Real Plaza Puruchuco

HVAC Load Analysis


for

Crisol

Prepared By:

Ing. Humberto Chavez Lozano -


Hch Proyectos

982 188 338


jueves, 3 de Noviembre de 2022
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 2

General Project Data Input


General Project Information
Project file name: D:\D v.22.07.3\0_NORMAS PATRON\01_ELITE
PRINCIPAL\2_ELITE_2022 CORRIDAS REPORTES\01 ELITE
LIMA corridas\22.11.03 CRISOL PURUCHUCO BENJA\REAL
PLAZA PURUCHUCO-CRISOL.CHV
Project title: Real Plaza Puruchuco
Project date: 2/11/2022
Weather reference city: LIMA
Client name: Crisol
Company name: Hch Proyectos
Company representative: Ing. Humberto Chavez Lozano -
Company phone: 982 188 338
Company e-mail address: hch.proyectos@gmail.com
Barometric pressure: 29.240 in.Hg.
Altitude: 636 feet
Latitude: -12 Degrees
Mean daily temperature range: 17 Degrees
Starting & ending time for HVAC load calculations: 7am - 10pm
Number of unique zones in this project: 1

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 2.00 Watts per square foot
Equipment requirements: 2.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 0 %
Zone latent safety factor: 0 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 2
Equipment profile number: 3
People profile number: 1
Building default ceiling height: 17.00 feet
Building default wall height: 19.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 0 0 0 C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
February 85 75 50% 75 51.79 -6
Winter 0 0

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 1 0.350 No No

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 C 0.350 M

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.330 5 20

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 1.100 1.000 2 0.640

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name: Fc-1
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 1.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 10.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 7.5 CFM/Pr, 0.06 CFM/sq.ft
Cooling infiltration: 0 Direct
Heating ventilation: 100% sup.
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
February 85 75 50% 75 51.79 -6
Winter 0 0

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 5

Building Envelope Report


Envelope Report Using Summer U-Factors
Material Gross Glass Net -U- Area x Average
Types Area Area Area Factor U-Factor U-Factor
Roof 1 1,700.1 0.0 1,700.1 0.350 595.028 0.350
Tot.Roof 1,700.1 0.0 1,700.1 N/A 595.028 0.350

Glass 1 28.0 N/A 28.0 1.000 28.000 1.000


Tot.Glass 28.0 N/A 28.0 N/A 28.000 1.000
Totals 1,728.1 623.028 0.361

Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 0.0 0.0 0.0 0.000 0.000 0.000
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 0.0 0.0 0.0 0.000 0.000 0.000
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 0.0 0.0 0.0 0.000 0.000 0.000
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 0.0 0.0 0.0 0.000 0.000 0.000
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 0.0 0.0 0.0 0.000 0.000 0.000

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 6

Building Summary Loads


Building peaks in February at 2pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 1,700 0 0.00 0 20,082 20,082 21.23
Wall 0 0 0.00 0 0 0 0.00
Glass 28 0 0.00 0 140 140 0.15
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 20,222 20,222 21.38
Lighting 3,400 0 0.00 0 11,602 11,602 12.27
Equipment 2,400 0 0.00 0 8,189 8,189 8.66
People 55 0 0.00 11,000 13,750 24,750 26.17
Partition 3,202 0 0.00 0 5,283 5,283 5.59
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 515 0 0.00 18,271 4,978 23,248 24.58
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 1,288 1,288 1.36
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 29,271 65,312 94,583 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 18,271 4,978 23,248 24.58
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 11,000 59,046 70,046 74.06
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 1,288 1,288 1.36
Building Totals 0 0.00 29,271 65,312 94,583 100.00

Check Figures
Total Building Supply Air (based on a 20° TD): 2,806 CFM
Total Building Vent. Air (18.33% of Supply): 515 CFM
Total Conditioned Air Space: 1,700 Sq.ft
Supply Air Per Unit Area: 1.6507 CFM/Sq.ft
Area Per Cooling Capacity: 215.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0046 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 7.88 Tons

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 7

Air Handler #1 - Fc-1 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Sala De Ventas 1,700 0 59,046 11,000 100% 7.5/P, 0.06/ft²
2pm February 55 0 2,806 0 0 515
28,901 0.00 1.65 0 0 515
Zone Peak Totals: 1,700 0 59,046 11,000
Total Zones: 1 55 0 2,806 0 0 515
Unique Zones: 1 28,901 0.00 1.65 0 0 515

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 8

Air Handler #1 - Fc-1 - Total Load Summary


Air Handler Description: Fc-1 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.52 HP
Fan Input: 85% motor and fan efficiency with 1 in. water across the fan
Sensible Heat Ratio: 0.84 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in February.
Outdoor Conditions: Clg: 84° DB, 75° WB, 118.81 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.977 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 59,046 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,288 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 60,335 Btuh
Cooling Supply Air: 60,335 / (.977 X 1.1 X 20) = 2,806 CFM
Summer Vent Outside Air (18.3% of supply) = 515 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,978 Btuh 515 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 4,978 Btuh
Total sensible gain on air handling system: 65,312 Btuh
Zone space latent gain: 11,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 18,271 Btuh
Total latent gain on air handling system: 29,271 Btuh
Total system sensible and latent gain: 94,583 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 2,806 CFM
Total Air Handler Vent. Air (18.33% of Supply): 515 CFM
Total Conditioned Air Space: 1,700 Sq.ft
Supply Air Per Unit Area: 1.6507 CFM/Sq.ft
Area Per Cooling Capacity: 215.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0046 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 7.88 Tons

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 9

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Sala De Ventas peaks (sensible) in February at 2pm, Air Handler 1 (Fc-1), Group 0, 158.0 x 10.8,
Construction Type: 1 (Light), SIDB: 75°F
Roof-1-1-No.Clg-L 1,700 0.50 33.8 0.350 20,082 0.000 0
Partition-1-1 1007 5/20 0.330 1,662 6.600 6,646
Partition-2-1 960 5/20 0.330 1,584 6.600 6,336
Partition-3-1 513 5/20 0.330 846 6.600 3,386
Partition-4-1 722 5/20 0.330 1,191 6.600 4,765
Gls-P-1-90-Tran 28.0 1.000 8 1.000 140 22.000 616
0%S-0-NS-Solar 28.0 1.000 0 0.000 0
Lights-Prof=2 3,400 1.000 11,602
Equipment-Prof=3 2,400 1.000 8,189 0
People-Prof=1 55.0 1.000 13,750 11,000
Sub-total 59,046 11,000 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 59,046 11,000 0

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 10

Air System #1 (Fc-1) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 60.144 55.000
Draw-Thru Fan 1,288 0.427 60
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 11,000 5.898 59,046 19.573 2,746
Sensible Reserve 0 0.000 0
Zone Condition 11,000 66.042 60,335 75.000 2,806
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 515 CFM 18,271 9.820 4,978 1.650
Blow-Thru Fan 0 0.000
Entering Coil Condition 29,271 75.863 65,312 76.650 2,806

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.977 x 1.10 x 2,806 x( 76.650 - 55.000 )= 65,312 Btuh


TLH = 0.977 x 0.68 x 2,806 x( 75.863 - 60.144 )= 29,314 Btuh
----------
SUM = 94,626 Btuh
GTH = 0.977 x 4.50 x 2,806 x( 30.266 - 22.528 )= 95,496 Btuh
Total System Load = 94,583 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 95,496 / ( 10.00 x 500 ) = 19.1 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.65 Dry bulb temperature: .00
Wet bulb temperature: 65.01
Relative humidity: 54.14
Enthalpy: 30.27 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: .00
Wet bulb temperature: 53.56
Relative humidity: 91.39
Enthalpy: 22.53 Btu/lbm

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 11

Air System #1 (Fc-1) Psychrometric Analysis (G)


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 60.144 55.000
Draw-Thru Fan 1,288 0.427 60
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 11,000 5.898 59,046 19.573 2,746
Sensible Reserve 0 0.000 0
Zone Condition 11,000 66.042 60,335 75.000 2,806
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 515 CFM 18,271 9.820 4,978 1.650
Blow-Thru Fan 0 0.000
Entering Coil Condition 29,271 75.863 65,312 76.650 2,806

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.977 x 1.10 x 2,806 x( 76.650 - 55.000 )= 65,312 Btuh


TLH = 0.977 x 0.68 x 2,806 x( 75.863 - 60.144 )= 29,314 Btuh
----------
SUM = 94,626 Btuh
GTH = 0.977 x 4.50 x 2,806 x( 30.266 - 22.528 )= 95,496 Btuh
Total System Load = 94,583 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 95,496 / ( 10.00 x 500 ) = 19.1 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.65 Dry bulb temperature: .00
Wet bulb temperature: 65.01
Relative humidity: 54.14
Enthalpy: 30.27 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: .00
Wet bulb temperature: 53.56
Relative humidity: 91.39
Enthalpy: 22.53 Btu/lbm

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 12

Air System #1 (Fc-1) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 13

Air System #1 (Fc-1) Psychrometric Chart (G)


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. Real Plaza Puruchuco
Barranquilla, Page 14

Building Pie Charts


Building peaks in February at 2pm.

Draw-Thru Fan - 1.36%

Roof - 21.23%
Cool. Vent. - 24.58%

Glass - 0.15%
Building
Net Gain
94,583 Lighting - 12.27%
Btuh
Partition - 5.59%

Equipment - 8.66%

People - 26.17%

D:\ ...\REAL PLAZA PURUCHUCO-CRISOL.CHV jueves, 3 de Noviembre de 2022, 12:03 p. m.