You are on page 1of 7

GAS TRANSMISSION

COMPANY LIMITED
29 Tuas Avenue 3 Singapore 639420 Tel : +65 6865 1765
E-mail : zepl@zicomgroup.com Fax : +65 6865 1764

INSTRUMENT DATASHEET FOR CHART RECORDER


IFT No. : 28.14.0000.827.41.001.21(Lot-A)
Date : 12-11-2021
Doc. No.: 357-06-DTS-100

Job No. : P-357

Client : GAS TRANSMISSION COMPANY LIMITED (GTCL)

Location : ASHULIA, DEMRA, GARARAN, MONOHORDI

: INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-


Project Title
TRANSMISSION POINTS OF GTCL PROJECT

A 10-01-2022 7 ISSUED FOR PROCUREMENT LK AS RK GTCL


Rev. Date Page Description of Revision Prepared Checked Approved Client
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER

Project Name: INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL
Rev: A
PROJECT
Station Name: 250 MMSCFD CGS ASHULIA Sheet No.: 2 of 7
1 Tag No. Refer to Sheet No. 06 of 07
2 Quantity 5
3 Manufacturer -
4 Model VTA
GENERAL
5 Service Metering
6 Function Record Only
7 Line Size & Class Refer to Sheet No. 06 of 07
8 P&ID No. Refer to Sheet No. 06 of 07
9 Fluid Natural Gas
10 State Gas
PROCESS
11 Operating Pressure Refer to Sheet No. 06 of 07
CONDITION
12 Operating Dif.Pressure Refer to Sheet No. 06 of 07
13 Operating Temperature Refer to Sheet No. 06 of 07
14 Casing MFR STD
15 Enclosure Class Weather Proof IP65
16 Power Supply N/A
17 Chart Type Circular Disc
18 Chart Dimension 10"
19 Scale 0~100 %
20 Chart Drive 24hr and 7 days
21 Diaphragm Material VTA
22 Accuracy VTA
23 Range
24 Pressure Refer to Sheet No. 06 of 07
25 Dif.Pressure Refer to Sheet No. 06 of 07
CHART RECORDER
26 Temperature Refer to Sheet No. 06 of 07
27 Spiral Armour Length VTA
28 Thermowell
29 Connection Size 3/4" NPT
30 Material 316 SS
31 U-Length Refer to Sheet No. 06 of 07
32 Others
33 Number of Pen 3
Red for DP , Green for Static Pressure, Violet
34 Pen Colour
for Temp
35 Mounting Bracket Yes
36 Zero Elevation or Suppression N/A
Notes:
1. VTA =Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER

Project Name: INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL
Rev: A
PROJECT
Station Name: 250 MMSCFD CGS AT DEMRA Sheet No.: 3 of 7
1 Tag No. Refer to Sheet No. 07 of 07
2 Quantity 6
3 Manufacturer -
4 Model VTA
GENERAL
5 Service Metering
6 Function Record Only
7 Line Size & Class Refer to Sheet No. 07 of 07
8 P&ID No. Refer to Sheet No. 07 of 07
9 Fluid Natural Gas
10 State Gas
PROCESS
11 Operating Pressure Refer to Sheet No. 07 of 07
CONDITION
12 Operating Dif.Pressure Refer to Sheet No. 07 of 07
13 Operating Temperature Refer to Sheet No. 07 of 07
14 Casing MFR STD
15 Enclosure Class Weather Proof IP65
16 Power Supply N/A
17 Chart Type Circular Disc
18 Chart Dimension 10"
19 Scale 0~100 %
20 Chart Drive 24hr and 7 days
21 Diaphragm Material VTA
22 Accuracy VTA
23 Range
24 Pressure Refer to Sheet No. 07 of 07
25 Dif.Pressure Refer to Sheet No. 07 of 07
CHART RECORDER
26 Temperature Refer to Sheet No. 07 of 07
27 Spiral Armour Length VTA
28 Thermowell
29 Connection Size 3/4" NPT
30 Material 316 SS
31 U-Length Refer to Sheet No. 07 of 07
32 Others
33 Number of Pen 3
Red for DP , Green for Static Pressure, Violet
34 Pen Colour
for Temp
35 Mounting Bracket Yes
36 Zero Elevation or Suppression N/A
Notes:
1. VTA =Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER

Project Name: INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL
Rev: A
PROJECT
Station Name: 300 MMSCFD MS AT GARARAN Sheet No.: 4 of 7
1 Tag No. CR-57301, CR-57302, CR-57303
2 Quantity 3
3 Manufacturer -
4 Model VTA
GENERAL
5 Service Metering
6 Function Record Only
7 Line Size & Class 12" ANSI 600#
8 P&ID No. 357-03-PID-300
9 Fluid Natural Gas
10 State Gas
PROCESS
11 Operating Pressure 575 ~ 975 PSIG
CONDITION
12 Operating Dif.Pressure 0 ~ 500 mbar
13 Operating Temperature 10 ~ 24 °C
14 Casing MFR STD
15 Enclosure Class Weather Proof IP65
16 Power Supply N/A
17 Chart Type Circular Disc
18 Chart Dimension 10"
19 Scale 0~100 %
20 Chart Drive 24hr and 7 days
21 Diaphragm Material VTA
22 Accuracy VTA
23 Range
24 Pressure 0 ~ 1200 PSIG
25 Dif.Pressure 0 ~ 500 mbar
CHART RECORDER
26 Temperature 0 ~ 60 °C
27 Spiral Armour Length VTA
28 Thermowell
29 Connection Size 3/4" NPT
30 Material 316 SS
31 U-Length 8 Inch
32 Others
33 Number of Pen 3
Red for DP , Green for Static Pressure,
34 Pen Colour
Violet for Temp
35 Mounting Bracket Yes
36 Zero Elevation or Suppression N/A
Notes:
1. VTA =Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER

Project Name: INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL
Rev: A
PROJECT
Station Name: 400 MMSCFD CMS AT MONOHORDI Sheet No.: 5 of 7
1 Tag No. CR-57501
2 Quantity 1
3 Manufacturer -
4 Model VTA
GENERAL
5 Service Metering
6 Function Record Only
7 Line Size & Class 12" ANSI 600#
8 P&ID No. 357-03-PID-500
9 Fluid Natural Gas
10 State Gas
PROCESS
11 Operating Pressure 750 ~ 1000 PSIG
CONDITION
12 Operating Dif.Pressure 0 ~ 500 mbar
13 Operating Temperature 10 ~ 24 °C
14 Casing MFR STD
15 Enclosure Class Weather Proof IP65
16 Power Supply N/A
17 Chart Type Circular Disc
18 Chart Dimension 10"
19 Scale 0~100 %
20 Chart Drive 24hr and 7 days
21 Diaphragm Material VTA
22 Accuracy VTA
23 Range
24 Pressure 0 ~ 1500 PSIG
25 Dif.Pressure 0 ~ 500 mbar
CHART RECORDER
26 Temperature 0 ~ 60 °C
27 Spiral Armour Length VTA
28 Thermowell
29 Connection Size 3/4" NPT
30 Material 316 SS
31 U-Length 8 Inch
32 Others
33 Number of Pen 3
Red for DP , Green for Static Pressure,
34 Pen Colour
Violet for Temp
35 Mounting Bracket Yes
36 Zero Elevation or Suppression N/A
Notes:
1. VTA =Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER
PROJECT NAME : INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL PROJECT Rev: A
DOC NO.: Station Name: 250 MMSCFD CGS AT ASHULIA Sheet No.: 6 of 7
General Information Process Information
Pressure Temperature Differential Pressure
Operating Full Scale Operating Full Scale Operating Full Scale U Length of Line Pipe
Sl. Flow
Tag No. Model No. P&ID No. Location Range Range Range Range Range Range Thermo -Well Size Class/
No
Min Max Min Max Min Max Min Max Min Max Min Max Rating

(MMSCFD) Psig Psig Psig Psig °C °C °C °C mbar mbar mbar mbar Inch Inch

Orifice Metering at
1 CR-57101 VTA 357-03-PID-100 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
2 CR-57102 VTA 357-03-PID-100 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
3 CR-57103 VTA 357-03-PID-100 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
4 CR-57104 VTA 357-03-PID-100 100 150 300 0 500 15 - 0 60 0 500 0 500 10 16 ASME 600
Station Outlet 2

Orifice Metering at
5 CR-57105 VTA 357-03-PID-100 100 150 300 0 500 15 - 0 60 0 500 0 500 10 16 ASME 600
Station Outlet 2
Notes.
1. VTA = Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard,
GAS TRANSMISSION DATASHEET FOR
COMPANY LIMITED CHART RECORDER
PROJECT NAME : INSTALLATION AND MODIFICATION OF GAS STATIONS AT OFF-TRANSMISSION POINTS OF GTCL PROJECT Rev: A
DOC NO.: Station Name: 250 MMSCFD CGS AT DEMRA Sheet No.: 7 of 7
General Information Process Information

Pressure Temperature Differential Pressure


U Length of Line Pipe
Sl. Flow Operating Full Scale Operating Full Scale Operating Full Scale
Tag No. Model No. Serial No. P&ID No. Location Thermo -Well Size Class/
No Range Range Range Range Range Range
Rating
Min Max Min Max Min Max Min Max Min Max Min Max
(MMSCFD) Psig Psig Psig Psig °C °C °C °C mbar mbar mbar mbar Inch Inch

Orifice Metering at
1 CR-57201 VTA VTA 357-03-PID-200 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
2 CR-57202 VTA VTA 357-03-PID-200 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
3 CR-57203 VTA VTA 357-03-PID-200 75 300 350 0 500 15 23 0 60 0 500 0 500 6 10 ASME 600
Station Outlet 1

Orifice Metering at
4 CR-57204 VTA VTA 357-03-PID-200 100 150 300 0 500 15 - 0 60 0 500 0 500 10 16 ASME 600
Station Outlet 2

Orifice Metering at
5 CR-57205 VTA VTA 357-03-PID-200 100 150 300 0 500 15 - 0 60 0 500 0 500 10 16 ASME 600
Station Outlet 2

Orifice Metering at
6 CR-57206 VTA VTA 357-03-PID-200 250 500 1000 0 1500 10 24 0 60 0 500 0 500 10 16 ASME 600
Station Outlet 3
Notes.
1. VTA = Vendor to Advise, N/A-Not Applicable, MFR STD- Manufacturer Standard,