TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 1 OF: 17


Project : M245CIL2A3 Date:11.05.2021

1. Location : MWP -13

Reference : 520 KVA STEP UP TRASFORMER

2. Name plate details:

Make SHILCHAR TECHNOLOGIES LTD


Sl.No 2820/06
Rating 520 KVA
Primary Voltage 415 V
TESTED BY VOLTECH WITNESSED BY CIL
TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 2 OF: 17


Project : M245CIL2A3 Date:11.05.2021

Secondary Voltage 1219-4282 V


Primary Current 723.43 A
Secondary Current 246.29- 70.11 A
Temp rise oil /wdg 45/50 ˚c
Type of Cooling Oil Cooled Copper Wound
% Impedance 3.20%
MFD YEAR 2018
Frequency 50HZ

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 3 OF: 17


Project : M245CIL2A3 Date:11.05.2021

3. General Inspection: OK

4. Insulation Resistance Test:

Applied Voltage ( DC Measured Values (Ω)


Reference
V) 1 min (GΩ) 10 min (GΩ) PI
Sec– Earth 500 >1GΩ - -
Pri – Sec 2500 5.47 8.82 1.61
Pri – Earth 2500 3.10 7.07 2.28

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 4 OF: 17


Project : M245CIL2A3 Date:11.05.2021

5. Winding Resistance Test:


Injecting Current : 1A

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 5 OF: 17


Project : M245CIL2A3 Date:11.05.2021

Tap Measured Resistance Value in Primary (mΩ)


Position
(Normal) X1X2 X1X3 X2X3
4-5 4.3 4.4 4.3

Injecting Current : 10 A
TAP
Measured Resistance Value in Secondary (mΩ)
POSITION
H1HN H2HN H3HN

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 6 OF: 17


Project : M245CIL2A3 Date:11.05.2021

5-1 105.4 104.9 104.9


5-2 108.3 108.1 108.1
5-3 111.6 111.4 111.3
5-4 114.8 114.6 114.7
5-5 118.2 118.2 118.2

6. Magnetizing Current Test:

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 7 OF: 17


Project : M245CIL2A3 Date:11.05.2021

Tap Applied Voltage in (V) Measured Current in (A)


position IH1 IH2 IH3
H1H2 H2H3 H3H1 H1HN
1-1 417.3 416.5 416.1 240.4 3.2 3.2 3.2

1-2 417.6 417.5 417.0 240.9 3.2 3.3 3.2


1-3 417.3 416.5 416.1 240.4 3.2 3.2 3.2
1-4 417.6 417.5 417.0 240.9 3.1 3.1 3.0
1-5 417.3 416.5 416.1 240.4 3.0 3.0 3.0
2-1 417.6 417.5 417.0 240.9 2.9 2.8 2.8

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 8 OF: 17


Project : M245CIL2A3 Date:11.05.2021

2-2 417.3 416.5 416.1 240.4 2.6 2.7 2.7


2-3 417.6 417.5 417.0 240.9 2.6 2.6 2.7
2-4 417.3 416.5 416.1 240.4 2.6 2.6 2.7
2-5 417.6 417.5 417.0 240.9 2.6 2.6 2.7
3-1 417.3 416.5 416.1 240.4 2.6 2.6 2.5
3-2 417.6 417.5 417.0 240.9 2.6 2.6 2.6
3-3 417.3 416.5 416.1 240.4 2.6 2.6 2.6
3-4 417.6 417.5 417.0 240.9 2.6 2.5 2.5
3-5 417.3 416.5 416.1 240.4 2.4 2.5 2.5
4-1 417.6 417.5 417.0 240.9 2.4 2.4 2.4

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 9 OF: 17


Project : M245CIL2A3 Date:11.05.2021

4-2 417.3 416.5 416.1 240.4 2.4 2.4 2.4


4-3 417.6 417.5 417.0 240.9 2.4 2.4 2.4
4-4 417.3 416.5 416.1 240.4 2.3 2.4 2.4
4-5 417.6 417.5 417.0 240.9 2.3 2.3 2.3
5-1 417.3 416.5 416.1 240.4 2.3 2.3 2.3
5-2 417.6 417.5 417.0 240.9 2.3 2.3 2.2
5-3 417.3 416.5 416.1 240.4 2.3 2.3 2.2
5-4 417.6 417.5 417.0 240.9 2.2 2.2 2.1
5-5 417.3 416.5 416.1 240.4 2.2 2.2 2.1

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 10 OF: 17


Project : M245CIL2A3 Date:11.05.2021

7. Ratio Test:

Tap Applied Voltage in (V) Measured Voltage in LV Side (V)


position X1X2 X2X3 X3X1
H1H2 H3H1 H1,H2,H3
H2H3
,HN
1-1 417.3 416.5 416.1 240.4 81.9 81.7 81.8
1-2 417.6 417.5 417.0 240.9 78.1 77.9 77.8
1-3 417.3 416.5 416.1 240.4 74.5 74.4 74.3

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 11 OF: 17


Project : M245CIL2A3 Date:11.05.2021

1-4 417.6 417.5 417.0 240.9 71.2 71.1 71.1


1-5 417.3 416.5 416.1 240.4 67.1 67.8 67.8
2-1 417.6 417.5 417.0 240.9 67.8 67.7 67.7
2-2 417.3 416.5 416.1 240.4 65.35 65.36 65.37
2-3 417.6 417.5 417.0 240.9 63.05 62.08 62.63
2-4 417.3 416.5 416.1 240.4 60.78 60.55 60.72
2-5 417.6 417.5 417.0 240.9 58.43 58.23 58.26
3-1 417.3 416.5 416.1 240.4 58.26 58.23 58.23
3-2 417.6 417.5 417.0 240.9 56.25 56.19 56.21
3-3 417.3 416.5 416.1 240.4 54.27 54.25 54.31

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 12 OF: 17


Project : M245CIL2A3 Date:11.05.2021

3-4 417.6 417.5 417.0 240.9 52.68 52.59 52.61


3-5 417.3 416.5 416.1 240.4 50.95 50.78 50.89
4-1 417.6 417.5 417.0 240.9 50.87 50.75 50.76
4-2 417.3 416.5 416.1 240.4 49.32 49.19 49.27
4-3 417.6 417.5 417.0 240.9 47.95 47.75 47.78
4-4 417.3 416.5 416.1 240.4 46.51 46.50 46.45
4-5 417.6 417.5 417.0 240.9 45.20 45.10 45.12
5-1 417.3 416.5 416.1 240.4 45.19 45.06 45.04
5-2 417.6 417.5 417.0 240.9 43.95 43.83 43.83
5-3 417.3 416.5 416.1 240.4 42.86 42.68 42.73

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 13 OF: 17


Project : M245CIL2A3 Date:11.05.2021

5-4 417.6 417.5 417.0 240.9 41.62 41,61 41.67


5-5 417.3 416.5 416.1 240.4 40.56 40.47 40.53

8. Magnetic Balance Test:

LV SIDE IN (V) HV SIDE IN (V)


PHASE H1H2 H2H3 H3H1 H1HNN H2HN H3H X1X2 X2X3 X1X3
CUT
H1HN 410.8 88.8 321.7 244.1 166.1 77.4 27.95 13.03 40.98
OPEN

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 14 OF: 17


Project : M245CIL2A3 Date:11.05.2021

H2HN 368.1 366.4 2.40 123.2 244.6 121.1 41.4 20.39 20.66
OPEN
H3HN 86.3 408.3 321.6 78.3 164.7 243.3 27.70 40.88 13.16
OPEN

9.Vector group

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 15 OF: 17


Project : M245CIL2A3 Date:11.05.2021

Short 1U (X1)) and 2U(H1) and then apply 440 volts on HT side & Measure Following voltages

H1 X1

X2

X3
HN

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 16 OF: 17


Project : M245CIL2A3 Date:11.05.2021

H2
H3

H1X3+ X3HN =H1HN 40.49 + 200.7 = 241.7


H3X3=H2X3 382.8 =384.0
H3X2> H3X3 419.2 > 382.2

TESTED BY VOLTECH WITNESSED BY CIL


TEST REPORT FOR POWER TRANSFORMER

Client : M/s CAIRN INDIA LTD., BARMER. SHEET : 17 OF: 17


Project : M245CIL2A3 Date:11.05.2021

9. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 Inspection of any physical damages OK


2 Tightness of Earthing Cables OK

10. Remarks : Test Results are Found Satisfactory.

TESTED BY VOLTECH WITNESSED BY CIL