Voltage Drop Calculations for 3-Phase Aluminium Cable

Resistivity
Length of
of the
Cable
material
Factor
conductor

Simple Simple
Length of Length of
Reactance
Cable Cable
0.023 for per Length
(Distance Cross (Distance Current in
b=2 for Copper & unit Sinus
between Power Section of between Watt= Amps Voltage
Single 0.037 for the source (default {(acos(cosφ KW Remarks
Factor the Cable the source KWx1000 I=W/575.02 Drop
Sr. No. Phase Aluminum value )}
and the in mm² and the 4
Wiring & (Ambient appliance), 0.00008
appliance),
b=1 for Temp = 25 in meters ohm/m)
in meters
three Phase °C in (m) (m)
wiring ohm.mm/m
²

b ρ L Cos φ S λ L Sin φ I ∆V

1 2 3 4 5 6 7 8 9 10 11 12 13 14

1 1 0.037 150 0.8 400 0.00008 150 0.58779 350 350000 608.67 11.05

Fix Value
Voltage Drop Calculations for 3-Phase Copper Cable
Resistivity
Length of
of the
Cable
material
Factor
conductor

Simple Simple
Length of Length of
Reactance
Cable Cable
0.023 for per Length
(Distance Cross (Distance Current in
b=2 for Copper & unit Sinus
between Power Section of between Watt= Amps Voltage
Single 0.037 for the source (default {(acos(cosφ KW Remarks
Factor the Cable the source KWx1000 I=W/575.02 Drop
Sr. No. Phase Aluminum value )}
and the in mm² and the 4
Wiring & (Ambient appliance), 0.00008
appliance),
b=1 for Temp = 25 in meters ohm/m)
in meters
three Phase °C in (m) (m)
wiring ohm.mm/m
²

b ρ L Cos φ S λ L Sin φ I ∆V

1 2 3 4 5 6 7 8 9 10 11 12 13 14

1 1 0.023 150 0.8 400 0.00008 150 0.58779 350 350000 608.67 8.49

Fix Value
Voltage Drop Calculations for 1-Phase Aluminium Cable
Resistivity
Length of
of the
Cable
material
Factor
conductor

Simple Simple
Length of Length of
Reactance
Cable Cable
0.023 for per Length
(Distance Cross (Distance
b=2 for Copper & unit Sinus Current in
between Power Section of between Watt= Voltage
Single 0.037 for the source (default {(acos(cosφ KW Amps Remarks
Factor the Cable the source KWx1000 Drop
Sr. No. Phase Aluminum value )} I=W/172
and the in mm² and the
Wiring & (Ambient appliance), 0.00008
appliance),
b=1 for Temp = 25 in meters ohm/m)
in meters
three Phase °C in (m) (m)
wiring ohm.mm/m
²

b ρ L Cos φ S λ L Sin φ I ∆V

1 2 3 4 5 6 7 8 9 10 11 12 13 14

1 2 0.037 150 0.8 400 0.00008 150 0.58779 350 350000 2034.88 73.88

Fix Value
Voltage Drop Calculations for 1-Phase Copper Cable
Resistivity
Length of
of the
Cable
material
Factor
conductor

Simple Simple
Length of Length of
Reactance
Cable Cable
0.023 for per Length
(Distance Cross (Distance
b=2 for Copper & unit Sinus Current in
between Power Section of between Watt= Voltage
Single 0.037 for the source (default {(acos(cosφ KW Amps Remarks
Factor the Cable the source KWx1000 Drop
Sr. No. Phase Aluminum value )} I=W/172
and the in mm² and the
Wiring & (Ambient appliance), 0.00008
appliance),
b=1 for Temp = 25 in meters ohm/m)
in meters
three Phase °C in (m) (m)
wiring ohm.mm/m
²

b ρ L Cos φ S λ L Sin φ I ∆V

1 2 3 4 5 6 7 8 9 10 11 12 13 14

1 2 0.023 150 0.8 400 0.00008 150 0.58779 350 350000 2034.88 56.79

Fix Value