Electrical load Calculation of Spring Homes

S.No Description No. of unit Load per Unit Total Load

Tower - A (S+21) Nos of Tower = 1


3BHK + 3T+Servant
1 39 units @ 6.1 KW = 239 KW
(122.8 sq M @ 50 W/sqM = 6.14 KW)
4BHK + 4T+Servant
2 39 units @ 9.6 KW = 373 KW
(191.1 sq M @ 50 W/sqM = 9.56 KW)

Tower - B/C(S+18) Nos of Tower = 2


3BHK+2T - type1
3 108 units @ 4.4 KW = 480 KW
(88.8 sq M @ 50 W/sqM = 4.44 KW)
3BHK+2T - type2
4 108 units @ 5.0 KW = 537 KW
(99.5 sq M @ 50 W/sqM = 4.98 KW)

Tower - D (S+16) Nos of Tower = 1


5BHK + 5T+ 2 Servant
5 16 units @ 18.3 KW = 292 KW
(365.0 sq M @ 50 W/sqM = 18.25 KW)

Total Load = 1921 KW


Calculation for Transformers
By taking Overall Diversity factor 50 % => 960 KW
By taking Power factor 0.90 => 1070 KVA
Total Electrical Load = 1070 KVA

Recommended Transformers @ 80% Loading = 1 nos. 1600 KVA

Elec_Load Calc_Spring Homes Page 1


Electrical load Calculation of Spring Homes-EV Charging

S.No Description No. of unit Load per Unit Total Load

EV Charging load

1 Electrical Car Charging (20 % of Dwelling units) 62 nos @ 3.0 KW = 186 KW

Total Load = 186 KW

By taking Overall Diversity factor 30 % => 56 KW

By taking Power factor 0.90 => 60 KVA

Total Electrical Load = 60 KVA


Recommended Transformers @ 80% Loading = 1 nos. 160 KVA, 11/0.433 kV Compact Substation
(Considering Future Contingency)

Consummate Engg Services Pvt. Ltd Page 2


Common Services - Electrical load Calculation of Spring Homes

S.No Description No. of unit Load per Unit Total Load

COMMON SERVICES - TOWERS

Tower - A (S+21) Nos of Tower = 1


1 Elevators (13 Passenger) 1.75 mps 2 nos @ 10 KW = 20 KW
2 Elevators (15 Passenger) 1.75 mps 1 nos @ 15 KW = 15 KW
3 Common Lights 1 towers @ 5 KW = 5 KW

Tower - B/C(S+18) Nos of Tower = 2


4 Elevators (13 Passenger) 1.75 mps 2 nos @ 10 KW = 40 KW
5 Elevators (15 Passenger) 1.75 mps 1 nos @ 15 KW = 30 KW
6 Common Lights 1 towers @ 5 KW = 10 KW

Tower - D (S+16) Nos of Tower = 1


7 Elevators (13 Passenger) 1.75 mps 3 nos @ 10 KW = 30 KW
8 Common Lights 1 towers @ 5 KW = 5 KW

COMMON SERVICES - General

9 Water Supply / Tube wells 1 job @ 40 KW = 40 KW


10 STP 1 job @ 2.5 KW = 2.5 KW
11 External / Gate / Landscape lighting = 10 KW
12 Podium lights 5756 sqm @ 1.0 W/sqm = 6 KW
13 Basement lights 6402 sqm @ 1.0 W/sqm = 6 KW
14 Basement Ventilation @ 25% Diversity 15 KW
15 Community Hall 200 KW
Fire pumps (only jockey pumps have been
16 1 set @ 20 KW = 20 KW
considered)

Total Load = 455 KW


Calculation for Transformers
By taking Overall Diversity factor 75 % => 341 KW
By taking Power factor 0.90 => 380 KVA
Total Electrical Load = 380 KVA

Recommended Transformers @ 80% Loading = 1 nos. 630 KVA (Considering Fire Dead Load)

Elec_Load Calc_Spring Homes Page 3


Essential Electrical Load Calculations - Spring Homes

S.no Description No. of unit Load per Unit Total Load

SUB HEAD - A (APARTMENTS)

Tower - A (S+21) Nos of Tower = 1


1 3BHK + 3T+Servant 39 units @ 3.00 KVA = 117 KVA
2 4BHK + 4T+Servant 39 units @ 4.00 KVA = 156 KVA
Tower - B/C(S+18) Nos of Tower = 2
3 3BHK+2T - type1 108 units @ 3.00 KVA = 648 KVA
4 3BHK+2T - type2 108 units @ 3.00 KVA = 648 KVA
Tower - D (S+16) Nos of Tower = 1
5 5BHK + 5T+ 2 Servant 16 units @ 5.00 KVA = 80 KVA

Total Load = 1649 KVA

By taking overall Diversity factor 70 % => 1154 KVA


Essential Load ( A ) = 1154 KVA

COMMON SERVICES - TOWERS

Description Nos of Tower = 1


6 Elevators (13 Passenger) 1.75 mps 2 nos @ 10 KW = 20 KW
7 Elevators (15 Passenger) 1.75 mps 1 nos @ 15 KW = 15 KW
8 Common Lights 1 towers @ 5 KW = 5 KW

Tower - B/C(S+18) Nos of Tower = 2


9 Elevators (13 Passenger) 1.75 mps 2 nos @ 10 KW = 40 KW
10 Elevators (15 Passenger) 1.75 mps 1 nos @ 15 KW = 30 KW
11 Common Lights 1 towers @ 5 KW = 10 KW

Tower - D (S+16) Nos of Tower = 1


12 Elevators (13 Passenger) 1.75 mps 3 nos @ 10 KW = 30 KW
13 Common Lights 1 towers @ 5 KW = 5 KW

COMMON SERVICES - General


14 Water Supply / Tube wells 1 job @ 40 KW = 40 KW
15 STP 1 job @ 2.5 KW = 2.5 KW
16 External / Gate / Landscape lighting = 10 KW
17 Podium lights 5756 sqm @ 1.0 W/sqm = 6 KW
18 Basement lights 6402 sqm @ 1.0 W/sqm = 6 KW
19 Basement Ventilation @ 25% Diversity 15 KW
20 Community Hall 200 KW

Ess_Load Calc_Spring Homes 4


Essential Electrical Load Calculations - Spring Homes

S.no Description No. of unit Load per Unit Total Load

Fire pumps (only jockey pumps have


21 1 set @ 20 KW = 20 KW
been considered)

Total Load = 455 KW


By taking overall Diversity factor 60 % => 273 KW
By taking Power factor 0.80 => 341 KVA
Essential Load ( B ) = 340 KVA

Total Essential Load (A + B ) = 1494 KVA

Considering DG loading 90 % => 1660 KVA

Recommended DG Sets = 1 nos 1010 kVA & 1 no 630 KVA DG Sets

Ess_Load Calc_Spring Homes 5