SITE TEST REPORT Date : 14/12/2021

Contractor’s name:
Client: SEC-COA
SEPCOlll

Name of substation: Layla 380/132KV BSP #9049 SS Contract No.:4400012943

Page 1 of 1
LEAKAGE CURRENT METER
Line 9028 -R Leakage Current Meter

1. GENERAL DATA AND INFORMATION :

Bay Ref : 380KV Bay Name : AL KHARJ 9028 LINE-1

YEAR : 7- 2020 Ammeter Type : Analog

Range : 0-50 mA AC Counter Type : DCC-ML 2


Phase : Red
Manufacturer : TRIDELTA MADE IN : GERMANY

2. MECHANICAL AND VISUAL INSPECTION :

Item Description Checked


1. Inspect for physical damage / defects. OK
2. Check nameplate information for correctness. OK
3. Check that all groundings are properly connected. OK
4. Check tightness of all connections. OK
5. Check the 6 digit cyclometer display. OK

3. ELECTRICAL TESTS:
Observation Applied current to the Applied Voltage Displayed current in
Results
number meter (mA) (V) the meter (mA)
1 1 3.477 1 OK
2 2 5.853 2 OK
3 3 7.530 3 OK
4 10 16.23 9 OK
5 30 41.58 28 OK
6 50 65.76 48 OK
4. COMMENTS:

5. EQUIPMENTS USED
SVERKER760 S/N:7602271 Due date:27-jul-2021
FLUKE-187 MULTIMETER S/N 89750004 Due date:27-jul-2022

TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : IFTIKHAR ALI / XER057 Name : Mr. ABDUL RAZZAQ