You are on page 1of 4

SHEET : 1 OF: 4

TEST REPORT FOR RELAY PAGE :


DATE : 27.06.2022
Client : M/S. BPCL Refinery,Mahul,Mumbai,Maharastra.
Project: Maintenance and Testing of Relays

1. Location : GT 3 Switch House/BOP MCC

Feeder Name : BUS COUPLER

P.No : 6F-C

2. Name Plate Details :

Make ALSTOM

TESTED BY VOLTECH WITNESSED BY


SHEET : 2 OF: 4
TEST REPORT FOR RELAY PAGE :
DATE : 27.06.2022
Client : M/S. BPCL Refinery,Mahul,Mumbai,Maharastra.
Project: Maintenance and Testing of Relays

TYPE SKE11

SR.NO 130060110018001

Normal Volts 110 V DC

Drop off Volts 66 V DC

Vn 240 V AC

3. General Inspection : OK

TESTED BY VOLTECH WITNESSED BY


SHEET : 3 OF: 4
TEST REPORT FOR RELAY PAGE :
DATE : 27.06.2022
Client : M/S. BPCL Refinery,Mahul,Mumbai,Maharastra.
Project: Maintenance and Testing of Relays

4.Secondary Injection Test:

Ref % Difference Of Pick up(Volts) Drop Off(Volts)


Lockout
(5,7) 2% 109.1 107.1
(8,10) 2% 109.2 107.4

5. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

TESTED BY VOLTECH WITNESSED BY


SHEET : 4 OF: 4
TEST REPORT FOR RELAY PAGE :
DATE : 27.06.2022
Client : M/S. BPCL Refinery,Mahul,Mumbai,Maharastra.
Project: Maintenance and Testing of Relays

1 Wiring Connections OK
2 Flag OK
3 Coil OK

6. Comments : Nil.

7. Remarks : Relay Found Healthy.

TESTED BY VOLTECH WITNESSED BY