_T801 T801 AVR SUPPLY FAULTY
C2.A_T801 T801 TAP CHANGER OUT OF STEP

344 TAP CHANGER IN PROGRESS TAP CHANGER IN PROGRESS


SDRA C2.A_T801 T801 TAP CHANGER IN PROGRESS

345 TAP CHANGER DRIVE TRIP TAP CHANGER DRIVE TRIP


SDRA C2.A_T801 T801 TAP CHANGER DRIVE TRIP

346 RTCC INCOMPLETE RTCC INCOMPLETE


SDRA C2.A_T801 T801 RTCC INCOMPLETE

347 RTCC LOCAL / SUPERVISARY RTCC LOCAL / SUPERVISARY


SDRA C2.A_T801 T801 RTCC LOCAL / SUPERVISARY

348 RTCC AUTO/MANUAL RTCC AUTO/MANUAL


SDRA C2.A_T801 T801 RTCC AUTO/MANUAL

349 RTCC MASTER ON/OFF RTCC MASTER ON/OFF


SDRA C2.A_T801 T801 RTCC MASTER ON/OFF

350 PARALLEL/INDEPENDENT PARALLEL/INDEPENDENT


SDRA C2.A_T801 T801 PARALLEL/INDEPENDENT

AUTOMATIC VOLTAGE CONTROL (T802)


351 TAP CHAGER INCOMPLETE TAP CHANGER INCOMPLETE
SDRA C4.C_T802 T802 TAP CHANGER INCOMPLETE

352 TAP CHANGER FAULTY TAP CHANGER INCOMPLETE


SDRA C4.C_T802 T802 TAP CHANGER DRIVE FAILURE
C4.C_T802 T802 OLTC PARALLEL OPERATION DISTURBED
C4.C_T802 T802 OLTC RAISE/LOWER LIMIT REACHED
C4.C_T802 T802 OLTC MOTOR CIRCUIT TRIPPED
C4.C_T802 T802 LOSS OF OLTC MOTOR SUPPLY

29 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
C4.C_T802 T802 OLTC OUT OF STEP
C4.C_T802 T802 AVR BLOCKED (O/V,O/C,U/V)
C4.C_T802 T802 RTCC CONTROL SUPPLY FAIL
C4.C_T802 T802 VOLTAGE CONTROL FAIL
C4.C_T802 T802 TAP CHANGE MOTOR FAIL
C4.C_T802 T802 AVR SUPPLY FAULTY
C4.C_T802 T802 TAP CHANGER OUT OF STEP

353 TAP CHANGER IN PROGRESS TAP CHANGER IN PROGRESS


SDRA C4.C_T802 T802 TAP CHANGER IN PROGRESS

354 TAP CHANGER DRIVE TRIP TAP CHANGER DRIVE TRIP


SDRA C4.C_T802 T802 TAP CHANGER DRIVE TRIP

355 RTCC INCOMPLETE RTCC INCOMPLETE


SDRA C4.C_T802 T802 RTCC INCOMPLETE

356 RTCC LOCAL / SUPERVISARY RTCC LOCAL / SUPERVISARY


SDRA C4.C_T802 T802 RTCC LOCAL / SUPERVISARY

357 RTCC AUTO/MANUAL RTCC AUTO/MANUAL


SDRA C4.C_T802 T802 RTCC AUTO/MANUAL

358 RTCC MASTER ON/OFF RTCC MASTER ON/OFF


SDRA C4.C_T802 T802 RTCC MASTER ON/OFF

359 PARALLEL/INDEPENDENT PARALLEL/INDEPENDENT


SDRA C4.C_T802 T802 PARALLEL/INDEPENDENT

FUTURE AUTOMATIC VOLTAGE CONTROL (T803)


360 TAP CHAGER INCOMPLETE TAP CHANGER INCOMPLETE
SDRA C5.C_T803 T803 TAP CHANGER INCOMPLETE

361 TAP CHANGER FAULTY TAP CHANGER INCOMPLETE


SDRA C5.C_T803 T803 TAP CHANGER DRIVE FAILURE
C5.C_T803 T803 OLTC PARALLEL OPERATION DISTURBED
C5.C_T803 T803 OLTC RAISE/LOWER LIMIT REACHED
C5.C_T803 T803 OLTC MOTOR CIRCUIT TRIPPED
C5.C_T803 T803 LOSS OF OLTC MOTOR SUPPLY
C5.C_T803 T803 OLTC OUT OF STEP
C5.C_T803 T803 AVR BLOCKED (O/V,O/C,U/V)
C5.C_T803 T803 RTCC CONTROL SUPPLY FAIL
C5.C_T803 T803 VOLTAGE CONTROL FAIL
C5.C_T803 T803 TAP CHANGE MOTOR FAIL
C5.C_T803 T803 AVR SUPPLY FAULTY
C5.C_T803 T803 TAP CHANGER OUT OF STEP

362 TAP CHANGER IN PROGRESS TAP CHANGER IN PROGRESS


SDRA C5.C_T803 T803 TAP CHANGER IN PROGRESS

363 TAP CHANGER DRIVE TRIP TAP CHANGER DRIVE TRIP


SDRA C5.C_T803 T803 TAP CHANGER DRIVE TRIP

364 RTCC INCOMPLETE RTCC INCOMPLETE


SDRA C5.C_T803 T803 RTCC INCOMPLETE

365 RTCC LOCAL / SUPERVISARY RTCC LOCAL / SUPERVISARY


SDRA C5.C_T803 T803 RTCC LOCAL / SUPERVISARY

366 RTCC AUTO/MANUAL RTCC AUTO/MANUAL


SDRA C5.C_T803 T803 RTCC AUTO/MANUAL

367 RTCC MASTER ON/OFF RTCC MASTER ON/OFF


SDRA C5.C_T803 T803 RTCC MASTER ON/OFF

30 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
368 PARALLEL/INDEPENDENT PARALLEL/INDEPENDENT
SDRA C5.C_T803 T803 PARALLEL/INDEPENDENT

GROUNDING TRANSFORMER (301)


369 PHASE O/C PROTECTION OPERATED PHASE O/C PROTECTION OPERATED
SDRA GT301 GT301 PHASE O/C PROTECTION OPERATED

370 NEUTRAL O/C PROTECTION OPERATED NEUTRAL O/C PROTECTION OPERATED


SDRA GT301 GT301 NEUTRAL O/C PROTECTION OPERATED

371 BUCHOLZ STG-1 OPERATED BUCHOLZ STG-1 OPERATED


SDRA GT301 GT301 BUCHOLZ STG-1 OPERATED

372 BUCHOLZ STG-2 OPERATED BUCHOLZ STG-2 OPERATED


SDRA GT301 GT301 BUCHOLZ STG-2 OPERATED

373 PRESSURE RELIEF DEVICE OPERATED PRESSURE RELIEF DEVICE OPERATED


SDRA GT301 GT301 PRESSURE RELIEF DEVICE OPERATED

374 OIL LEVEL LOW OIL LEVEL LOW


SDRA GT301 GT301 OIL LEVEL LOW

GROUNDING TRANSFORMER (302)


375 PHASE O/C PROTECTION OPERATED PHASE O/C PROTECTION OPERATED
SDRA GT302 GT302 PHASE O/C PROTECTION OPERATED

376 NEUTRAL O/C PROTECTION OPERATED NEUTRAL O/C PROTECTION OPERATED


SDRA GT302 GT302 NEUTRAL O/C PROTECTION OPERATED

377 BUCHOLZ STG-1 OPERATED BUCHOLZ STG-1 OPERATED


SDRA GT302 GT302 BUCHOLZ STG-1 OPERATED

378 BUCHOLZ STG-2 OPERATED BUCHOLZ STG-2 OPERATED


SDRA GT302 GT302 BUCHOLZ STG-2 OPERATED

379 PRESSURE RELIEF DEVICE OPERATED PRESSURE RELIEF DEVICE OPERATED


SDRA GT302 GT302 PRESSURE RELIEF DEVICE OPERATED

380 OIL LEVEL LOW OIL LEVEL LOW


SDRA GT302 GT302 OIL LEVEL LOW

FUTURE GROUNDING TRANSFORMER (303)


381 PHASE O/C PROTECTION OPERATED PHASE O/C PROTECTION OPERATED
SDRA GT302 GT302 PHASE O/C PROTECTION OPERATED

382 NEUTRAL O/C PROTECTION OPERATED NEUTRAL O/C PROTECTION OPERATED


SDRA GT302 GT302 NEUTRAL O/C PROTECTION OPERATED

383 BUCHOLZ STG-1 OPERATED BUCHOLZ STG-1 OPERATED


SDRA GT302 GT302 BUCHOLZ STG-1 OPERATED

384 BUCHOLZ STG-2 OPERATED BUCHOLZ STG-2 OPERATED


SDRA GT302 GT302 BUCHOLZ STG-2 OPERATED

385 PRESSURE RELIEF DEVICE OPERATED PRESSURE RELIEF DEVICE OPERATED


SDRA GT302 GT302 PRESSURE RELIEF DEVICE OPERATED

386 OIL LEVEL LOW OIL LEVEL LOW


SDRA GT302 GT302 OIL LEVEL LOW

BBP MAIN-1 PROTECTION OPTD


387 BBP MAIN-1 PROTECTION OPERATE BBP MAIN-1 PROTECTION NORMAL OPERATE
SDRA BBP M1 BBP M1 A804 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A807 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A810 86B-M1 LOR OPTD

31 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA BBP M1 BBP M1 A813 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A806 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A809 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A812 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A815 86B-M1 LOR OPTD

388 BBP MAIN-2 PROTECTION OPERATE BBP MAIN-2 PROTECTION NORMAL OPERATE
SDRA BBP M2 BBP M2 A804 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A807 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A810 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A813 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A806 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A809 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A812 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A815 86B-M2 LOR OPTD

389 BBP MAIN-1 PROTECTION FAIL BB PROTECTION FAULTY FAULTY NORMAL


SDRA BBPM1/A804 BBP M1 74/86B-M1/A804 SUPV. OPTD
SDRA BBPM1/A804 BBP M1 BAY UNIT DC SUPPLY FAIL
SDRA BBPM1/A804 BBP M1 50BF/87BB RELAY FAIL
SDRA BBPM1/A804 BBP M1 BAY UNIT COMM. ERROR
SDRA BBPM1/A804 BBP M1 BBP MAIN-1 TRIP ISOLATED
SDRA BBPM1/A807 BBP M1 74/86B-M1/A807 SUPV. OPTD
SDRA BBPM1/A807 BBP M1 BAY UNIT DC SUPPLY FAIL
SDRA BBPM1/A807 BBP M1 50BF/87BB RELAY FAIL
SDRA BBPM1/A807 BBP M1 BAY UNIT COMM. ERROR
SDRA BBPM1/A807 BBP M1 BBP MAIN-1 TRIP ISOLATED
SDRA BBPM1/A810 BBP M1 74/86B-M1/A810 SUPV. OPTD
SDRA BBPM1/A810 BBP M1 BAY UNIT DC SUPPLY FAIL
SDRA BBPM1/A810 BBP M1 50BF/87BB RELAY FAIL
SDRA BBPM1/A810 BBP M1 BAY UNIT COMM. ERROR
SDRA BBPM1/A810 BBP M1 BBP MAIN-1 TRIP ISOLATED
SDRA BBPM1/A813 (FUTURE) BBP M1 74/86B-M1/A813 SUPV. OPTD
SDRA BBPM1/A813 (FUTURE) BBP M1 BAY UNIT DC SUPPLY FAIL
SDRA BBPM1/A813 (FUTURE) BBP M1 50BF/87BB RELAY FAIL
SDRA BBPM1/A813 (FUTURE) BBP M1 BAY UNIT COMM. ERROR
SDRA BBPM1/A813 (FUTURE) BBP M1 BBP MAIN-1 TRIP ISOLATED

390 BBP MAIN-2 PROTECTION FAIL BB PROTECTION FAULTY FAULTY NORMAL


SDRA BBPM2/A804 BB PM2 74/86B-M2/A804 SUPV. OPTD
SDRA BBPM2/A804 BB PM2 BAY UNIT DC SUPPLY FAIL
SDRA BBPM2/A804 BB PM2 50BF/87BB RELAY FAIL
SDRA BBPM2/A804 BB PM2 BAY UNIT COMM. ERROR
SDRA BBPM2/A804 BB PM2 BBP MAIN-2 TRIP ISOLATED
SDRA BBPM2/A807 BB PM2 74/86B-M2/A807 SUPV. OPTD
SDRA BBPM2/A807 BB PM2 BAY UNIT DC SUPPLY FAIL
SDRA BBPM2/A807 BB PM2 50BF/87BB RELAY FAIL
SDRA BBPM2/A807 BB PM2 BAY UNIT COMM. ERROR
SDRA BBPM2/A807 BB PM2 BBP MAIN-2 TRIP ISOLATED
SDRA BBPM2/A810 BB PM2 74/86B-M2/A810 SUPV. OPTD
SDRA BBPM2/A810 BB PM2 BAY UNIT DC SUPPLY FAIL
SDRA BBPM2/A810 BB PM2 50BF/87BB RELAY FAIL
SDRA BBPM2/A810 BB PM2 BAY UNIT COMM. ERROR
SDRA BBPM2/A810 BB PM2 BBP MAIN-2 TRIP ISOLATED
SDRA BBPM2/A813 (FUTURE) BB PM2 74/86B-M2/A813 SUPV. OPTD
SDRA BBPM2/A813 (FUTURE) BB PM2 BAY UNIT DC SUPPLY FAIL
SDRA BBPM2/A813 (FUTURE) BB PM2 50BF/87BB RELAY FAIL
SDRA BBPM2/A813 (FUTURE) BB PM2 BAY UNIT COMM. ERROR
SDRA BBPM2/A813 (FUTURE) BB PM2 BBP MAIN-2 TRIP ISOLATED

391 BBP CENTRAL UNIT OPERATED BB CENRAL UNIT FAULTY FAULTY OPERATE
SDRA F87_CU F87_CU BUS ZONE-1A OPERATED
SDRA F87_CU F87_CU BUS ZONE-2A OPERATED
SDRA F87_CU F87_CU BUS ZONE-1B OPERATED
SDRA F87_CU F87_CU BUS ZONE-2B OPERATED

32 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA F87_CU F87_CU BBP LOR OPERATED
SDRA F87_CU F87_CU CENTRAL UNIT POWER SUPPLY FAIL
SDRA F87_CU F87_CU 87CU RELAY FAIL
SDRA F87_CU F87_CU CENTRAL UNIT COMM. ERROR

BUS-1A & BUS1B SIGNALS

392 POSTION INDICATIONS


SDRA
BUS-1A D801 DISC D801 POSITION INDICATION D801 ISOLATOR OPEN CLOSE
SDRA
BUS-2A D802 DISC D802 POSITION INDICATION D802 ISOLATOR OPEN CLOSE
SDRA
BUS-1A K801 ESW K801 POSITION INDICATION K801 ISOLATOR OPEN CLOSE
SDRA
BUS-1B K802 ESW K802 POSITION INDICATION K802 ISOLATOR OPEN CLOSE
SDRA
BUS-2A K803 ESW K803 POSITION INDICATION K803 ISOLATOR OPEN CLOSE
SDRA
BUS-2B K804 ESW K804 POSITION INDICATION K804 ISOLATOR OPEN CLOSE
SDRA
BUS-1A BUS-1A BUS-1A VT ISOLATOR POSITION INDICATION BUS-1A VT ISOLATOR OPEN CLOSE
SDRA
BUS-1B BUS-1B BUS-1B VT ISOLATOR POSITION INDICATION BUS-1B VT ISOLATOR OPEN CLOSE
SDRA
BUS-2A BUS-2A BUS-2A VT ISOLATOR POSITION INDICATION BUS-2A VT ISOLATOR OPEN CLOSE
SDRA
BUS-2B BUS-2B BUS-2B VT ISOLATOR POSITION INDICATION BUS-2B VT ISOLATOR OPEN CLOSE
393 GIS BUS-1A SF6 GAS ALARM BUS-1A GIS SF6 ALARM NORMAL
SDRA
BUS-1A BUS-1A BUS-1A GIS SF6 GAS PRESSURE LOW STAGE-1
SDRA
BUS-1A BUS-1A BUS-1A GIS SF6 GAS PRESSURE HIGH
394 GIS BUS-1A SF6 STAGE-2 ALARM BUS-1A GIS SF6 2 ALARM NORMAL
SDRA
BUS-1A BUS-1A BUS-1A GIS SF6 GAS PRESSURE LOW STAGE-2
395 GIS BUS-1B SF6 GAS ALARM BUS-1B GIS SF6 ALARM NORMAL
SDRA
BUS-1B BUS-1B BUS-1B GIS SF6 GAS PRESSURE LOW STAGE-1
SDRA
BUS-1B BUS-1B BUS-1B GIS SF6 GAS PRESSURE HIGH
396 GIS BUS-1B SF6 STAGE-2 ALARM BUS-1B GIS SF6 2 ALARM NORMAL
SDRA
BUS-1B BUS-1B BUS-1B GIS SF6 GAS PRESSURE LOW STAGE-2
397 GIS BUS-2A SF6 GAS ALARM BUS-2A GIS SF6 ALARM NORMAL
SDRA
BUS-2A BUS-2A BUS-2A GIS SF6 GAS PRESSURE LOW STAGE-1
SDRA
BUS-2A BUS-2A BUS-2A GIS SF6 GAS PRESSURE HIGH
398 GIS BUS-2A SF6 STAGE-2 ALARM BUS-2A GIS SF6 2 ALARM NORMAL
SDRA
BUS-2A BUS-2A BUS-2A GIS SF6 GAS PRESSURE LOW STAGE-2
399 GIS BUS-2B SF6 GAS ALARM BUS-2B GIS SF6 ALARM NORMAL
SDRA
BUS-2B BUS-2B BUS-2B GIS SF6 GAS PRESSURE LOW STAGE-1
SDRA
BUS-2B BUS-2B BUS-2B GIS SF6 GAS PRESSURE HIGH
400 GIS BUS-2B SF6 STAGE-2 ALARM BUS-2B GIS SF6 2 ALARM NORMAL
SDRA
BUS-2B BUS-2B BUS-2B GIS SF6 GAS PRESSURE LOW STAGE-2
401 AC/DC SUPPLY FAIL BUS-1A&1B AC/DC SUPPLY FAIL FAILED NORMAL
SDRA
BUS-1 BUS-1 DS /ES CONTROL SUPPLY FAIL
SDRA
BUS-1 BUS-1 DS/ES MOTOR SUPPLY FAIL
SDRA
BUS-1A BUS-1A BUS 1A VT FFR OPTD
SDRA
BUS-1B BUS-1B BUS 1B VT FFR OPTD
SDRA
BUS-2A BUS-2A BUS 2A VT FFR OPTD
SDRA
BUS-2B BUS-2B BUS 2B VT FFR OPTD

33 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA
BUS-1A BUS-1A BUS 1A VT MCB FAILED
SDRA
BUS-1B BUS-1B BUS 1B VT MCB FAILED
SDRA
BUS-2A BUS-2A BUS 2A VT MCB FAILED
SDRA
BUS-2B BUS-2B BUS 2B VT MCB FAILED
402 SYNCHROCHECK FAIL BUS SYNC CHK FAULTY NORMAL
SDRA
BUS 7VK61 CB BUS SYNCHROCHECK FAIL

34.5kV SWGR (A401)

403 BAY CB A401 SIGNALS A401 AC/DC SP FAILED NORMAL


SDRA A401 CB A401 POSITION INDICATION A401 BREAKER OPEN CLOSE
SDRA K401 ESW K401 POSITION INDICATION K401 ISOLATOR OPEN CLOSE
SDRA K402 ESW K402 POSITION INDICATION K402 ISOLATOR OPEN CLOSE

404 AC/DC SUPPLY FAIL A401 AC/DC SP FAILED NORMAL


SDRA A1_REF615 A401 PANEL AC SUPPLY FAILED
SDRA A1_REF615 A401 PANEL DC SUPPLY FAILED

405 CONTROL SELECTOR SWITCH POS. A401 CONTROL SEL. OFF


SDRA A1_REF615 A401 BAY CONT. SEL. SWITCH LOCAL POSITTION LOCAL
SDRA A1_REF615 A401 BAY CONT. SEL. SWITCH REMOTE POSITTION REMOTE
SDRA A1_REF615 A401 BAY CONT. SEL. SWITCH BCU POSITTION BCU

406 13.8kV INCOMER CB NORMAL OFF


SDRA TRIP COIL LOCKOUT LOCAL
SDRA RELAY FAULTY REMOTE
SDRA SF6 DENSITY BCU

407 13.8kV INCOMER AC/DC SUPPLY FAIL OFF


SDRA 13.8kV INCOMER AC/DC SUPPLY FAIL LOCAL

408 CB RACK IN/OUT OFF


SDRA CB RACK IN/OUT LOCAL

13.8kV OUTGOING FEEDER (A301)

409 BAY CB A301 SIGNALS A301 AC/DC SP FAILED NORMAL


SDRA A301 CB A301 POSITION INDICATION A301 BREAKER OPEN CLOSE
SDRA K301 ESW K301 POSITION INDICATION K301 ISOLATOR OPEN CLOSE
SDRA K302 ESW K302 POSITION INDICATION K302 ISOLATOR OPEN CLOSE

410 AC/DC SUPPLY FAIL A301 AC/DC SP FAILED NORMAL


SDRA A1_REF615 A301 PANEL AC SUPPLY FAILED
SDRA A1_REF615 A301 PANEL DC SUPPLY FAILED

411 CONTROL SELECTOR SWITCH POS. A301 CONTROL SEL. OFF


SDRA A1_REF615 A301 BAY CONT. SEL. SWITCH LOCAL POSITTION LOCAL
SDRA A1_REF615 A301 BAY CONT. SEL. SWITCH REMOTE POSITTION REMOTE
SDRA A1_REF615 A301 BAY CONT. SEL. SWITCH BCU POSITTION BCU

412 13.8kV INCOMER CB NORMAL OFF


SDRA TRIP COIL LOCKOUT LOCAL

34 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA RELAY FAULTY REMOTE
SDRA SF6 DENSITY BCU

413 13.8kV INCOMER AC/DC SUPPLY FAIL OFF


SDRA 13.8kV INCOMER AC/DC SUPPLY FAIL LOCAL

414 CB RACK IN/OUT OFF


SDRA CB RACK IN/OUT LOCAL
SDRA A302 PANEL DC SUPPLY FAILED

13.8kV OUTGOING FEEDER (A302)

415 BAY CB A302 SIGNALS A302 AC/DC SP FAILED NORMAL


SDRA A302 CB A302 POSITION INDICATION A302 BREAKER OPEN CLOSE
SDRA K301 ESW K303 POSITION INDICATION K301 ISOLATOR OPEN CLOSE
SDRA K302 ESW K304 POSITION INDICATION K302 ISOLATOR OPEN CLOSE

416 AC/DC SUPPLY FAIL A302 AC/DC SP FAILED NORMAL


SDRA A1_REF615 A302 PANEL AC SUPPLY FAILED
SDRA A1_REF615 A302 PANEL DC SUPPLY FAILED

417 CONTROL SELECTOR SWITCH POS. A302 CONTROL SEL. OFF


SDRA A1_REF615 A302 BAY CONT. SEL. SWITCH LOCAL POSITTION LOCAL
SDRA A1_REF615 A302 BAY CONT. SEL. SWITCH REMOTE POSITTION REMOTE
SDRA A1_REF615 A302 BAY CONT. SEL. SWITCH BCU POSITTION BCU

418 13.8kV INCOMER CB NORMAL OFF


SDRA TRIP COIL LOCKOUT LOCAL
SDRA RELAY FAULTY REMOTE
SDRA SF6 DENSITY BCU

419 13.8kV INCOMER AC/DC SUPPLY FAIL OFF


SDRA 13.8kV INCOMER AC/DC SUPPLY FAIL LOCAL

420 CB RACK IN/OUT OFF


SDRA CB RACK IN/OUT LOCAL
SDRA A302 PANEL DC SUPPLY FAILED

GENERAL POINTS

421 125 BATTERIES (BATTERY-1) FAULTY

125 BATTERIES (BATTERY-1) FAULTY NORMAL


422 125 BATTERIES (BATTERY-2) FAULTY

125 BATTERIES (BATTERY-2) FAULTY NORMAL


423 48V DC SYSTEM GROUND

48V DC SYSTEM GROUND NORMAL


424 48V BATTERIES FAULTY

48V BATTERIES FAULTY NORMAL


425 DC SYSTEM GROUND

DC SYSTEM GROUND NORMAL


426 SMOKE DETECTOR OPERATED

35 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SMOKE DETECTOR OPERATED NORMAL
427 SMOKE DETECTOR OPERATED

SMOKE DETECTOR OPERATED NORMAL


428 ROOM TEMPERATURE HIGH

ROOM TEMPERATURE HIGH NORMAL


429 RTU POWER SUPPLY FAILED

RTU POWER SUPPLY FAILED NORMAL


430 FIRE SYSTEM FAULTY

FIRE SYSTEM FAULTY NORMAL


431 FIRE SYSTEM OPERATED

FIRE SYSTEM OPERATED NORMAL


432 S/S AUX. SUPPLY FAILED

S/S AUX. SUPPLY FAILED NORMAL


433 MAIN DC SUPPLY FAILED

MAIN DC SUPPLY FAILED NORMAL


434 ALARM SYSTEM FAULTY

ALARM SYSTEM FAULTY NORMAL


435 HVAC SYSTEM MAIN FAULTY

HVAC SYSTEM MAIN FAULTY NORMAL


436 HVAC SYSTEM BACK-UP FAULTY

HVAC SYSTEM BACK-UP FAULTY NORMAL

36 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
BAY C2 JUBL LINE-1 MEASUREMENTS

1 SDRA LINE CT 7SD522-M1 CURRENT L1


2 SDRA LINE CT 7SD522-M1 CURRENT L2
3 SDRA LINE CT 7SD522-M1 CURRENT L3
4 SDRA LINE VT 7SD522-M1 VOLTAGE L12
5 SDRA LINE VT 7SD522-M1 VOLTAGE L23
6 SDRA LINE VT 7SD522-M1 VOLTAGE L31
7 SDRA LINE VT 7SD522-M1 CURRENT LN
8 SDRA LINE VT 7SD522-M1 VOLTAGE LN
9 SDRA LINE VT 7SD522-M1 ACTIVE POWER (P)
10 SDRA LINE VT 7SD522-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7SD522-M1 BUS VT VOLTAGE YN
1 SDRA LINE CT P546-M2 CURRENT L1
2 SDRA LINE CT P546-M2 CURRENT L2
3 SDRA LINE CT P546-M2 CURRENT L3
4 SDRA LINE VT P546-M2 VOLTAGE L12
5 SDRA LINE VT P546-M2 VOLTAGE L23
6 SDRA LINE VT P546-M2 VOLTAGE L31
7 SDRA LINE VT P546-M2 CURRENT LN
8 SDRA LINE VT P546-M2 VOLTAGE LN
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C3 JUBL LINE-2 MEASUREMENTS

1 SDRA LINE CT 7SD522-M1 CURRENT L1


2 SDRA LINE CT 7SD522-M1 CURRENT L2
3 SDRA LINE CT 7SD522-M1 CURRENT L3
4 SDRA LINE VT 7SD522-M1 VOLTAGE L12
5 SDRA LINE VT 7SD522-M1 VOLTAGE L23
6 SDRA LINE VT 7SD522-M1 VOLTAGE L31
7 SDRA LINE VT 7SD522-M1 CURRENT LN
8 SDRA LINE VT 7SD522-M1 VOLTAGE LN
9 SDRA LINE VT 7SD522-M1 ACTIVE POWER (P)

37 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
10 SDRA LINE VT 7SD522-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7SD522-M1 BUS VT VOLTAGE YN
1 SDRA LINE CT P546-M2 CURRENT L1
2 SDRA LINE CT P546-M2 CURRENT L2
3 SDRA LINE CT P546-M2 CURRENT L3
4 SDRA LINE VT P546-M2 VOLTAGE L12
5 SDRA LINE VT P546-M2 VOLTAGE L23
6 SDRA LINE VT P546-M2 VOLTAGE L31
7 SDRA LINE VT P546-M2 CURRENT LN
8 SDRA LINE VT P546-M2 VOLTAGE LN
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C3 JUBL COMMUNITY2 LINE-2 MEASUREMENTS

1 SDRA LINE CT 7SD522-M1 CURRENT L1


2 SDRA LINE CT 7SD522-M1 CURRENT L2
3 SDRA LINE CT 7SD522-M1 CURRENT L3
4 SDRA LINE VT 7SD522-M1 VOLTAGE L12
5 SDRA LINE VT 7SD522-M1 VOLTAGE L23
6 SDRA LINE VT 7SD522-M1 VOLTAGE L31
7 SDRA LINE VT 7SD522-M1 CURRENT LN
8 SDRA LINE VT 7SD522-M1 VOLTAGE LN
9 SDRA LINE VT 7SD522-M1 ACTIVE POWER (P)
10 SDRA LINE VT 7SD522-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7SD522-M1 BUS VT VOLTAGE YN
1 SDRA LINE CT P546-M2 CURRENT L1
2 SDRA LINE CT P546-M2 CURRENT L2
3 SDRA LINE CT P546-M2 CURRENT L3
4 SDRA LINE VT P546-M2 VOLTAGE L12
5 SDRA LINE VT P546-M2 VOLTAGE L23
6 SDRA LINE VT P546-M2 VOLTAGE L31
7 SDRA LINE VT P546-M2 CURRENT LN
8 SDRA LINE VT P546-M2 VOLTAGE LN

38 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C4 JUBL COMMUNITY2 LINE-1 MEASUREMENTS

1 SDRA LINE CT 7SD522-M1 CURRENT L1


2 SDRA LINE CT 7SD522-M1 CURRENT L2
3 SDRA LINE CT 7SD522-M1 CURRENT L3
4 SDRA LINE VT 7SD522-M1 VOLTAGE L12
5 SDRA LINE VT 7SD522-M1 VOLTAGE L23
6 SDRA LINE VT 7SD522-M1 VOLTAGE L31
7 SDRA LINE VT 7SD522-M1 CURRENT LN
8 SDRA LINE VT 7SD522-M1 VOLTAGE LN
9 SDRA LINE VT 7SD522-M1 ACTIVE POWER (P)
10 SDRA LINE VT 7SD522-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7SD522-M1 BUS VT VOLTAGE YN
1 SDRA LINE CT P546-M2 CURRENT L1
2 SDRA LINE CT P546-M2 CURRENT L2
3 SDRA LINE CT P546-M2 CURRENT L3
4 SDRA LINE VT P546-M2 VOLTAGE L12
5 SDRA LINE VT P546-M2 VOLTAGE L23
6 SDRA LINE VT P546-M2 VOLTAGE L31
7 SDRA LINE VT P546-M2 CURRENT LN
8 SDRA LINE VT P546-M2 VOLTAGE LN
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C2 T801 TRANSFORMER MEASUREMENTS

1 SDRA XFER CT 7UT635-M1 CURRENT L1


2 SDRA XFER CT 7UT635-M1 CURRENT L2
3 SDRA XFER CT 7UT635-M1 CURRENT L3
4 SDRA XFER VT 7UT635-M1 VOLTAGE L12
5 SDRA XFER VT 7UT635-M1 VOLTAGE L23
6 SDRA XFER VT 7UT635-M1 VOLTAGE L31

39 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
7 SDRA XFER VT 7UT635-M1 CURRENT LN
8 SDRA XFER VT 7UT635-M1 VOLTAGE LN
9 SDRA XFER VT 7UT635-M1 ACTIVE POWER (P)
10 SDRA XFER VT 7UT635-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7UT635-M1 BUS VT VOLTAGE YN
1 SDRA XFER CT RET670-M2 CURRENT L1
2 SDRA XFER CT RET670-M2 CURRENT L2
3 SDRA XFER CT RET670-M2 CURRENT L3
4 SDRA XFER VT RET670-M2 VOLTAGE L12
5 SDRA XFER VT RET670-M2 VOLTAGE L23
6 SDRA XFER VT RET670-M2 VOLTAGE L31
7 SDRA XFER VT RET670-M2 CURRENT LN
8 SDRA XFER VT RET670-M2 VOLTAGE LN
9 SDRA XFER VT RET670-M2 ACTIVE POWER (P)
10 SDRA XFER VT RET670-M2 REACTIVE POWER (Q)
11 SDRA BUS VT RET670-M2 BUS VT VOLTAGE YN
BAY C3 T802 TRANSFORMER MEASUREMENTS

1 SDRA XFER CT 7UT635-M1 CURRENT L1


2 SDRA XFER CT 7UT635-M1 CURRENT L2
3 SDRA XFER CT 7UT635-M1 CURRENT L3
4 SDRA XFER VT 7UT635-M1 VOLTAGE L12
5 SDRA XFER VT 7UT635-M1 VOLTAGE L23
6 SDRA XFER VT 7UT635-M1 VOLTAGE L31
7 SDRA XFER VT 7UT635-M1 CURRENT LN
8 SDRA XFER VT 7UT635-M1 VOLTAGE LN
9 SDRA XFER VT 7UT635-M1 ACTIVE POWER (P)
10 SDRA XFER VT 7UT635-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7UT635-M1 BUS VT VOLTAGE YN
1 SDRA XFER CT RET670-M2 CURRENT L1
2 SDRA XFER CT RET670-M2 CURRENT L2
3 SDRA XFER CT RET670-M2 CURRENT L3
4 SDRA XFER VT RET670-M2 VOLTAGE L12
5 SDRA XFER VT RET670-M2 VOLTAGE L23

40 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
6 SDRA XFER VT RET670-M2 VOLTAGE L31
7 SDRA XFER VT RET670-M2 CURRENT LN
8 SDRA XFER VT RET670-M2 VOLTAGE LN
9 SDRA XFER VT RET670-M2 ACTIVE POWER (P)
10 SDRA XFER VT RET670-M2 REACTIVE POWER (Q)
11 SDRA BUS VT RET670-M2 BUS VT VOLTAGE YN
BAY C3 T803 FUTURE TRANSFORMER MEASUREMENTS

1 SDRA XFER CT 7UT635-M1 CURRENT L1


2 SDRA XFER CT 7UT635-M1 CURRENT L2
3 SDRA XFER CT 7UT635-M1 CURRENT L3
4 SDRA XFER VT 7UT635-M1 VOLTAGE L12
5 SDRA XFER VT 7UT635-M1 VOLTAGE L23
6 SDRA XFER VT 7UT635-M1 VOLTAGE L31
7 SDRA XFER VT 7UT635-M1 CURRENT LN
8 SDRA XFER VT 7UT635-M1 VOLTAGE LN
9 SDRA XFER VT 7UT635-M1 ACTIVE POWER (P)
10 SDRA XFER VT 7UT635-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7UT635-M1 BUS VT VOLTAGE YN
1 SDRA XFER CT RET670-M2 CURRENT L1
2 SDRA XFER CT RET670-M2 CURRENT L2
3 SDRA XFER CT RET670-M2 CURRENT L3
4 SDRA XFER VT RET670-M2 VOLTAGE L12
5 SDRA XFER VT RET670-M2 VOLTAGE L23
6 SDRA XFER VT RET670-M2 VOLTAGE L31
7 SDRA XFER VT RET670-M2 CURRENT LN
8 SDRA XFER VT RET670-M2 VOLTAGE LN
9 SDRA XFER VT RET670-M2 ACTIVE POWER (P)
10 SDRA XFER VT RET670-M2 REACTIVE POWER (Q)
11 SDRA BUS VT RET670-M2 BUS VT VOLTAGE YN
380kV BUS MEASUREMENTS

1 SDRA BUS 1A CT 7SS522 CURRENT L1


2 SDRA BUS 1A CT 7SS522 CURRENT L2
3 SDRA BUS 1A CT 7SS522 CURRENT L3

41 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS

IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
4 SDRA BUS 1A CT 7SS522 CURRENT LN
5 SDRA BUS 1A VT 7SS522 VOLTAGE L12
6 SDRA BUS 1A VT 7SS522 VOLTAGE L23
7 SDRA BUS 1A VT 7SS522 VOLTAGE L31
8 SDRA BUS 1A VT 7SS522 VOLTAGE LN
9 SDRA BUS 1B CT 7SS522 CURRENT L1
10 SDRA BUS 1B CT 7SS522 CURRENT L2
11 SDRA BUS 1B CT 7SS522 CURRENT L3
12 SDRA BUS 1B CT 7SS522 CURRENT LN
13 SDRA BUS 1B VT 7SS522 VOLTAGE L12
14 SDRA BUS 1B VT 7SS522 VOLTAGE L23
15 SDRA BUS 1B VT 7SS522 VOLTAGE L31
16 SDRA BUS 1B VT 7SS522 VOLTAGE LN