Hotel Iberostar
Lima
Prepared By:
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 8 0.126 No No
2 4 0.206 No No
3 8 0.126 No Yes
4 12 0.192 No Yes
5 13 1.080 No No
6 1 0.213 No Yes
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 C 0.490 L
2 G 0.081 L
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.381 8 10
2 0.081 8 10
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.270 0.270 0.546 2 0.420
2 0.490 0.380 0.420 2 0.420
Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 14,449.3 2,242.8 12,206.5 0.490 0.270 0.546
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 9,754.0 2,831.7 6,922.3 0.490 0.270 0.546
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 17,406.7 15,572.9 1,833.8 0.490 0.270 0.546
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 12,853.0 11,037.0 1,816.0 0.490 0.270 0.546
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 54,463.0 31,684.4 22,778.5 0.490 0.270 0.546
Check Figures
Total Building Supply Air (based on a 18° TD): 186,948 CFM
Total Building Vent. Air (6.29% of Supply): 11,751 CFM
Total Conditioned Air Space: 89,738 Sq.ft
Supply Air Per Unit Area: 2.0833 CFM/Sq.ft
Area Per Cooling Capacity: 259.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0039 Tons/Sq.ft
Heating Capacity Per Area: 20.10 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,803,660 Btuh
Total Cooling Required With Outside Air: 345.75 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,074 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 346 Sq.ft
Supply Air Per Unit Area: 3.1070 CFM/Sq.ft
Area Per Cooling Capacity: 186.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0054 Tons/Sq.ft
Heating Capacity Per Area: 8.66 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,991 Btuh
Total Cooling Required With Outside Air: 1.85 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 451 CFM
Total Air Handler Vent. Air (6.66% of Supply): 30 CFM
Total Conditioned Air Space: 106 Sq.ft
Supply Air Per Unit Area: 4.2425 CFM/Sq.ft
Area Per Cooling Capacity: 115.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0087 Tons/Sq.ft
Heating Capacity Per Area: 20.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,193 Btuh
Total Cooling Required With Outside Air: 0.92 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,391 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 112 Sq.ft
Supply Air Per Unit Area: 12.4302 CFM/Sq.ft
Area Per Cooling Capacity: 46.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0214 Tons/Sq.ft
Heating Capacity Per Area: 14.75 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,650 Btuh
Total Cooling Required With Outside Air: 2.40 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 628 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 129 Sq.ft
Supply Air Per Unit Area: 4.8730 CFM/Sq.ft
Area Per Cooling Capacity: 119.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0084 Tons/Sq.ft
Heating Capacity Per Area: 14.63 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,883 Btuh
Total Cooling Required With Outside Air: 1.08 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 868 CFM
Total Air Handler Vent. Air (40.05% of Supply): 348 CFM
Total Conditioned Air Space: 598 Sq.ft
Supply Air Per Unit Area: 1.4524 CFM/Sq.ft
Area Per Cooling Capacity: 158.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0063 Tons/Sq.ft
Heating Capacity Per Area: 22.02 Btuh/Sq.ft
Total Heating Required With Outside Air: 13,155 Btuh
Total Cooling Required With Outside Air: 3.78 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 561 CFM
Total Air Handler Vent. Air (13.68% of Supply): 77 CFM
Total Conditioned Air Space: 480 Sq.ft
Supply Air Per Unit Area: 1.1694 CFM/Sq.ft
Area Per Cooling Capacity: 329.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0030 Tons/Sq.ft
Heating Capacity Per Area: 17.22 Btuh/Sq.ft
Total Heating Required With Outside Air: 8,263 Btuh
Total Cooling Required With Outside Air: 1.46 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 574 CFM
Total Air Handler Vent. Air (15.37% of Supply): 88 CFM
Total Conditioned Air Space: 551 Sq.ft
Supply Air Per Unit Area: 1.0411 CFM/Sq.ft
Area Per Cooling Capacity: 358.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0028 Tons/Sq.ft
Heating Capacity Per Area: 13.22 Btuh/Sq.ft
Total Heating Required With Outside Air: 7,288 Btuh
Total Cooling Required With Outside Air: 1.54 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 175 CFM
Total Air Handler Vent. Air (12.24% of Supply): 21 CFM
Total Conditioned Air Space: 108 Sq.ft
Supply Air Per Unit Area: 1.6276 CFM/Sq.ft
Area Per Cooling Capacity: 244.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0041 Tons/Sq.ft
Heating Capacity Per Area: 26.02 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,803 Btuh
Total Cooling Required With Outside Air: 0.44 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 143 CFM
Total Air Handler Vent. Air (14.51% of Supply): 21 CFM
Total Conditioned Air Space: 96 Sq.ft
Supply Air Per Unit Area: 1.4866 CFM/Sq.ft
Area Per Cooling Capacity: 249.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0040 Tons/Sq.ft
Heating Capacity Per Area: 22.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,181 Btuh
Total Cooling Required With Outside Air: 0.39 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 69 CFM
Total Air Handler Vent. Air (8.96% of Supply): 6 CFM
Total Conditioned Air Space: 39 Sq.ft
Supply Air Per Unit Area: 1.7860 CFM/Sq.ft
Area Per Cooling Capacity: 244.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0041 Tons/Sq.ft
Heating Capacity Per Area: 32.45 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,256 Btuh
Total Cooling Required With Outside Air: 0.16 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 107 CFM
Total Air Handler Vent. Air (7.75% of Supply): 8 CFM
Total Conditioned Air Space: 69 Sq.ft
Supply Air Per Unit Area: 1.5482 CFM/Sq.ft
Area Per Cooling Capacity: 284.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Heating Capacity Per Area: 25.80 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,781 Btuh
Total Cooling Required With Outside Air: 0.24 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 452 CFM
Total Air Handler Vent. Air (2.96% of Supply): 13 CFM
Total Conditioned Air Space: 56 Sq.ft
Supply Air Per Unit Area: 8.0515 CFM/Sq.ft
Area Per Cooling Capacity: 64.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0155 Tons/Sq.ft
Heating Capacity Per Area: 33.92 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,902 Btuh
Total Cooling Required With Outside Air: 0.87 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 5,146 CFM
Total Air Handler Vent. Air (2.88% of Supply): 148 CFM
Total Conditioned Air Space: 705 Sq.ft
Supply Air Per Unit Area: 7.2979 CFM/Sq.ft
Area Per Cooling Capacity: 72.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0138 Tons/Sq.ft
Heating Capacity Per Area: 36.31 Btuh/Sq.ft
Total Heating Required With Outside Air: 25,600 Btuh
Total Cooling Required With Outside Air: 9.72 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 4,930 CFM
Total Air Handler Vent. Air (20.09% of Supply): 990 CFM
Total Conditioned Air Space: 1,294 Sq.ft
Supply Air Per Unit Area: 3.8111 CFM/Sq.ft
Area Per Cooling Capacity: 103.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0097 Tons/Sq.ft
Heating Capacity Per Area: 69.86 Btuh/Sq.ft
Total Heating Required With Outside Air: 90,377 Btuh
Total Cooling Required With Outside Air: 12.53 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 494 CFM
Total Air Handler Vent. Air (31.28% of Supply): 154 CFM
Total Conditioned Air Space: 468 Sq.ft
Supply Air Per Unit Area: 1.0550 CFM/Sq.ft
Area Per Cooling Capacity: 280.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0036 Tons/Sq.ft
Heating Capacity Per Area: 6.42 Btuh/Sq.ft
Total Heating Required With Outside Air: 3,006 Btuh
Total Cooling Required With Outside Air: 1.67 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,991 CFM
Total Air Handler Vent. Air (7.73% of Supply): 154 CFM
Total Conditioned Air Space: 483 Sq.ft
Supply Air Per Unit Area: 4.1213 CFM/Sq.ft
Area Per Cooling Capacity: 117.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0085 Tons/Sq.ft
Heating Capacity Per Area: 36.85 Btuh/Sq.ft
Total Heating Required With Outside Air: 17,805 Btuh
Total Cooling Required With Outside Air: 4.10 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,227 CFM
Total Air Handler Vent. Air (26.08% of Supply): 320 CFM
Total Conditioned Air Space: 832 Sq.ft
Supply Air Per Unit Area: 1.4746 CFM/Sq.ft
Area Per Cooling Capacity: 231.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0043 Tons/Sq.ft
Heating Capacity Per Area: 39.40 Btuh/Sq.ft
Total Heating Required With Outside Air: 32,786 Btuh
Total Cooling Required With Outside Air: 3.60 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 2,630 CFM
Total Air Handler Vent. Air (9.46% of Supply): 249 CFM
Total Conditioned Air Space: 812 Sq.ft
Supply Air Per Unit Area: 3.2373 CFM/Sq.ft
Area Per Cooling Capacity: 146.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0068 Tons/Sq.ft
Heating Capacity Per Area: 31.62 Btuh/Sq.ft
Total Heating Required With Outside Air: 25,685 Btuh
Total Cooling Required With Outside Air: 5.55 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 2,682 CFM
Total Air Handler Vent. Air (9.45% of Supply): 253 CFM
Total Conditioned Air Space: 890 Sq.ft
Supply Air Per Unit Area: 3.0139 CFM/Sq.ft
Area Per Cooling Capacity: 155.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 31.08 Btuh/Sq.ft
Total Heating Required With Outside Air: 27,654 Btuh
Total Cooling Required With Outside Air: 5.71 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 2,216 CFM
Total Air Handler Vent. Air (7.50% of Supply): 166 CFM
Total Conditioned Air Space: 1,040 Sq.ft
Supply Air Per Unit Area: 2.1322 CFM/Sq.ft
Area Per Cooling Capacity: 234.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0043 Tons/Sq.ft
Heating Capacity Per Area: 19.06 Btuh/Sq.ft
Total Heating Required With Outside Air: 19,815 Btuh
Total Cooling Required With Outside Air: 4.44 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 226 CFM
Total Air Handler Vent. Air (11.29% of Supply): 26 CFM
Total Conditioned Air Space: 160 Sq.ft
Supply Air Per Unit Area: 1.4168 CFM/Sq.ft
Area Per Cooling Capacity: 282.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Heating Capacity Per Area: 33.01 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,273 Btuh
Total Cooling Required With Outside Air: 0.56 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 548 CFM
Total Air Handler Vent. Air (4.86% of Supply): 27 CFM
Total Conditioned Air Space: 444 Sq.ft
Supply Air Per Unit Area: 1.2340 CFM/Sq.ft
Area Per Cooling Capacity: 387.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0026 Tons/Sq.ft
Heating Capacity Per Area: 20.43 Btuh/Sq.ft
Total Heating Required With Outside Air: 9,069 Btuh
Total Cooling Required With Outside Air: 1.15 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 207 CFM
Total Air Handler Vent. Air (14.48% of Supply): 30 CFM
Total Conditioned Air Space: 167 Sq.ft
Supply Air Per Unit Area: 1.2401 CFM/Sq.ft
Area Per Cooling Capacity: 346.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0029 Tons/Sq.ft
Heating Capacity Per Area: 28.77 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,813 Btuh
Total Cooling Required With Outside Air: 0.48 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 211 CFM
Total Air Handler Vent. Air (13.27% of Supply): 28 CFM
Total Conditioned Air Space: 175 Sq.ft
Supply Air Per Unit Area: 1.2061 CFM/Sq.ft
Area Per Cooling Capacity: 366.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0027 Tons/Sq.ft
Heating Capacity Per Area: 27.61 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,826 Btuh
Total Cooling Required With Outside Air: 0.48 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 666 CFM
Total Air Handler Vent. Air (4.13% of Supply): 27 CFM
Total Conditioned Air Space: 291 Sq.ft
Supply Air Per Unit Area: 2.2856 CFM/Sq.ft
Area Per Cooling Capacity: 235.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0042 Tons/Sq.ft
Heating Capacity Per Area: 20.82 Btuh/Sq.ft
Total Heating Required With Outside Air: 6,063 Btuh
Total Cooling Required With Outside Air: 1.24 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 626 CFM
Total Air Handler Vent. Air (4.21% of Supply): 26 CFM
Total Conditioned Air Space: 273 Sq.ft
Supply Air Per Unit Area: 2.2949 CFM/Sq.ft
Area Per Cooling Capacity: 234.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0043 Tons/Sq.ft
Heating Capacity Per Area: 17.53 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,779 Btuh
Total Cooling Required With Outside Air: 1.16 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,043 CFM
Total Air Handler Vent. Air (2.64% of Supply): 28 CFM
Total Conditioned Air Space: 293 Sq.ft
Supply Air Per Unit Area: 3.5639 CFM/Sq.ft
Area Per Cooling Capacity: 156.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 18.69 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,472 Btuh
Total Cooling Required With Outside Air: 1.87 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 520 CFM
Total Air Handler Vent. Air (4.94% of Supply): 26 CFM
Total Conditioned Air Space: 261 Sq.ft
Supply Air Per Unit Area: 1.9901 CFM/Sq.ft
Area Per Cooling Capacity: 280.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0036 Tons/Sq.ft
Heating Capacity Per Area: 18.62 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,861 Btuh
Total Cooling Required With Outside Air: 0.93 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 542 CFM
Total Air Handler Vent. Air (4.74% of Supply): 26 CFM
Total Conditioned Air Space: 261 Sq.ft
Supply Air Per Unit Area: 2.0748 CFM/Sq.ft
Area Per Cooling Capacity: 260.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0038 Tons/Sq.ft
Heating Capacity Per Area: 22.07 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,762 Btuh
Total Cooling Required With Outside Air: 1.00 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 404 CFM
Total Air Handler Vent. Air (6.66% of Supply): 27 CFM
Total Conditioned Air Space: 281 Sq.ft
Supply Air Per Unit Area: 1.4355 CFM/Sq.ft
Area Per Cooling Capacity: 366.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0027 Tons/Sq.ft
Heating Capacity Per Area: 21.58 Btuh/Sq.ft
Total Heating Required With Outside Air: 6,069 Btuh
Total Cooling Required With Outside Air: 0.77 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 381 CFM
Total Air Handler Vent. Air (7.05% of Supply): 27 CFM
Total Conditioned Air Space: 281 Sq.ft
Supply Air Per Unit Area: 1.3565 CFM/Sq.ft
Area Per Cooling Capacity: 378.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0026 Tons/Sq.ft
Heating Capacity Per Area: 17.49 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,917 Btuh
Total Cooling Required With Outside Air: 0.74 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 503 CFM
Total Air Handler Vent. Air (5.15% of Supply): 26 CFM
Total Conditioned Air Space: 266 Sq.ft
Supply Air Per Unit Area: 1.8951 CFM/Sq.ft
Area Per Cooling Capacity: 283.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Heating Capacity Per Area: 22.04 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,856 Btuh
Total Cooling Required With Outside Air: 0.94 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 447 CFM
Total Air Handler Vent. Air (5.80% of Supply): 26 CFM
Total Conditioned Air Space: 266 Sq.ft
Supply Air Per Unit Area: 1.6826 CFM/Sq.ft
Area Per Cooling Capacity: 316.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0032 Tons/Sq.ft
Heating Capacity Per Area: 18.16 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,823 Btuh
Total Cooling Required With Outside Air: 0.84 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 316 CFM
Total Air Handler Vent. Air (4.97% of Supply): 16 CFM
Total Conditioned Air Space: 262 Sq.ft
Supply Air Per Unit Area: 1.2084 CFM/Sq.ft
Area Per Cooling Capacity: 373.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0027 Tons/Sq.ft
Heating Capacity Per Area: 16.24 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,253 Btuh
Total Cooling Required With Outside Air: 0.70 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 626 CFM
Total Air Handler Vent. Air (5.10% of Supply): 32 CFM
Total Conditioned Air Space: 532 Sq.ft
Supply Air Per Unit Area: 1.1774 CFM/Sq.ft
Area Per Cooling Capacity: 381.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0026 Tons/Sq.ft
Heating Capacity Per Area: 15.47 Btuh/Sq.ft
Total Heating Required With Outside Air: 8,230 Btuh
Total Cooling Required With Outside Air: 1.39 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 180 CFM
Total Air Handler Vent. Air (5.21% of Supply): 9 CFM
Total Conditioned Air Space: 156 Sq.ft
Supply Air Per Unit Area: 1.1506 CFM/Sq.ft
Area Per Cooling Capacity: 388.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0026 Tons/Sq.ft
Heating Capacity Per Area: 14.81 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,314 Btuh
Total Cooling Required With Outside Air: 0.40 Tons
Air Handler #42 - Oficio & Vestibulo Servicio P3 - Total Load Summary
Air Handler Description: Oficio & Vestibulo Servicio P3 Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.07 HP
Fan Input: 65% motor and fan efficiency with 1.5 in. water across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 15 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: Clg: 86° DB, 75° WB, 113.83 grains, Htg: 55° DB
Indoor Conditions: Clg: 73° DB, 50% RH, Htg: 73° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 3,814 Btuh
Infiltration sensible loss: 3 Btuh 0 CFM
Outside Air sensible loss: 511 Btuh 26 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 4,329 Btuh
Heating Supply Air: 3,818 / (.998 X 1.08 X 11) = 330 CFM
Winter Vent Outside Air (8.0% of supply) = 26 CFM
Zone space sensible gain: 3,932 Btuh
Infiltration sensible gain: 2 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 3,935 Btuh
Cooling Supply Air: 3,935 / (.998 X 1.1 X 18) = 199 CFM
Summer Vent Outside Air (13.2% of supply) = 26 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 376 Btuh 26 CFM
Blow-thru fan sensible gain: 183 Btuh
Total sensible gain on return side of coil: 559 Btuh
Total sensible gain on air handling system: 4,494 Btuh
Zone space latent gain: 658 Btuh
Infiltration latent gain: 6 Btuh
Outside air latent gain: 946 Btuh
Total latent gain on air handling system: 1,611 Btuh
Total system sensible and latent gain: 6,104 Btuh
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 199 CFM
Total Air Handler Vent. Air (13.23% of Supply): 26 CFM
Total Conditioned Air Space: 165 Sq.ft
Supply Air Per Unit Area: 1.2094 CFM/Sq.ft
Area Per Cooling Capacity: 323.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0031 Tons/Sq.ft
Heating Capacity Per Area: 26.30 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,329 Btuh
Total Cooling Required With Outside Air: 0.51 Tons
Air Handler #43 - Junior Suite X07 P13 - Total Load Summary
Air Handler Description: Junior Suite X07 P13 Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.55 HP
Fan Input: 65% motor and fan efficiency with 1.5 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 3 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: Clg: 85° DB, 75° WB, 115.15 grains, Htg: 55° DB
Indoor Conditions: Clg: 73° DB, 50% RH, Htg: 73° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 4,028 Btuh
Infiltration sensible loss: 7 Btuh 0 CFM
Outside Air sensible loss: 2,536 Btuh 32 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 6,572 Btuh
Heating Supply Air: 4,035 / (.998 X 1.08 X 11) = 330 CFM
Winter Vent Outside Air (9.8% of supply) = 32 CFM
Zone space sensible gain: 29,731 Btuh
Infiltration sensible gain: 5 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 29,736 Btuh
Cooling Supply Air: 29,736 / (.998 X 1.1 X 18) = 1,505 CFM
Summer Vent Outside Air (2.1% of supply) = 32 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 71 Btuh 32 CFM
Blow-thru fan sensible gain: 1,384 Btuh
Total sensible gain on return side of coil: 1,455 Btuh
Total sensible gain on air handling system: 31,191 Btuh
Zone space latent gain: 200 Btuh
Infiltration latent gain: 14 Btuh
Outside air latent gain: 682 Btuh
Total latent gain on air handling system: 896 Btuh
Total system sensible and latent gain: 32,086 Btuh
Pretreated air sensible loss: -1,911 Btuh
Pretreated air sensible gain: 354 Btuh
Pretreated air latent gain: 512 Btuh
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,505 CFM
Total Air Handler Vent. Air (2.14% of Supply): 32 CFM
Total Conditioned Air Space: 371 Sq.ft
Supply Air Per Unit Area: 4.0608 CFM/Sq.ft
Area Per Cooling Capacity: 138.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0072 Tons/Sq.ft
Heating Capacity Per Area: 17.74 Btuh/Sq.ft
Total Heating Required With Outside Air: 6,572 Btuh
Total Cooling Required With Outside Air: 2.67 Tons
Air Handler #44 - Junior Suite X08 P13 - Total Load Summary
Air Handler Description: Junior Suite X08 P13 Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.32 HP
Fan Input: 65% motor and fan efficiency with 1.5 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 3 time(s) in the building. ---
Air System Peak Time: 2pm in January.
Outdoor Conditions: Clg: 85° DB, 75° WB, 114.71 grains, Htg: 55° DB
Indoor Conditions: Clg: 73° DB, 50% RH, Htg: 73° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 5,201 Btuh
Infiltration sensible loss: 9 Btuh 0 CFM
Outside Air sensible loss: 3,040 Btuh 39 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 8,250 Btuh
Heating Supply Air: 5,210 / (.998 X 1.08 X 15) = 330 CFM
Winter Vent Outside Air (11.7% of supply) = 39 CFM
Zone space sensible gain: 17,520 Btuh
Infiltration sensible gain: 6 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 17,526 Btuh
Cooling Supply Air: 17,526 / (.998 X 1.1 X 18) = 887 CFM
Summer Vent Outside Air (4.4% of supply) = 39 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 85 Btuh 39 CFM
Blow-thru fan sensible gain: 816 Btuh
Total sensible gain on return side of coil: 900 Btuh
Total sensible gain on air handling system: 18,427 Btuh
Zone space latent gain: 200 Btuh
Infiltration latent gain: 18 Btuh
Outside air latent gain: 817 Btuh
Total latent gain on air handling system: 1,035 Btuh
Total system sensible and latent gain: 19,461 Btuh
Pretreated air sensible loss: -2,290 Btuh
Pretreated air sensible gain: 466 Btuh
Pretreated air latent gain: 571 Btuh
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 887 CFM
Total Air Handler Vent. Air (4.36% of Supply): 39 CFM
Total Conditioned Air Space: 477 Sq.ft
Supply Air Per Unit Area: 1.8588 CFM/Sq.ft
Area Per Cooling Capacity: 294.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0034 Tons/Sq.ft
Heating Capacity Per Area: 17.29 Btuh/Sq.ft
Total Heating Required With Outside Air: 8,250 Btuh
Total Cooling Required With Outside Air: 1.62 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 316 CFM
Total Air Handler Vent. Air (4.97% of Supply): 16 CFM
Total Conditioned Air Space: 262 Sq.ft
Supply Air Per Unit Area: 1.2084 CFM/Sq.ft
Area Per Cooling Capacity: 373.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0027 Tons/Sq.ft
Heating Capacity Per Area: 16.24 Btuh/Sq.ft
Total Heating Required With Outside Air: 4,253 Btuh
Total Cooling Required With Outside Air: 0.70 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 461 CFM
Total Air Handler Vent. Air (5.05% of Supply): 23 CFM
Total Conditioned Air Space: 388 Sq.ft
Supply Air Per Unit Area: 1.1886 CFM/Sq.ft
Area Per Cooling Capacity: 379.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0026 Tons/Sq.ft
Heating Capacity Per Area: 15.37 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,958 Btuh
Total Cooling Required With Outside Air: 1.02 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 5,734 CFM
Total Air Handler Vent. Air (10.98% of Supply): 630 CFM
Total Conditioned Air Space: 1,749 Sq.ft
Supply Air Per Unit Area: 3.2785 CFM/Sq.ft
Area Per Cooling Capacity: 125.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0080 Tons/Sq.ft
Heating Capacity Per Area: 17.17 Btuh/Sq.ft
Total Heating Required With Outside Air: 30,032 Btuh
Total Cooling Required With Outside Air: 13.93 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 3,245 CFM
Total Air Handler Vent. Air (7.13% of Supply): 231 CFM
Total Conditioned Air Space: 771 Sq.ft
Supply Air Per Unit Area: 4.2063 CFM/Sq.ft
Area Per Cooling Capacity: 113.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0088 Tons/Sq.ft
Heating Capacity Per Area: 18.91 Btuh/Sq.ft
Total Heating Required With Outside Air: 14,593 Btuh
Total Cooling Required With Outside Air: 6.82 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 231 CFM
Total Air Handler Vent. Air (3.88% of Supply): 9 CFM
Total Conditioned Air Space: 149 Sq.ft
Supply Air Per Unit Area: 1.5483 CFM/Sq.ft
Area Per Cooling Capacity: 306.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0033 Tons/Sq.ft
Heating Capacity Per Area: 24.64 Btuh/Sq.ft
Total Heating Required With Outside Air: 3,672 Btuh
Total Cooling Required With Outside Air: 0.49 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 368 CFM
Total Air Handler Vent. Air (3.90% of Supply): 14 CFM
Total Conditioned Air Space: 240 Sq.ft
Supply Air Per Unit Area: 1.5366 CFM/Sq.ft
Area Per Cooling Capacity: 309.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0032 Tons/Sq.ft
Heating Capacity Per Area: 23.46 Btuh/Sq.ft
Total Heating Required With Outside Air: 5,620 Btuh
Total Cooling Required With Outside Air: 0.77 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 153 CFM
Total Air Handler Vent. Air (12.04% of Supply): 18 CFM
Total Conditioned Air Space: 115 Sq.ft
Supply Air Per Unit Area: 1.3293 CFM/Sq.ft
Area Per Cooling Capacity: 302.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0033 Tons/Sq.ft
Heating Capacity Per Area: 21.17 Btuh/Sq.ft
Total Heating Required With Outside Air: 2,437 Btuh
Total Cooling Required With Outside Air: 0.38 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 997 CFM
Total Air Handler Vent. Air (3.93% of Supply): 39 CFM
Total Conditioned Air Space: 320 Sq.ft
Supply Air Per Unit Area: 3.1156 CFM/Sq.ft
Area Per Cooling Capacity: 169.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0059 Tons/Sq.ft
Heating Capacity Per Area: 11.85 Btuh/Sq.ft
Total Heating Required With Outside Air: 3,793 Btuh
Total Cooling Required With Outside Air: 1.89 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 1,858 CFM
Total Air Handler Vent. Air (14.94% of Supply): 278 CFM
Total Conditioned Air Space: 542 Sq.ft
Supply Air Per Unit Area: 3.4252 CFM/Sq.ft
Area Per Cooling Capacity: 108.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0092 Tons/Sq.ft
Heating Capacity Per Area: 20.74 Btuh/Sq.ft
Total Heating Required With Outside Air: 11,249 Btuh
Total Cooling Required With Outside Air: 5.01 Tons
Air Handler #54 - Oficio & Vestibulo Servicio Az - Total Load Summary
Air Handler Description: Oficio & Vestibulo Servicio Az Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.07 HP
Fan Input: 65% motor and fan efficiency with 1.5 in. water across the fan
Sensible Heat Ratio: 0.87 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in January.
Outdoor Conditions: Clg: 85° DB, 75° WB, 114.71 grains, Htg: 55° DB
Indoor Conditions: Clg: 73° DB, 50% RH, Htg: 73° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 2,955 Btuh
Infiltration sensible loss: 3 Btuh 0 CFM
Outside Air sensible loss: 452 Btuh 23 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 3,410 Btuh
Heating Supply Air: 2,958 / (.998 X 1.08 X 8) = 330 CFM
Winter Vent Outside Air (7.1% of supply) = 23 CFM
Zone space sensible gain: 3,900 Btuh
Infiltration sensible gain: 2 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 3,902 Btuh
Cooling Supply Air: 3,920 / (.998 X 1.1 X 18) = 198 CFM
Summer Vent Outside Air (11.7% of supply) = 23 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 333 Btuh 23 CFM
Blow-thru fan sensible gain: 182 Btuh
Total sensible gain on return side of coil: 515 Btuh
Total sensible gain on air handling system: 4,417 Btuh
Zone space latent gain: 583 Btuh
Infiltration latent gain: 5 Btuh
Outside air latent gain: 863 Btuh
Total latent gain on air handling system: 1,451 Btuh
Total system sensible and latent gain: 5,868 Btuh
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 198 CFM
Total Air Handler Vent. Air (11.75% of Supply): 23 CFM
Total Conditioned Air Space: 146 Sq.ft
Supply Air Per Unit Area: 1.3618 CFM/Sq.ft
Area Per Cooling Capacity: 297.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0034 Tons/Sq.ft
Heating Capacity Per Area: 23.41 Btuh/Sq.ft
Total Heating Required With Outside Air: 3,410 Btuh
Total Cooling Required With Outside Air: 0.49 Tons
7.5/P, 7.5/P,
Hall Ascensores P1 156 3,116 4,315 1,377
13 0.18/ft² 0.18/ft²
3pm March 3 75 218 0
52 52
1,874 0.48 1.40 0
75 45
7.5/P, 7.5/P,
Web Corner P1 38 1,419 9,753 758
15 0.18/ft² 0.18/ft²
2pm December 3 34 493 0
29 29
459 0.90 12.89 0
34 102
7.5/P, 7.5/P,
Lobby Bar P1 753 9,355 18,516 8,155
17 0.18/ft² 0.18/ft²
4pm January 20 226 937 0
286 286
9,034 0.30 1.24 0
226 194
7.5/P, 7.5/P,
Back Office P1 64 1,759 2,584 908
18 0.18/ft² 0.18/ft²
3pm March 3 43 131 0
34 34
768 0.66 2.04 0
43 27
7.5/P, 7.5/P,
Uma P1 1 18 26 9
55 0.18/ft² 0.18/ft²
3pm March 0 0 1 0
0 0
1 0.44 1.32 0
0 0
Zone Peak Totals: 1,310 20,643 50,412 13,846
Total Zones: 6 35 499 2,551 0 499 499
Unique Zones: 6 15,705 0.38 1.95 0 499 529
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 2,404 CFM
Total Air Handler Vent. Air (20.76% of Supply): 499 CFM
Total Conditioned Air Space: 1,310 Sq.ft
Supply Air Per Unit Area: 1.8355 CFM/Sq.ft
Area Per Cooling Capacity: 175.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0057 Tons/Sq.ft
Heating Capacity Per Area: 23.15 Btuh/Sq.ft
Total Heating Required With Outside Air: 30,324 Btuh
Total Cooling Required With Outside Air: 7.46 Tons
Air System #42 (Oficio & Vestibulo Servicio P3) Psychrometric Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain MR Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
MIX Mixed Air Condition RML Return Miscellaneous Latent Gain
Air System #54 (Oficio & Vestibulo Servicio Az) Psychrometric Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain MR Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
MIX Mixed Air Condition RML Return Miscellaneous Latent Gain