Professional Documents
Culture Documents
Contractor’s name:
Client: SEC-COA
SEPCOlll
Page 1 of 1
LEAKAGE CURRENT METER
Line 9028 -R Leakage Current Meter
3. ELECTRICAL TESTS:
Observation Applied current to the Applied Voltage Displayed current in
Results
number meter (mA) (V) the meter (mA)
1 1 3.477 1 OK
2 2 5.853 2 OK
3 3 7.530 3 OK
4 10 16.23 9 OK
5 30 41.58 28 OK
6 50 65.76 48 OK
4. COMMENTS:
5. EQUIPMENTS USED
SVERKER760 S/N:7602271 Due date:27-jul-2021
FLUKE-187 MULTIMETER S/N 89750004 Due date:27-jul-2022