SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
1 SDRA BS1 D801 DISC D801 COMMAND EXECUTE CLOSE / OPEN D801ISOLATOR OFF ON
2 SDRA BS1 K801 ESWS K801 COMMAND EXECUTE CLOSE / OPEN K816 EARTHSWITCH OFF ON
3 SDRA BS1 K802 ESWS K802 COMMAND EXECUTE CLOSE / OPEN K817 EARTHSWITCH OFF ON
4 SDRA BS1 PROTECTION IN/OUT IN/OUT OFF ON
2 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
BAY C3.A COMMANDS
30 SDRA A807_C3.A A807 CB A807 COMMAND EXECUTE CLOSE / OPEN A807 BREAKER OFF ON
31 SDRA A807_C3.A D819 DISC D819 COMMAND EXECUTE CLOSE / OPEN D819 ISOLATOR OFF ON
32 SDRA A807_C3.A D820 DISC D820 COMMAND EXECUTE CLOSE / OPEN D820 ISOLATOR OFF ON
33 SDRA A807_C3.A D825 DISC D825 COMMAND EXECUTE CLOSE / OPEN D825 ISOLATOR OFF ON
34 SDRA A807_C3.A K825 ESWS K825 COMMAND EXECUTE CLOSE / OPEN K825 EARTHSWITCH OFF ON
35 SDRA A807_C3.A K826 ESWS K826 COMMAND EXECUTE CLOSE / OPEN K826 EARTHSWITCH OFF ON
36 SDRA A807_C3.A K820 ESWS K820 COMMAND EXECUTE CLOSE / OPEN K820 EARTHSWITCH OFF ON
37 SDRA A807_C3.A PROTECTION IN/OUT IN/OUT OFF ON
3 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
BAY C4.C COMMANDS
65 SDRA A812_C4.C A812 CB A812 COMMAND EXECUTE CLOSE / OPEN A812 BREAKER OFF ON
66 SDRA A812_C4.C D831 DISC D831 COMMAND EXECUTE CLOSE / OPEN D831 ISOLATOR OFF ON
67 SDRA A812_C4.C D832 DISC D832 COMMAND EXECUTE CLOSE / OPEN D828 ISOLATOR OFF ON
68 SDRA A812_C4.C D834 DISC D834 COMMAND EXECUTE CLOSE / OPEN D834 ISOLATOR OFF ON
69 SDRA A812_C4.C K841 ESWS K841 COMMAND EXECUTE CLOSE / OPEN K841 EARTHSWITCH OFF ON
70 SDRA A812_C4.C K842 ESWS K842 COMMAND EXECUTE CLOSE / OPEN K842 EARTHSWITCH OFF ON
71 SDRA A812_C4.C K840 ESWS K840 COMMAND EXECUTE CLOSE / OPEN K840 EARTHSWITCH OFF ON
72 SDRA A812_C4.C PROTECTION IN/OUT IN/OUT OFF ON
4 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device GROUP
S.No IED Name Name Name Name SCADA Text SCADA Text Bit status=01 Bit status=10 Address
AUTOMATIC VOLTAGE CONTROL (T802)
99 SDRA A812_C4.C TAPCON 260 T802 AVR TAP RAISE/LOWER T802 AVR RAISE LOWER
100 SDRA A812_C4.C TAPCON 260 T802 AVR AUTO/MANUAL T802 AVR AUTO MANUAL
101 SDRA A812_C4.C TAPCON 260 T802 AVR MASTER/FOLLOWER T802 AVR MASTER FOLLOWER
102 SDRA A812_C4.C TAPCON 260 T802 AVRSINGLE/PARALLEL T802 AVR SINGLE PARALLEL
5 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
BAY C2 - SIGNALS
1 POSTION INDICATIONS
SDRA C2.A_T801 A804 CB A804 POSITION INDICATION A804 BREAKER OPEN CLOSE
SDRA C2.B A805 CB A805 POSITION INDICATION A805 BREAKER OPEN CLOSE
SDRA C2.C_JUBL LINE-1 A806 CB A806 POSITION INDICATION A806 BREAKER OPEN CLOSE
SDRA C2 D811 DISC D811 POSITION INDICATION D811 ISOLATOR OPEN CLOSE
SDRA C2 D812 DISC D812 POSITION INDICATION D812 ISOLATOR OPEN CLOSE
SDRA C2 D817 DISC D817 POSITION INDICATION D817 ISOLATOR OPEN CLOSE
SDRA C2 D813 DISC D813 POSITION INDICATION D813 ISOLATOR OPEN CLOSE
SDRA C2 D814 DISC D814 POSITION INDICATION D814 ISOLATOR OPEN CLOSE
SDRA C2 D815 DISC D815 POSITION INDICATION D815 ISOLATOR OPEN CLOSE
SDRA C2 D816 DISC D816 POSITION INDICATION D816 ISOLATOR OPEN CLOSE
SDRA C2 D818 DISC D818 POSITION INDICATION D818 ISOLATOR OPEN CLOSE
SDRA C2 K815 ESW K815 POSITION INDICATION K815 ISOLATOR OPEN CLOSE
SDRA C2 K816 ESW K816 POSITION INDICATION K816 ISOLATOR OPEN CLOSE
SDRA C2 K817 ESW K817 POSITION INDICATION K817 ISOLATOR OPEN CLOSE
SDRA C2 K823 ESW K823 POSITION INDICATION K823 ISOLATOR OPEN CLOSE
SDRA C2 K818 ESW K818 POSITION INDICATION K818 ISOLATOR OPEN CLOSE
SDRA C2 K819 ESW K819 POSITION INDICATION K819 ISOLATOR OPEN CLOSE
SDRA C2 K820 ESW K820 POSITION INDICATION K820 ISOLATOR OPEN CLOSE
SDRA C2 K824 ESW K824 POSITION INDICATION K824 ISOLATOR OPEN CLOSE
SDRA C2 K821 ESW K821 POSITION INDICATION K821 ISOLATOR OPEN CLOSE
SDRA C2 K822 ESW K822 POSITION INDICATION K822 ISOLATOR OPEN CLOSE
SDRA C2 K823 ESW K823 POSITION INDICATION K823 ISOLATOR OPEN CLOSE
C2 VT805 T801 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
C2 VT806 JUBL LINE1 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
BAY C3 - SIGNALS
2 POSTION INDICATIONS
SDRA C3.A A807 CB A807 POSITION INDICATION A807 BREAKER OPEN CLOSE
SDRA C3.B A808 CB A808 POSITION INDICATION A808 BREAKER OPEN CLOSE
SDRA C3.C A809 CB A809 POSITION INDICATION A809 BREAKER OPEN CLOSE
SDRA C3 D819 DISC D819 POSITION INDICATION D819 ISOLATOR OPEN CLOSE
SDRA C3 D820 DISC D820 POSITION INDICATION D820 ISOLATOR OPEN CLOSE
SDRA C3 D825 DISC D825 POSITION INDICATION D825 ISOLATOR OPEN CLOSE
SDRA C3 D821 DISC D821 POSITION INDICATION D821 ISOLATOR OPEN CLOSE
SDRA C3 D822 DISC D822 POSITION INDICATION D822 ISOLATOR OPEN CLOSE
SDRA C3 D823 DISC D823 POSITION INDICATION D823 ISOLATOR OPEN CLOSE
SDRA C3 D824 DISC D824 POSITION INDICATION D824 ISOLATOR OPEN CLOSE
SDRA C3 D826 DISC D826 POSITION INDICATION D826 ISOLATOR OPEN CLOSE
SDRA C3 K825 ESW K825 POSITION INDICATION K825 ISOLATOR OPEN CLOSE
SDRA C3 K826 ESW K826 POSITION INDICATION K826 ISOLATOR OPEN CLOSE
SDRA C3 K827 ESW K827 POSITION INDICATION K827 ISOLATOR OPEN CLOSE
SDRA C3 K833 ESW K833 POSITION INDICATION K833 ISOLATOR OPEN CLOSE
SDRA C3 K828 ESW K828 POSITION INDICATION K828 ISOLATOR OPEN CLOSE
SDRA C3 K829 ESW K829 POSITION INDICATION K829 ISOLATOR OPEN CLOSE
SDRA C3 K831 ESW K831 POSITION INDICATION K831 ISOLATOR OPEN CLOSE
SDRA C3 K832 ESW K832 POSITION INDICATION K832 ISOLATOR OPEN CLOSE
SDRA C3 K830 ESW K830 POSITION INDICATION K830 ISOLATOR OPEN CLOSE
SDRA C3 K834 ESW K834 POSITION INDICATION K834 ISOLATOR OPEN CLOSE
SDRA C3 VT807 JUBL LINE 2 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
SDRA C3 VT808 JUBL COMMUNITY2 LINE2 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
BAY C4 - SIGNALS
3 POSTION INDICATIONS
SDRA C4.A A810 CB A810 POSITION INDICATION A810 BREAKER OPEN CLOSE
SDRA C4.B A811 CB A811 POSITION INDICATION A811 BREAKER OPEN CLOSE
SDRA C4.C A812 CB A812 POSITION INDICATION A812 BREAKER OPEN CLOSE
SDRA C4 D827 DISC D827 POSITION INDICATION D827 ISOLATOR OPEN CLOSE
SDRA C4 D828 DISC D828 POSITION INDICATION D828 ISOLATOR OPEN CLOSE
SDRA C4 D833 DISC D833 POSITION INDICATION D833 ISOLATOR OPEN CLOSE
SDRA C4 D829 DISC D829 POSITION INDICATION D829 ISOLATOR OPEN CLOSE
SDRA C4 D830 DISC D830 POSITION INDICATION D830 ISOLATOR OPEN CLOSE
SDRA C4 D831 DISC D831 POSITION INDICATION D831 ISOLATOR OPEN CLOSE
SDRA C4 D832 DISC D832 POSITION INDICATION D832 ISOLATOR OPEN CLOSE
6 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4 D834 DISC D834 POSITION INDICATION D834 ISOLATOR OPEN CLOSE
7 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4 K835 ESW K835 POSITION INDICATION K835 ISOLATOR OPEN CLOSE
SDRA C4 K836 ESW K836 POSITION INDICATION K836 ISOLATOR OPEN CLOSE
SDRA C4 K837 ESW K837 POSITION INDICATION K837 ISOLATOR OPEN CLOSE
SDRA C4 K843 ESW K843 POSITION INDICATION K843 ISOLATOR OPEN CLOSE
SDRA C4 K838 ESW K838 POSITION INDICATION K838 ISOLATOR OPEN CLOSE
SDRA C4 K839 ESW K839 POSITION INDICATION K839 ISOLATOR OPEN CLOSE
SDRA C4 K841 ESW K841 POSITION INDICATION K841 ISOLATOR OPEN CLOSE
SDRA C4 K842 ESW K842 POSITION INDICATION K842 ISOLATOR OPEN CLOSE
SDRA C4 K840 ESW K840 POSITION INDICATION K840 ISOLATOR OPEN CLOSE
SDRA C4 K837 ESW K844 POSITION INDICATION K844 ISOLATOR OPEN CLOSE
SDRA C4 VT809 JUBL COMMUNITY2 LINE 1 FEEDER VT ISOLATYOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
SDRA C4 VT810 T802 FEEDER VT ISOLATOR POSITION INDICATION VT ISOLATOR OPEN CLOSE
BUS
5 POSTION INDICATIONS
SDRA BUS A D801 CB D801 POSITION INDICATION D801 BREAKER OPEN CLOSE
SDRA BUS B D802 CB D802 POSITION INDICATION D802 BREAKER OPEN CLOSE
SDRA BUS-1A K801 ESW K801 POSITION INDICATION K801 BREAKER OPEN CLOSE
SDRA BUS-1B K802 ESW K802 POSITION INDICATION K802 ISOLATOR OPEN CLOSE
SDRA BUS-2A K803 ESW K803 POSITION INDICATION K803 ISOLATOR OPEN CLOSE
SDRA BUS-2B K804 ESW K804 POSITION INDICATION K804 ISOLATOR OPEN CLOSE
8 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C2.A_T801 A804 CB A804 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C2.A_T801 A804 CB A804 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED
8 CIRCUIT BREAKER GAS PRESSURE LOW A804 GAS PRESSURE LOW ALARM NORMAL
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 2
9 GIS GAS DENSITY ALARM A804 GAS DESITY ALARM ALARM NORMAL
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C2.A_T801 A804 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C2.A_T801 A804 GIS GAS PRESSURE HIGH
10 BAY CONTROL SUPPLY FAIL A804 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C2.A_T801 A804 CB A804 OPERATING MECH. SUPPLY FAIL
SDRA C2.A_T801 A804 CB A804 CONTROL SUPPLY DC FAIL
SDRA C2.A_T801 A804 CB A804 MOTOR SUPPLY AC FAIL
SDRA C2.A_T801 A804 DS/ES CONTROL SUPPLY FAIL
SDRA C2.A_T801 A804 DS/ES MOTOR SUPPLY FAIL
SDRA C2.A_T801 A804 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C2.A_T801 A804 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
12 CIRCUIT BREAKER POLE DISCREPANCY A804 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C2.A_T801 A804 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C2.A_T801 A804 POLE DISCREPANCY RELAY OPERATED STAGE-2
89 GIS GAS DENSITY ALARM A809 GAS DESITY ALARM ALARM NORMAL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 GIS GAS PRESSURE HIGH
90 BAY CONTROL SUPPLY FAIL A809 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 OPERATING MECH. SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 CONTROL SUPPLY DC FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB A809 MOTOR SUPPLY AC FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 DS/ES CONTROL SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 DS/ES MOTOR SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
9 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY OPERATED STAGE-1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY OPERATED STAGE-2
92 CIRCUIT BREAKER POLE DISCREPANCY A809 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C3.A_JUBL COMMUNITY2 LINE-2 A809 POLE DISCREPANCY RELAY OPERATED STAGE-2
104 CIRCUIT BREAKER GAS PRESSURE LOW A810 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 2
105 GIS GAS DENSITY ALARM A810 GAS DESITY ALARM ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB SF6 GAS PRESSURE LOW STAGE 2
10 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 GIS GAS PRESSURE HIGH
106 BAY CONTROL SUPPLY FAIL A810 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 OPERATING MECH. SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 CONTROL SUPPLY DC FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB A810 MOTOR SUPPLY AC FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 DS/ES CONTROL SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 DS/ES MOTOR SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
108 CIRCUIT BREAKER POLE DISCREPANCY A810 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 POLE DISCREPANCY RELAY OPERATED STAGE-2
111 CBF PROTECTION OPERATED A810 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 50BF CBF FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 BAY UNIT COMM. ERROR
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 CBF 86BF-2 TRIP RELAY FAULTY
112 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF LOCAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH LOCAL
113 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF REMOTE
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH REMOTE
114 CONTROL SELECTOR SWITCH POS. A810 CONTROL SEL. OFF BCU
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 BAY CONTROL SELECTOR SWITCH BCU
115 GIS SF6 STAGE-2 ALARM A810 GIS SF6 2 ALARM NORMAL
SDRA C4.A_JUBL COMMUNITY2 LINE-1 A810 A810 GIS SF6 GAS Pressure Low Stage-2
11 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.B A811 A811 BAY DS/ES MOTOR SUPPLY FAIL
SDRA C4.B A811 A811 BAY DS/ES CONTROL SUPPLY FAIL
120 CIRCUIT BREAKER GAS PRESSURE LOW A811 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 2
121 GIS GAS DENSITY ALARM A811 GAS DESITY ALARM ALARM NORMAL
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.B A811 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C4.B A811 GIS GAS PRESSURE HIGH
122 BAY CONTROL SUPPLY FAIL A811 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.B A811 CB A811 OPERATING MECH. SUPPLY FAIL
SDRA C4.B A811 CB A811 CONTROL SUPPLY DC FAIL
SDRA C4.B A811 CB A811 MOTOR SUPPLY AC FAIL
SDRA C4.B A811 DS/ES CONTROL SUPPLY FAIL
SDRA C4.B A811 DS/ES MOTOR SUPPLY FAIL
SDRA C4.B A811 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.B A811 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
124 CIRCUIT BREAKER POLE DISCREPANCY A811 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.B A811 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.B A811 POLE DISCREPANCY RELAY OPERATED STAGE-2
127 CBF PROTECTION OPERATED A811 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.B A811 50BF CBF FAULTY
SDRA C4.B A811 BAY UNIT COMM. ERROR
SDRA C4.B A811 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C4.B A811 CBF 86BF-2 TRIP RELAY FAULTY
128 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF LOCAL
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH LOCAL
129 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF REMOTE
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH REMOTE
130 CONTROL SELECTOR SWITCH POS. A811 CONTROL SEL. OFF BCU
SDRA C4.B A811 A811 BAY CONTROL SELECTOR SWITCH BCU
131 GIS SF6 STAGE-2 ALARM A811 GIS SF6 2 ALARM NORMAL
SDRA C4.B A811 A811 GIS SF6 GAS Pressure Low Stage-2
12 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
133 INTERLOCK BYPASS A811 INTL BYPASS ON OFF
SDRA C4.B A811 CB SECTION A811 INTERLOCK BYPASS
136 CIRCUIT BREAKER GAS PRESSURE LOW A812 GAS PRESSURE LOW ALARM NORMAL
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 2
137 GIS GAS DENSITY ALARM A812 GAS DESITY ALARM ALARM NORMAL
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C4.C_T802 A812 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C4.C_T802 A812 GIS GAS PRESSURE HIGH
138 BAY CONTROL SUPPLY FAIL A812 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C4.C_T802 A812 CB A812 OPERATING MECH. SUPPLY FAIL
SDRA C4.C_T802 A812 CB A812 CONTROL SUPPLY DC FAIL
SDRA C4.C_T802 A812 CB A812 MOTOR SUPPLY AC FAIL
SDRA C4.C_T802 A812 DS/ES CONTROL SUPPLY FAIL
SDRA C4.C_T802 A812 DS/ES MOTOR SUPPLY FAIL
SDRA C4.C_T802 A812 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C4.C_T802 A812 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
140 CIRCUIT BREAKER POLE DISCREPANCY A812 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C4.C_T802 A812 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C4.C_T802 A812 POLE DISCREPANCY RELAY OPERATED STAGE-2
143 CBF PROTECTION OPERATED A812 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C4.C_T802 A812 50BF CBF FAULTY
SDRA C4.C_T802 A812 BAY UNIT COMM. ERROR
SDRA C4.C_T802 A812 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C4.C_T802 A812 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C4.C_T802 A812 CBF 94BF-2 TRIP RELAY FAULTY
13 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.C_T802 A812 CBF 86BF-2 TRIP RELAY FAULTY
144 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF LOCAL
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH LOCAL
145 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF REMOTE
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH REMOTE
146 CONTROL SELECTOR SWITCH POS. A812 CONTROL SEL. OFF BCU
SDRA C4.C_T802 A812 A812 BAY CONTROL SELECTOR SWITCH BCU
147 GIS SF6 STAGE-2 ALARM A812 GIS SF6 2 ALARM NORMAL
SDRA C4.C_T802 A812 A812 GIS SF6 GAS Pressure Low Stage-2
151 TRIP CIRCUIT FAULTY FUTURE A813 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED
152 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A813 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 2
153 GIS GAS DENSITY ALARM FUTURE A813 GAS DESITY ALARM ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.A_FUTURE LINE FUTURE A813 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.A_FUTURE LINE FUTURE A813 GIS GAS PRESSURE HIGH
154 BAY CONTROL SUPPLY FAIL FUTURE A813 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 OPERATING MECH. SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 CONTROL SUPPLY DC FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 MOTOR SUPPLY AC FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 DS/ES CONTROL SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 DS/ES MOTOR SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
156 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A813 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.A_FUTURE LINE FUTURE A813 POLE DISCREPANCY RELAY OPERATED STAGE-2
157 SYNCHROCHECK RELAY FAULT FUTURE A813 SYNC CHK FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 DC FAIL OPERATED
14 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.A_FUTURE LINE FUTURE A813 SELF SUPERVISION OPERATED
SDRA C5.A_FUTURE LINE FUTURE A813 SYNCROCHECK FUSE FAILURE OPERATED
158 ALARM SUPPLY FAIL FUTURE A813 ALARM SUPPLY FAILED NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 ALARM INDICATION SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.A_FUTURE LINE FUTURE A813 ANNUNCIATION AC BACKUP SUPPLY FAIL
159 CBF PROTECTION OPERATED FUTURE A813 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 50BF CBF FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 BAY UNIT COMM. ERROR
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.A_FUTURE LINE FUTURE A813 CBF 86BF-2 TRIP RELAY FAULTY
160 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF LOCAL
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH LOCAL
161 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF REMOTE
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH REMOTE
162 CONTROL SELECTOR SWITCH POS. FUTURE A813 CONTROL SEL. OFF BCU
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 BAY CONTROL SELECTOR SWITCH BCU
163 GIS SF6 STAGE-2 ALARM FUTURE A813 GIS SF6 2 ALARM NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 FUTURE A813 GIS SF6 GAS Pressure Low Stage-2
164 CLOSING SUPPLY FAIL FUTURE A813 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE A813 CB FUTURE A813 Closing coil DC fail
165 INTERLOCK BYPASS FUTURE A813 INTL BYPASS ON OFF
SDRA C5.A_FUTURE LINE FUTURE A813 CB SECTION FUTURE A813 INTERLOCK BYPASS
167 TRIP CIRCUIT FAULTY FUTURE A814 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED
168 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A814 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 2
169 GIS GAS DENSITY ALARM FUTURE A814 GAS DESITY ALARM ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.B_FUTURE LINE FUTURE A814 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.B_FUTURE LINE FUTURE A814 GIS GAS PRESSURE HIGH
170 BAY CONTROL SUPPLY FAIL FUTURE A814 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 OPERATING MECH. SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 CONTROL SUPPLY DC FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 MOTOR SUPPLY AC FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 DS/ES CONTROL SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 DS/ES MOTOR SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
15 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.B_FUTURE LINE FUTURE A814 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
172 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A814 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.B_FUTURE LINE FUTURE A814 POLE DISCREPANCY RELAY OPERATED STAGE-2
173 SYNCHROCHECK RELAY FAULT FUTURE A814 SYNC CHK FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 DC FAIL OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 SELF SUPERVISION OPERATED
SDRA C5.B_FUTURE LINE FUTURE A814 SYNCROCHECK FUSE FAILURE OPERATED
174 ALARM SUPPLY FAIL FUTURE A814 ALARM SUPPLY FAILED NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 ALARM INDICATION SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.B_FUTURE LINE FUTURE A814 ANNUNCIATION AC BACKUP SUPPLY FAIL
175 CBF PROTECTION OPERATED FUTURE A814 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 50BF CBF FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 BAY UNIT COMM. ERROR
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.B_FUTURE LINE FUTURE A814 CBF 86BF-2 TRIP RELAY FAULTY
176 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF LOCAL
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH LOCAL
177 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF REMOTE
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH REMOTE
178 CONTROL SELECTOR SWITCH POS. FUTURE A814 CONTROL SEL. OFF BCU
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 BAY CONTROL SELECTOR SWITCH BCU
179 GIS SF6 STAGE-2 ALARM FUTURE A814 GIS SF6 2 ALARM NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 FUTURE A814 GIS SF6 GAS Pressure Low Stage-2
180 CLOSING SUPPLY FAIL FUTURE A814 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.B_FUTURE LINE FUTURE A814 CB FUTURE A814 Closing coil DC fail
181 INTERLOCK BYPASS FUTURE A814 INTL BYPASS ON OFF
SDRA C5.B_FUTURE LINE FUTURE A814 CB SECTION FUTURE A814 INTERLOCK BYPASS
183 TRIP CIRCUIT FAULTY FUTURE A815 TRIP CIRCUIT FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 TRIP CIRCUIT-1 SUPERVISION RELAY OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 TRIP CIRCUIT-2 SUPERVISION RELAY OPERATED
184 CIRCUIT BREAKER GAS PRESSURE LOW FUTURE A815 GAS PRESSURE LOW ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 1
16 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 2
185 GIS GAS DENSITY ALARM FUTURE A815 GAS DESITY ALARM ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 1
SDRA C5.C_FUTURE LINE FUTURE A815 CB SF6 GAS PRESSURE LOW STAGE 2
SDRA C5.C_FUTURE LINE FUTURE A815 GIS GAS PRESSURE HIGH
186 BAY CONTROL SUPPLY FAIL FUTURE A815 BAY CONTROL SUPPLY FAIL FAILED NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 OPERATING MECH. SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 CONTROL SUPPLY DC FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 MOTOR SUPPLY AC FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 DS/ES CONTROL SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 DS/ES MOTOR SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB TRIP CIRCUIT-1 DC SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 CB TRIP CIRCUIT-2 DC SUPPLY FAIL
188 CIRCUIT BREAKER POLE DISCREPANCY FUTURE A815 CB PPLE DISCREPANCY OPTD NORMAL OPERATE
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY RELAY OPERATED STAGE-1
SDRA C5.C_FUTURE LINE FUTURE A815 POLE DISCREPANCY RELAY OPERATED STAGE-2
189 SYNCHROCHECK RELAY FAULT FUTURE A815 SYNC CHK FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 DC FAIL OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 SELF SUPERVISION OPERATED
SDRA C5.C_FUTURE LINE FUTURE A815 SYNCROCHECK FUSE FAILURE OPERATED
190 ALARM SUPPLY FAIL FUTURE A815 ALARM SUPPLY FAILED NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 ALARM INDICATION SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 ANNUNCIATION DC SUPPLY FAIL
SDRA C5.C_FUTURE LINE FUTURE A815 ANNUNCIATION AC BACKUP SUPPLY FAIL
191 CBF PROTECTION OPERATED FUTURE A815 CBF PROTECTION FAULTY FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 50BF CBF FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 BAY UNIT COMM. ERROR
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 94BF-1 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 86BF-1 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 94BF-2 TRIP RELAY FAULTY
SDRA C5.C_FUTURE LINE FUTURE A815 CBF 86BF-2 TRIP RELAY FAULTY
192 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF LOCAL
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH LOCAL
193 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF REMOTE
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH REMOTE
194 CONTROL SELECTOR SWITCH POS. FUTURE A815 CONTROL SEL. OFF BCU
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 BAY CONTROL SELECTOR SWITCH BCU
195 GIS SF6 STAGE-2 ALARM FUTURE A815 GIS SF6 2 ALARM NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 FUTURE A815 GIS SF6 GAS Pressure Low Stage-2
196 CLOSING SUPPLY FAIL FUTURE A815 CLOSE CIRCUIT FAULTY NORMAL
SDRA C5.C_FUTURE LINE FUTURE A815 CB FUTURE A815 Closing coil DC fail
197 INTERLOCK BYPASS FUTURE A815 INTL BYPASS ON OFF
SDRA C5.C_FUTURE LINE FUTURE A815 CB SECTION FUTURE A815 INTERLOCK BYPASS
17 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 R1 PROTN. LOSS OF AC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/DC-1 LOSS OF DC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-1 VT FUSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 98/25AR BUS VT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/94-1 SUPVN OPTD
199 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-A OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-B OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_1 PH-C OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 94-1 TRIP RELAY OPTD
200 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 87L/21-1- RELAY TRIP
203 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-2 CCVT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-2 REALY OPERATED
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 TRIP RELAY COIL FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION TRIP ISOLATED
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 R1 PROTN. LOSS OF AC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/DC-2 LOSS OF DC
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 21-2 VT FUSE FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 98/25AR BUS VT FAIL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 74/94-2 SUPVN OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 PROTECTION IN/OUT
204 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-A OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-B OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 87L_2 PH-C OPTD
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 94-2 TRIP RELAY OPTD
205 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 SET-1 87L/21-2- RELAY TRIP
18 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
212 AUTO RECLOSE FAIL AR FAIL FAULTY NORMAL
SDRA C2.C_JUBL LINE-1 JUBAIL LINE-1 AUTO RECLOSE FAIL
217 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-A OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-B OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_1 PH-C OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 94-1 TRIP RELAY OPTD
218 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 87L/21-1- RELAY TRIP
221 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-2 CCVT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-2 REALY OPERATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 TRIP RELAY COIL FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/DC-2 LOSS OF DC
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 21-2 VT FUSE FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 98/25AR BUS VT FAIL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 74/94-2 SUPVN OPTD
222 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-A OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-B OPTD
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 87L_2 PH-C OPTD
19 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 94-2 TRIP RELAY OPTD
223 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C3.A_JUBL LINE-2 JUBAIL LINE-2 SET-1 87L/21-2- RELAY TRIP
235 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-A OPTD
20 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-B OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_1 PH-C OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 94-1 TRIP RELAY OPTD
236 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 87L/21-1- RELAY TRIP
239 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-2 CCVT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-2 REALY OPERATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 TRIP RELAY COIL FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 PROTECTION TRIP ISOLATED
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 R1 PROTN. LOSS OF AC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/DC-2 LOSS OF DC
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-2 VT FUSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 98/25AR BUS VT FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 74/94-2 SUPVN OPTD
240 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-A OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-B OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 87L_2 PH-C OPTD
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 94-2 TRIP RELAY OPTD
241 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 SET-1 87L/21-2- RELAY TRIP
21 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-1 DIST CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 67N-1 DEF CH FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 21-1 PSE FAIL
SDRA C4.A_JUBL COMMUNITY LINE-1 JUBAIL COMMUNITY LINE-1 DTT CHNL FAULTY
253 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-A OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-B OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_1 PH-C OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 94-1 TRIP RELAY OPTD
254 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 87L/21-1- RELAY TRIP
257 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-2 CCVT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-2 REALY OPERATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP RELAY COIL FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 PROTECTION TRIP ISOLATED
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 R1 PROTN. LOSS OF AC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/DC-2 LOSS OF DC
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 21-2 VT FUSE FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 98/25AR BUS VT FAIL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 74/94-2 SUPVN OPTD
258 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-A OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-B OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 87L_2 PH-C OPTD
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 94-2 TRIP RELAY OPTD
259 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 SET-1 87L/21-2- RELAY TRIP
22 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C3.C_JUBL COMMUNITY LINE-2 JUBAIL COMMUNITY LINE-2 TRIP CIRCUIT-2 FAULTY
271 87L_M1 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-A OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-B OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_1 PH-C OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 94-1 TRIP RELAY OPTD
272 LINE PROTECTION MAIN-1 TRIP OPERATED MAIN-1 TRIP OPERATED FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 87L/21-1- RELAY TRIP
23 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
275 LINE PROTECTION MAIN-2 FAIL LINE PROTECTION MAIN-2 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-2 CCVT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-2 REALY OPERATED
SDRA C5.A_FUTURE LINE FUTURE LINE TRIP RELAY COIL FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION TRIP ISOLATED
SDRA C5.A_FUTURE LINE FUTURE LINE R1 PROTN. LOSS OF AC
SDRA C5.A_FUTURE LINE FUTURE LINE 74/DC-2 LOSS OF DC
SDRA C5.A_FUTURE LINE FUTURE LINE 21-2 VT FUSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 98/25AR BUS VT FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 74/94-2 SUPVN OPTD
276 87L_M2 PROTECTION OPERATE LINE PROTECTION MAIN-1 FAIL FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-A OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-B OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 87L_2 PH-C OPTD
SDRA C5.A_FUTURE LINE FUTURE LINE 94-2 TRIP RELAY OPTD
277 LINE PROTECTION MAIN-2 TRIP OPERATED MAIN-2 TRIP OPERATED FAULTY NORMAL
SDRA C5.A_FUTURE LINE FUTURE LINE SET-1 87L/21-2- RELAY TRIP
24 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.A_FUTURE LINE FUTURE LINE 67N-2 DEF CH FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE 21-2 PSE FAIL
SDRA C5.A_FUTURE LINE FUTURE LINE DTT CHNL FAULTY
SDRA C5.A_FUTURE LINE FUTURE LINE PROTECTION IN/OUT
292 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C2.A_T801 T801 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1
293 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C2.A_T801 T801 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1
294 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C2.A_T801 T801 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2
25 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
300 PRIMARY PROTECTION OPERATED PRIMARY PROTECTION OPERATED NORMAL OPERATE
SDRA C2.A_T801 T801 86-1 OPERATED
C2.A_T801 T801 HV OVER FLUXING OPERATED
C2.A_T801 T801 MV OVER FLUXING OPERATED
C2.A_T801 T801 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-1 OPERATED
C2.A_T801 T801 TRANSFORMER DIFFERENTIAL PROTECTION MAIN-2 OPERATED
C2.A_T801 T801 OLTC SURGE RELAY TRIP
C2.A_T801 T801 67 OVER CURRENT OPERATED
C2.A_T801 T801 51 GT OPERATED
C2.A_T801 T801 GT OPERATED
302 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL
SDRA C2.A_T801 T801 WINDING TEMP. STAGE-2 OPERATED
303 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C2.A_T801 T801 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
304 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C2.A_T801 T801 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
310 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C4.C_T802 T802 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1
311 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1
312 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2
26 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
313 OIL LEVEL LOW OIL LEVEL LOW NORMAL OPERATE
SDRA C4.C_T802 T802 MAIN TRANSFORMER OIL LEVEL LOW
SDRA C4.C_T802 T802 TAP CHANGER OIL LEVEL LOW
320 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL
SDRA C4.C_T802 T802 WINDING TEMP. STAGE-2 OPERATED
321 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C4.C_T802 T802 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
322 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C4.C_T802 T802 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
27 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
328 WINDING TEMP. STAGE-1 OPERATED WINDING TEMP. STAGE-1 OPERATED NORMAL OPERATE
SDRA C5.C_T803 T803 SERIES WINDING TEMPRATURE HIGH STAGE-1
COMMON WINDING TEMPERATURE HIGH STAGE-1
TERTIARY WDG TEMP. HIGH STAGE-1
329 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1 MAIN XFR OIL TEMP. THERMOMETER STG-1 NORMAL OPERATE
SDRA C5.C_T803 T803 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-1
330 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2 MAIN XFR OIL TEMP. THERMOMETER STG-2 NORMAL OPERATE
SDRA C5.C_T803 T803 MAIN TRANSFORMER OIL TEMP THERMOMETER STAGE-2
338 WINDING TEMP. STAGE-2 OPERATED WINDING TEMP. STAGE-2 OPERATED FAULTY NORMAL
28 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA C5.C_T803 T803 WINDING TEMP. STAGE-2 OPERATED
339 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C5.C_T803 T803 PRIMARY PROTECTION SUPPLY SUPERVISION OPERATED
340 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
FAULTY NORMAL
SDRA C5.C_T803 T803 BACK UP PROTECTION SUPPLY SUPERVISION OPERATED
29 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
C4.C_T802 T802 OLTC OUT OF STEP
C4.C_T802 T802 AVR BLOCKED (O/V,O/C,U/V)
C4.C_T802 T802 RTCC CONTROL SUPPLY FAIL
C4.C_T802 T802 VOLTAGE CONTROL FAIL
C4.C_T802 T802 TAP CHANGE MOTOR FAIL
C4.C_T802 T802 AVR SUPPLY FAULTY
C4.C_T802 T802 TAP CHANGER OUT OF STEP
30 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
368 PARALLEL/INDEPENDENT PARALLEL/INDEPENDENT
SDRA C5.C_T803 T803 PARALLEL/INDEPENDENT
31 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA BBP M1 BBP M1 A813 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A806 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A809 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A812 86B-M1 LOR OPTD
SDRA BBP M1 BBP M1 A815 86B-M1 LOR OPTD
388 BBP MAIN-2 PROTECTION OPERATE BBP MAIN-2 PROTECTION NORMAL OPERATE
SDRA BBP M2 BBP M2 A804 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A807 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A810 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A813 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A806 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A809 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A812 86B-M2 LOR OPTD
SDRA BBP M2 BBP M2 A815 86B-M2 LOR OPTD
391 BBP CENTRAL UNIT OPERATED BB CENRAL UNIT FAULTY FAULTY OPERATE
SDRA F87_CU F87_CU BUS ZONE-1A OPERATED
SDRA F87_CU F87_CU BUS ZONE-2A OPERATED
SDRA F87_CU F87_CU BUS ZONE-1B OPERATED
SDRA F87_CU F87_CU BUS ZONE-2B OPERATED
32 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA F87_CU F87_CU BBP LOR OPERATED
SDRA F87_CU F87_CU CENTRAL UNIT POWER SUPPLY FAIL
SDRA F87_CU F87_CU 87CU RELAY FAIL
SDRA F87_CU F87_CU CENTRAL UNIT COMM. ERROR
33 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA
BUS-1A BUS-1A BUS 1A VT MCB FAILED
SDRA
BUS-1B BUS-1B BUS 1B VT MCB FAILED
SDRA
BUS-2A BUS-2A BUS 2A VT MCB FAILED
SDRA
BUS-2B BUS-2B BUS 2B VT MCB FAILED
402 SYNCHROCHECK FAIL BUS SYNC CHK FAULTY NORMAL
SDRA
BUS 7VK61 CB BUS SYNCHROCHECK FAIL
34 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SDRA RELAY FAULTY REMOTE
SDRA SF6 DENSITY BCU
GENERAL POINTS
35 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA Text Bit status=0 Bit status=1 GROUP
Name Name Name
Address
SMOKE DETECTOR OPERATED NORMAL
427 SMOKE DETECTOR OPERATED
36 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
BAY C2 JUBL LINE-1 MEASUREMENTS
37 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
10 SDRA LINE VT 7SD522-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7SD522-M1 BUS VT VOLTAGE YN
1 SDRA LINE CT P546-M2 CURRENT L1
2 SDRA LINE CT P546-M2 CURRENT L2
3 SDRA LINE CT P546-M2 CURRENT L3
4 SDRA LINE VT P546-M2 VOLTAGE L12
5 SDRA LINE VT P546-M2 VOLTAGE L23
6 SDRA LINE VT P546-M2 VOLTAGE L31
7 SDRA LINE VT P546-M2 CURRENT LN
8 SDRA LINE VT P546-M2 VOLTAGE LN
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C3 JUBL COMMUNITY2 LINE-2 MEASUREMENTS
38 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
9 SDRA LINE VT P546-M2 ACTIVE POWER (P)
10 SDRA LINE VT P546-M2 REACTIVE POWER (Q)
11 SDRA BUS VT P546-M2 BUS VT VOLTAGE YN
BAY C4 JUBL COMMUNITY2 LINE-1 MEASUREMENTS
39 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
7 SDRA XFER VT 7UT635-M1 CURRENT LN
8 SDRA XFER VT 7UT635-M1 VOLTAGE LN
9 SDRA XFER VT 7UT635-M1 ACTIVE POWER (P)
10 SDRA XFER VT 7UT635-M1 REACTIVE POWER (Q)
11 SDRA BUS VT 7UT635-M1 BUS VT VOLTAGE YN
1 SDRA XFER CT RET670-M2 CURRENT L1
2 SDRA XFER CT RET670-M2 CURRENT L2
3 SDRA XFER CT RET670-M2 CURRENT L3
4 SDRA XFER VT RET670-M2 VOLTAGE L12
5 SDRA XFER VT RET670-M2 VOLTAGE L23
6 SDRA XFER VT RET670-M2 VOLTAGE L31
7 SDRA XFER VT RET670-M2 CURRENT LN
8 SDRA XFER VT RET670-M2 VOLTAGE LN
9 SDRA XFER VT RET670-M2 ACTIVE POWER (P)
10 SDRA XFER VT RET670-M2 REACTIVE POWER (Q)
11 SDRA BUS VT RET670-M2 BUS VT VOLTAGE YN
BAY C3 T802 TRANSFORMER MEASUREMENTS
40 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
6 SDRA XFER VT RET670-M2 VOLTAGE L31
7 SDRA XFER VT RET670-M2 CURRENT LN
8 SDRA XFER VT RET670-M2 VOLTAGE LN
9 SDRA XFER VT RET670-M2 ACTIVE POWER (P)
10 SDRA XFER VT RET670-M2 REACTIVE POWER (Q)
11 SDRA BUS VT RET670-M2 BUS VT VOLTAGE YN
BAY C3 T803 FUTURE TRANSFORMER MEASUREMENTS
41 OF 42
SADRAH 380/230kV BSP SAS - SCADA
STATION COMMANDS
IEC-101
Station Bay Device
S.No IED Name SCADA Text SCADA TEXT TYPE SCALE FACTOR GROUP
Name Name Name
Address
4 SDRA BUS 1A CT 7SS522 CURRENT LN
5 SDRA BUS 1A VT 7SS522 VOLTAGE L12
6 SDRA BUS 1A VT 7SS522 VOLTAGE L23
7 SDRA BUS 1A VT 7SS522 VOLTAGE L31
8 SDRA BUS 1A VT 7SS522 VOLTAGE LN
9 SDRA BUS 1B CT 7SS522 CURRENT L1
10 SDRA BUS 1B CT 7SS522 CURRENT L2
11 SDRA BUS 1B CT 7SS522 CURRENT L3
12 SDRA BUS 1B CT 7SS522 CURRENT LN
13 SDRA BUS 1B VT 7SS522 VOLTAGE L12
14 SDRA BUS 1B VT 7SS522 VOLTAGE L23
15 SDRA BUS 1B VT 7SS522 VOLTAGE L31
16 SDRA BUS 1B VT 7SS522 VOLTAGE LN