Electrical load Calculation - Manglam Ananda at Jaipur (Phase-02)

ESS- 02

S.no Description No. of unit Load per Unit Total Load

Tower - 4,5 & 13 (S+12) Nos of Block = 3


4 BHK
1 72 units @ 13.2 KW = 951 KW
(1650 sq Ft @ 8 W/sqFt = 13.2 KW)
4 BHK + Servent
2 66 units @ 14.2 KW = 940 KW
(1780 sq Ft @ 8 W/sqFt = 14.2 KW)
3 BHK + 3 Toi
3 6 units @ 12.6 KW = 76 KW
(1574 sq Ft @ 8 W/sqFt = 12.6 KW)

Tower - 1 & 3 (3rd to 12th) Nos of Block = 2


3 BHK + 3 Toi. (1)
4 40 units @ 10.1 KW = 403 KW
(1258 sq Ft @ 8 W/sqFt = 10.1 KW)
3 BHK + 3 Toi. (2)
5 40 units @ 10.3 KW = 412 KW
(1289 sq Ft @ 8 W/sqFt = 10.3 KW)

Tower - 2 (3rd to 12th) Nos of Block = 1


3 BHK + 3 Toi. (2)
6 40 units @ 10.3 KW = 412 KW
(1289 sq Ft @ 8 W/sqFt = 10.3 KW)
COMMON SERVICES - Towers

Tower - 4,5 & 13 (S+12) Nos of Block = 3

7 Elevators (16 Passenger) 1.0 mps 6 nos @ 9.0 KW = 54 KW

8 Common Lights 3 towers @ 2.0 KW = 6 KW

Tower - 1 & 3 (3rd to 12th) Nos of Block = 2

9 Elevators (16 Passenger) 1.0 mps 4 nos @ 9.0 KW = 36 KW

10 Common Lights 2 towers @ 2.0 KW = 4 KW

Tower - 2 (3rd to 12th) Nos of Block = 1

11 Elevators (16 Passenger) 1.0 mps 2 nos @ 9.0 KW = 18 KW

12 Common Lights 1 towers @ 2.0 KW = 2 KW

COMMON SERVICES - General

13 External / Gate / Landscape lighting = 5 KW

14 Basement Lights 7461 Sq M @ 0.7 W/sq m = 5 KW

15 Basement Ventilation = 50 KW

16 Commercial = 400 KW

17 Club = 200 KW
Total Load = 3974 KW
By taking Overall Diversity factor 50 % = 1987 KW

By taking Power factor 0.90 = 2210 KVA

Total Electrical Load = 2210 KVA

Recommended Transformers at 85% loading = 1 nos. 1600 KVA & 1 nos. 1000 KVA, 11 /
0.4 KV each