MIDTOWN 400 BLOQUE C

HVAC Load Analysis


for

Promotres Inmobiliarios Pronobis S. A.


Executive Center. Ave Jpaquin Orrantia Y
Guyaquil , Guayss

Prepared By:

Oscar Arias
Mechanical Proyevts
Urb. San Gabriel Mz 4 Villa 7
Duran , Guayas
0988871110
sábado, septiembre 17, 2022
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 2

General Project Data Input


General Project Information
Project file name: MP-Pronobis Midtown 400 Bloque C.CHV
Project title: MIDTOWN 400 BLOQUE C
Project address: Entre Rios
Project city, state, ZIP: Guayaquil, Guyas
Designed by: Oscar Arias
Project date: sábado, septiembre 17, 2022
Weather reference city: GUAYAQUIL, EQUADOR
Client name: Promotres Inmobiliarios Pronobis S. A.
Client address: Executive Center. Ave Jpaquin Orrantia Y
Client city: Guyaquil , Guayss
Client phone: 042168555
Company name: Mechanical Proyevts
Company representative: Oscar Arias
Company address: Urb. San Gabriel Mz 4 Villa 7
Company city: Duran , Guayas
Company phone: 0988871110
Company e-mail address: oscar.arias@mechanicalproyectssa.com
Barometric pressure: 29.890 in.Hg.
Altitude: 29 feet
Latitude: 2 Degrees
Mean daily temperature range: 13.3 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 15

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.00 Watts per square foot
Equipment requirements: 1.50 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 11.15 feet
Building default wall height: 9.84 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 91 76 60% 73 38.61 4
Winter 68 73

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 1 0.330 No Yes
Roof #1 Description: Flat roof, steel deck with no insulation, suspended ceiling below with no insulation

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 F 0.323 M
Wall #1 Description: Block wall, 4" sand & gravel, hollow core, bare block exterior, interior finish

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.323 10 10
Partition #1 Description: Block partition, 4" sand & gravel, hollow core, bare block exterior, interior finish

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.800 0.830 0.920 2 0.000

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 4

Air Handler #1 - PB Local 10 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
PB Local 10 897 0 40,028 7,040 None
1 0.18/ft²
2pm August 32 0 2,308 0 0
401
8,826 0.00 2.57 0 0
401
Zone Peak Totals: 897 0 40,028 7,040
Total Zones: 1 32 0 2,308 0 0 401
Unique Zones: 1 8,826 0.00 2.57 0 0 401

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 5

Air Handler #1 - PB Local 10 - Total Load Summary


Air Handler Description: PB Local 10 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.22 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.85 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 112.01 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 40,028 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 552 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 40,580 Btuh
Cooling Supply Air: 40,580 / (.999 X 1.1 X 16) = 2,308 CFM
Summer Vent Outside Air (17.4% of supply) = 401 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 7,941 Btuh 401 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 7,941 Btuh
Total sensible gain on air handling system: 48,520 Btuh
Zone space latent gain: 7,040 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 10,531 Btuh
Total latent gain on air handling system: 17,571 Btuh
Total system sensible and latent gain: 66,091 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 2,308 CFM
Total Air Handler Vent. Air (17.39% of Supply): 401 CFM
Total Conditioned Air Space: 897 Sq.ft
Supply Air Per Unit Area: 2.5731 CFM/Sq.ft
Area Per Cooling Capacity: 162.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 5.51 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 6

Air Handler #2 - Mz Local 10 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
Mz Local 10 925 0 46,107 7,040 None
2 0.18/ft²
3pm August 32 0 2,659 0 0
407
9,102 0.00 2.87 0 0
407
Zone Peak Totals: 925 0 46,107 7,040
Total Zones: 1 32 0 2,659 0 0 407
Unique Zones: 1 9,102 0.00 2.87 0 0 407

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 7

Air Handler #2 - Mz Local 10 - Total Load Summary


Air Handler Description: Mz Local 10 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.25 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.87 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 46,107 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 636 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 46,743 Btuh
Cooling Supply Air: 46,743 / (.999 X 1.1 X 16) = 2,659 CFM
Summer Vent Outside Air (15.3% of supply) = 407 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 8,040 Btuh 407 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 8,040 Btuh
Total sensible gain on air handling system: 54,783 Btuh
Zone space latent gain: 7,040 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 10,663 Btuh
Total latent gain on air handling system: 17,703 Btuh
Total system sensible and latent gain: 72,486 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 2,659 CFM
Total Air Handler Vent. Air (15.29% of Supply): 407 CFM
Total Conditioned Air Space: 925 Sq.ft
Supply Air Per Unit Area: 2.8742 CFM/Sq.ft
Area Per Cooling Capacity: 153.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0065 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.04 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 8

Air Handler #3 - Lobby De Acceso Oficina - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
Lobby Acceso Ofinas 435 0 21,992 2,200 None
3 0.18/ft²
3pm August 10 0 1,354 0 0
153
4,280 0.00 3.11 0 0
153
Zone Peak Totals: 435 0 21,992 2,200
Total Zones: 1 10 0 1,354 0 0 153
Unique Zones: 1 4,280 0.00 3.11 0 0 153

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 9

Air Handler #3 - Lobby De Acceso Oficina - Total Load Summary


Air Handler Description: Lobby De Acceso Oficina Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.13 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 21,992 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 324 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 22,316 Btuh
Cooling Supply Air: 22,316 / (.999 X 1.1 X 15) = 1,354 CFM
Summer Vent Outside Air (11.3% of supply) = 153 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 3,032 Btuh 153 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 3,032 Btuh
Total sensible gain on air handling system: 25,349 Btuh
Zone space latent gain: 2,200 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,021 Btuh
Total latent gain on air handling system: 6,221 Btuh
Total system sensible and latent gain: 31,570 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 1,354 CFM
Total Air Handler Vent. Air (11.32% of Supply): 153 CFM
Total Conditioned Air Space: 435 Sq.ft
Supply Air Per Unit Area: 3.1124 CFM/Sq.ft
Area Per Cooling Capacity: 165.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0060 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.63 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 10

Air Handler #4 - PB Local 11 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
PB Local 11 897 0 40,028 7,040 None
4 0.18/ft²
2pm August 32 0 2,308 0 0
401
8,826 0.00 2.57 0 0
401
Zone Peak Totals: 897 0 40,028 7,040
Total Zones: 1 32 0 2,308 0 0 401
Unique Zones: 1 8,826 0.00 2.57 0 0 401

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 11

Air Handler #4 - PB Local 11 - Total Load Summary


Air Handler Description: PB Local 11 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.22 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.85 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 112.01 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 40,028 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 552 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 40,580 Btuh
Cooling Supply Air: 40,580 / (.999 X 1.1 X 16) = 2,308 CFM
Summer Vent Outside Air (17.4% of supply) = 401 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 7,941 Btuh 401 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 7,941 Btuh
Total sensible gain on air handling system: 48,520 Btuh
Zone space latent gain: 7,040 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 10,531 Btuh
Total latent gain on air handling system: 17,571 Btuh
Total system sensible and latent gain: 66,091 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 2,308 CFM
Total Air Handler Vent. Air (17.39% of Supply): 401 CFM
Total Conditioned Air Space: 897 Sq.ft
Supply Air Per Unit Area: 2.5731 CFM/Sq.ft
Area Per Cooling Capacity: 162.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 5.51 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 12

Air Handler #5 - Mz Local 11 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
Mz Local 11 529 0 49,613 4,400 None
5 0.18/ft²
1pm August 20 0 3,054 0 0
245
5,205 0.00 5.77 0 0
245
Zone Peak Totals: 529 0 49,613 4,400
Total Zones: 1 20 0 3,054 0 0 245
Unique Zones: 1 5,205 0.00 5.77 0 0 245

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 13

Air Handler #5 - Mz Local 11 - Total Load Summary


Air Handler Description: Mz Local 11 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.29 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 1pm in August.
Outdoor Conditions: Clg: 90° DB, 76° WB, 113.75 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 49,613 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 731 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 50,344 Btuh
Cooling Supply Air: 50,344 / (.999 X 1.1 X 15) = 3,054 CFM
Summer Vent Outside Air (8.0% of supply) = 245 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,581 Btuh 245 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 4,581 Btuh
Total sensible gain on air handling system: 54,925 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 6,704 Btuh
Total latent gain on air handling system: 11,104 Btuh
Total system sensible and latent gain: 66,029 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 3,054 CFM
Total Air Handler Vent. Air (8.03% of Supply): 245 CFM
Total Conditioned Air Space: 529 Sq.ft
Supply Air Per Unit Area: 5.7737 CFM/Sq.ft
Area Per Cooling Capacity: 96.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0104 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 5.50 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 14

Air Handler #6 - Oficina D 101-201 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
6 Oficina D 101-201 516 0 27,170 4,400 None 5/P, 0.06/ft²
6pm August 20 0 1,567 0 0 131
5,077 0.00 3.04 0 0 131
Zone Peak Totals: 516 0 27,170 4,400
Total Zones: 1 20 0 1,567 0 0 131
Unique Zones: 1 5,077 0.00 3.04 0 0 131

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 15

Air Handler #6 - Oficina D 101-201 - Total Load Summary


Air Handler Description: Oficina D 101-201 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.15 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 26,850 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 375 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 27,225 Btuh
Cooling Supply Air: 27,545 / (.999 X 1.1 X 16) = 1,567 CFM
Summer Vent Outside Air (8.4% of supply) = 131 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,590 Btuh 131 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,590 Btuh
Total sensible gain on air handling system: 29,816 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,435 Btuh
Total latent gain on air handling system: 7,835 Btuh
Total system sensible and latent gain: 37,651 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 1,567 CFM
Total Air Handler Vent. Air (8.36% of Supply): 131 CFM
Total Conditioned Air Space: 516 Sq.ft
Supply Air Per Unit Area: 3.0362 CFM/Sq.ft
Area Per Cooling Capacity: 164.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.14 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 16

Air Handler #7 - Oficina D 102-202 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7 Oficina D 102-202 441 0 19,036 4,400 None 5/P, 0.06/ft²
6pm August 20 0 1,032 0 0 126
4,339 0.00 2.34 0 0 126
Zone Peak Totals: 441 0 19,036 4,400
Total Zones: 1 20 0 1,032 0 0 126
Unique Zones: 1 4,339 0.00 2.34 0 0 126

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 17

Air Handler #7 - Oficina D 102-202 - Total Load Summary


Air Handler Description: Oficina D 102-202 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.10 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.81 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 18,882 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 247 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 19,129 Btuh
Cooling Supply Air: 19,284 / (.999 X 1.1 X 17) = 1,032 CFM
Summer Vent Outside Air (12.3% of supply) = 126 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,501 Btuh 126 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,501 Btuh
Total sensible gain on air handling system: 21,631 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,317 Btuh
Total latent gain on air handling system: 7,717 Btuh
Total system sensible and latent gain: 29,348 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 1,032 CFM
Total Air Handler Vent. Air (12.25% of Supply): 126 CFM
Total Conditioned Air Space: 441 Sq.ft
Supply Air Per Unit Area: 2.3407 CFM/Sq.ft
Area Per Cooling Capacity: 180.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0055 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.45 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 18

Air Handler #8 - Oficina D 103-203-303 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
Oficina D 103-203-
612 0 18,315 4,400 None 5/P, 0.06/ft²
8 303
20 0 993 0 0 137
2pm August
6,022 0.00 1.62 0 0 137

Zone Peak Totals: 612 0 18,315 4,400


Total Zones: 1 20 0 993 0 0 137
Unique Zones: 1 6,022 0.00 1.62 0 0 137

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 19

Air Handler #8 - Oficina D 103-203-303 - Total Load Summary


Air Handler Description: Oficina D 103-203-303 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.09 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.81 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 112.01 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 18,315 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 238 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 18,553 Btuh
Cooling Supply Air: 18,553 / (.999 X 1.1 X 17) = 993 CFM
Summer Vent Outside Air (13.8% of supply) = 137 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,704 Btuh 137 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,704 Btuh
Total sensible gain on air handling system: 21,257 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,586 Btuh
Total latent gain on air handling system: 7,986 Btuh
Total system sensible and latent gain: 29,244 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 993 CFM
Total Air Handler Vent. Air (13.77% of Supply): 137 CFM
Total Conditioned Air Space: 612 Sq.ft
Supply Air Per Unit Area: 1.6228 CFM/Sq.ft
Area Per Cooling Capacity: 251.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0040 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.44 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 20

Air Handler #9 - Oficina D 104-204-304 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
Oficina D 104-204-
576 0 27,161 4,400 None 5/P, 0.06/ft²
9 304
20 0 1,566 0 0 135
1pm August
5,668 0.00 2.72 0 0 135

Zone Peak Totals: 576 0 27,161 4,400


Total Zones: 1 20 0 1,566 0 0 135
Unique Zones: 1 5,668 0.00 2.72 0 0 135

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 21

Air Handler #9 - Oficina D 104-204-304 - Total Load Summary


Air Handler Description: Oficina D 104-204-304 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.15 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 1pm in August.
Outdoor Conditions: Clg: 90° DB, 76° WB, 113.75 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 27,161 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 375 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 27,536 Btuh
Cooling Supply Air: 27,536 / (.999 X 1.1 X 16) = 1,566 CFM
Summer Vent Outside Air (8.6% of supply) = 135 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,514 Btuh 135 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,514 Btuh
Total sensible gain on air handling system: 30,050 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,679 Btuh
Total latent gain on air handling system: 8,079 Btuh
Total system sensible and latent gain: 38,129 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 1,566 CFM
Total Air Handler Vent. Air (8.59% of Supply): 135 CFM
Total Conditioned Air Space: 576 Sq.ft
Supply Air Per Unit Area: 2.7190 CFM/Sq.ft
Area Per Cooling Capacity: 181.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0055 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.18 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 22

Air Handler #10 - Oficina D 105-205 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
10 Oficina D 105-205 400 0 21,481 2,640 None 5/P, 0.06/ft²
3pm August 12 0 1,322 0 0 84
3,936 0.00 3.31 0 0 84
Zone Peak Totals: 400 0 21,481 2,640
Total Zones: 1 12 0 1,322 0 0 84
Unique Zones: 1 3,936 0.00 3.31 0 0 84

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 23

Air Handler #10 - Oficina D 105-205 - Total Load Summary


Air Handler Description: Oficina D 105-205 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.12 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 21,481 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 316 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 21,797 Btuh
Cooling Supply Air: 21,797 / (.999 X 1.1 X 15) = 1,322 CFM
Summer Vent Outside Air (6.4% of supply) = 84 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,661 Btuh 84 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,661 Btuh
Total sensible gain on air handling system: 23,459 Btuh
Zone space latent gain: 2,640 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 2,203 Btuh
Total latent gain on air handling system: 4,843 Btuh
Total system sensible and latent gain: 28,302 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 1,322 CFM
Total Air Handler Vent. Air (6.35% of Supply): 84 CFM
Total Conditioned Air Space: 400 Sq.ft
Supply Air Per Unit Area: 3.3060 CFM/Sq.ft
Area Per Cooling Capacity: 169.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0059 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.36 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 24

Air Handler #11 - Oficina D 301 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
11 Oficina D 301 516 0 34,806 4,400 None 5/P, 0.06/ft²
3pm August 20 0 2,143 0 0 131
5,077 0.00 4.15 0 0 131
Zone Peak Totals: 516 0 34,806 4,400
Total Zones: 1 20 0 2,143 0 0 131
Unique Zones: 1 5,077 0.00 4.15 0 0 131

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 25

Air Handler #11 - Oficina D 301 - Total Load Summary


Air Handler Description: Oficina D 301 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.20 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 34,806 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 513 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 35,319 Btuh
Cooling Supply Air: 35,319 / (.999 X 1.1 X 15) = 2,143 CFM
Summer Vent Outside Air (6.1% of supply) = 131 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,590 Btuh 131 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,590 Btuh
Total sensible gain on air handling system: 37,909 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,435 Btuh
Total latent gain on air handling system: 7,835 Btuh
Total system sensible and latent gain: 45,745 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 2,143 CFM
Total Air Handler Vent. Air (6.11% of Supply): 131 CFM
Total Conditioned Air Space: 516 Sq.ft
Supply Air Per Unit Area: 4.1527 CFM/Sq.ft
Area Per Cooling Capacity: 135.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0074 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.81 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 26

Air Handler #12 - Oficina D 302 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
12 Oficina D 302 441 0 25,682 4,400 None 5/P, 0.06/ft²
3pm August 20 0 1,481 0 0 126
4,339 0.00 3.36 0 0 126
Zone Peak Totals: 441 0 25,682 4,400
Total Zones: 1 20 0 1,481 0 0 126
Unique Zones: 1 4,339 0.00 3.36 0 0 126

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 27

Air Handler #12 - Oficina D 302 - Total Load Summary


Air Handler Description: Oficina D 302 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.14 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.85 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 25,682 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 354 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 26,036 Btuh
Cooling Supply Air: 26,036 / (.999 X 1.1 X 16) = 1,481 CFM
Summer Vent Outside Air (8.5% of supply) = 126 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,501 Btuh 126 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,501 Btuh
Total sensible gain on air handling system: 28,538 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 3,317 Btuh
Total latent gain on air handling system: 7,717 Btuh
Total system sensible and latent gain: 36,255 Btuh

Check Figures
Total Air Handler Supply Air (based on a 16° TD): 1,481 CFM
Total Air Handler Vent. Air (8.54% of Supply): 126 CFM
Total Conditioned Air Space: 441 Sq.ft
Supply Air Per Unit Area: 3.3580 CFM/Sq.ft
Area Per Cooling Capacity: 146.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0069 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.02 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 28

Air Handler #13 - Oficina D 305 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
13 Oficina D 305 400 0 27,648 2,640 None 5/P, 0.06/ft²
3pm August 12 0 1,702 0 0 84
3,936 0.00 4.26 0 0 84
Zone Peak Totals: 400 0 27,648 2,640
Total Zones: 1 12 0 1,702 0 0 84
Unique Zones: 1 3,936 0.00 4.26 0 0 84

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 29

Air Handler #13 - Oficina D 305 - Total Load Summary


Air Handler Description: Oficina D 305 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.16 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 111.36 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 27,648 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 407 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 28,055 Btuh
Cooling Supply Air: 28,055 / (.999 X 1.1 X 15) = 1,702 CFM
Summer Vent Outside Air (4.9% of supply) = 84 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,661 Btuh 84 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,661 Btuh
Total sensible gain on air handling system: 29,717 Btuh
Zone space latent gain: 2,640 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 2,203 Btuh
Total latent gain on air handling system: 4,843 Btuh
Total system sensible and latent gain: 34,560 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 1,702 CFM
Total Air Handler Vent. Air (4.94% of Supply): 84 CFM
Total Conditioned Air Space: 400 Sq.ft
Supply Air Per Unit Area: 4.2552 CFM/Sq.ft
Area Per Cooling Capacity: 138.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0072 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.88 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 30

Air Handler #14 - CU Sala De Reuniones - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
Cu Sala De
260 0 30,528 3,080 None 5/P, 0.06/ft²
14 Reuniones
14 0 1,879 0 0 86
2pm August
2,558 0.00 7.23 0 0 86

Zone Peak Totals: 260 0 30,528 3,080


Total Zones: 1 14 0 1,879 0 0 86
Unique Zones: 1 2,558 0.00 7.23 0 0 86

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 31

Air Handler #14 - CU Sala De Reuniones - Total Load Summary


Air Handler Description: CU Sala De Reuniones Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.18 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in August.
Outdoor Conditions: Clg: 91° DB, 76° WB, 112.01 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 30,528 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 450 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 30,977 Btuh
Cooling Supply Air: 30,977 / (.999 X 1.1 X 15) = 1,879 CFM
Summer Vent Outside Air (4.6% of supply) = 86 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,693 Btuh 86 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,693 Btuh
Total sensible gain on air handling system: 32,670 Btuh
Zone space latent gain: 3,080 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 2,245 Btuh
Total latent gain on air handling system: 5,325 Btuh
Total system sensible and latent gain: 37,996 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 1,879 CFM
Total Air Handler Vent. Air (4.55% of Supply): 86 CFM
Total Conditioned Air Space: 260 Sq.ft
Supply Air Per Unit Area: 7.2283 CFM/Sq.ft
Area Per Cooling Capacity: 82.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0122 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.17 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 32

Air Handler #15 - CU Cafeteria - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
7.5/P,
Cu Cafeteria 143 0 26,539 2,200 None
15 0.18/ft²
1pm August 10 0 1,634 0 0
101
1,407 0.00 11.43 0 0
101
Zone Peak Totals: 143 0 26,539 2,200
Total Zones: 1 10 0 1,634 0 0 101
Unique Zones: 1 1,407 0.00 11.43 0 0 101

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 33

Air Handler #15 - CU Cafeteria - Total Load Summary


Air Handler Description: CU Cafeteria Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.15 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 1pm in August.
Outdoor Conditions: Clg: 90° DB, 76° WB, 113.75 grains
Indoor Conditions: Clg: 73° DB, 60% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 26,539 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 391 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 26,930 Btuh
Cooling Supply Air: 26,930 / (.999 X 1.1 X 15) = 1,634 CFM
Summer Vent Outside Air (6.2% of supply) = 101 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,882 Btuh 101 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,882 Btuh
Total sensible gain on air handling system: 28,812 Btuh
Zone space latent gain: 2,200 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 2,754 Btuh
Total latent gain on air handling system: 4,954 Btuh
Total system sensible and latent gain: 33,766 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 1,634 CFM
Total Air Handler Vent. Air (6.17% of Supply): 101 CFM
Total Conditioned Air Space: 143 Sq.ft
Supply Air Per Unit Area: 11.4253 CFM/Sq.ft
Area Per Cooling Capacity: 50.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0197 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.81 Tons

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 34

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-PB Local 10 peaks (sensible) in August at 2pm, Air Handler 1 (PB Local 10), Group 1, 39.0 x
23.0, Construction Type: 2 (Light)
Wall-1-N-F-M 114 0.83 22.0 0.323 812 1.615 185
Wall-3-S-F-M 42 0.83 26.1 0.323 357 1.615 68
Partition-2-1 383.76 10/10 0.323 1,240 3.230 1,240
Partition-4-1 383.76 10/10 0.323 1,240 3.230 1,240
Gls-N-1-90-Tran 112.0 1.000 17 0.800 1,555 4.150 465
0%S-0-NS-Solar 112.0 0.920 82 0.820 6,928
Gls-S-1-90-Tran 184.0 1.000 17 0.800 2,554 4.150 764
0%S-0-NS-Solar 184.0 0.920 55 0.650 6,052
Lights-Prof=1 897 1.000 3,061
Equipment-Prof=1 1,346 1.000 4,591 0
People-Prof=1 32.0 1.000 8,000 6,400
Sub-total 36,389 6,400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 40,028 7,040 0

Zone 2-Mz Local 10 peaks (sensible) in August at 3pm, Air Handler 2 (Mz Local 10), Group 2, 37.0 x
25.0, Construction Type: 2 (Light)
Wall-1-N-F-M 100 0.83 23.6 0.323 764 1.615 162
Wall-3-S-F-M 364 0.83 29.5 0.323 3,464 1.615 588
Partition-2-1 246 10/10 0.323 795 3.230 795
Partition-4-1 246 10/10 0.323 795 3.230 795
Gls-N-1-90-Tran 264.0 1.000 18 0.800 3,876 4.150 1,096
0%S-0-NS-Solar 264.0 0.920 82 0.820 16,331
Lights-Prof=1 925 1.000 3,156
Equipment-Prof=1 1,388 1.000 4,734 0
People-Prof=1 32.0 1.000 8,000 6,400
Sub-total 41,915 6,400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 46,107 7,040 0

Zone 3-Lobby Acceso Ofinas peaks (sensible) in August at 3pm, Air Handler 3 (Lobby De Acceso
Oficina), Group 3, 29.0 x 15.0, Construction Type: 2 (Light)
Wall-1-N-F-M 44 0.83 23.6 0.323 333 1.615 70
Wall-3-S-F-M 84 0.83 29.5 0.323 795 1.615 135
Partition-2-1 285.36 10/10 0.323 922 3.230 922
Partition-4-1 285.36 10/10 0.323 922 3.230 922
Gls-N-1-90-Tran 104.0 1.000 18 0.800 1,527 4.150 432
0%S-0-NS-Solar 104.0 0.920 82 0.820 6,434
Gls-S-1-90-Tran 64.0 1.000 18 0.800 940 4.150 266
0%S-0-NS-Solar 64.0 0.920 55 0.590 1,911
Lights-Prof=1 435 1.000 1,484
Equipment-Prof=1 653 1.000 2,226 0
People-Prof=1 10.0 1.000 2,500 2,000
Sub-total 19,993 2,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 21,992 2,200 0

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 35

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 4-PB Local 11 peaks (sensible) in August at 2pm, Air Handler 4 (PB Local 11), Group 4, 39.0 x
23.0, Construction Type: 2 (Light)
Wall-1-N-F-M 114 0.83 22.0 0.323 812 1.615 185
Wall-3-S-F-M 42 0.83 26.1 0.323 357 1.615 68
Partition-2-1 383.76 10/10 0.323 1,240 3.230 1,240
Partition-4-1 383.76 10/10 0.323 1,240 3.230 1,240
Gls-N-1-90-Tran 112.0 1.000 17 0.800 1,555 4.150 465
0%S-0-NS-Solar 112.0 0.920 82 0.820 6,928
Gls-S-1-90-Tran 184.0 1.000 17 0.800 2,554 4.150 764
0%S-0-NS-Solar 184.0 0.920 55 0.650 6,052
Lights-Prof=1 897 1.000 3,061
Equipment-Prof=1 1,346 1.000 4,591 0
People-Prof=1 32.0 1.000 8,000 6,400
Sub-total 36,389 6,400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 40,028 7,040 0

Zone 5-Mz Local 11 peaks (sensible) in August at 1pm, Air Handler 5 (Mz Local 11), Group 5, 23.0 x
23.0, Construction Type: 2 (Light)
Wall-1-N-F-M 66 0.83 19.5 0.323 418 1.615 107
Wall-2-E-F-M 66 0.83 38.6 0.323 827 1.615 107
Wall-3-S-F-M 66 0.83 20.3 0.323 435 1.615 107
Partition-4-1 226.32 10/10 0.323 731 3.230 731
Gls-N-1-90-Tran 160.0 1.000 16 0.800 2,093 4.150 664
0%S-0-NS-Solar 160.0 0.920 82 0.800 9,656
Gls-E-1-90-Tran 160.0 1.000 16 0.800 2,093 4.150 664
0%S-0-NS-Solar 160.0 0.920 220 0.370 11,982
Gls-S-1-90-Tran 160.0 1.000 16 0.800 2,093 4.150 664
0%S-0-NS-Solar 160.0 0.920 55 0.650 5,262
Lights-Prof=1 529 1.000 1,805
Equipment-Prof=1 794 1.000 2,708 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 45,102 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 49,613 4,400 0

Zone 6-Oficina D 101-201 peaks (sensible) in August at 6pm, Air Handler 6 (Oficina D 101-201), Group
6, 43.0 x 12.0, Construction Type: 2 (Light)
Wall-1-N-F-M 283 0.83 27.0 0.323 2,466 1.615 457
Partition-2-1 118.08 10/10 0.323 381 3.230 381
Partition-3-1 423.12 10/10 0.323 1,367 3.230 1,367
Partition-4-1 118.08 10/10 0.323 381 3.230 381
Gls-N-1-90-Tran 140.0 1.000 16 0.800 1,831 4.150 581
0%S-0-NS-Solar 140.0 0.920 82 0.840 8,872
Lights-Prof=1 516 1.000 1,761
Equipment-Prof=1 774 1.000 2,641 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 24,700 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 36

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Total w/ safety factors: 27,170 4,400 0

Zone 7-Oficina D 102-202 peaks (sensible) in August at 6pm, Air Handler 7 (Oficina D 102-202), Group
7, 21.0 x 21.0, Construction Type: 2 (Light)
Wall-1-N-F-M 137 0.83 27.0 0.323 1,190 1.615 221
Partition-2-1 206.64 10/10 0.323 667 3.230 667
Partition-3-1 206.64 10/10 0.323 667 3.230 667
Partition-4-1 206.64 10/10 0.323 667 3.230 667
Gls-N-1-90-Tran 70.0 1.000 16 0.800 916 4.150 291
0%S-0-NS-Solar 70.0 0.920 82 0.840 4,436
Lights-Prof=1 441 1.000 1,505
Equipment-Prof=1 662 1.000 2,257 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 17,306 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 19,036 4,400 0

Zone 8-Oficina D 103-203-303 peaks (sensible) in August at 2pm, Air Handler 8 (Oficina D 103-203-
303), Group 8, 34.0 x 18.0, Construction Type: 2 (Light)
Wall-1-S-F-M 137 0.83 26.1 0.323 1,154 1.615 221
Partition-2-1 206.64 10/10 0.323 667 3.230 667
Partition-3-1 206.64 10/10 0.323 667 3.230 667
Partition-4-1 206.64 10/10 0.323 667 3.230 667
Gls-S-1-90-Tran 70.0 1.000 17 0.800 972 4.150 291
0%S-0-NS-Solar 70.0 0.920 55 0.650 2,302
Lights-Prof=1 612 1.000 2,088
Equipment-Prof=1 918 1.000 3,132 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 16,650 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 18,315 4,400 0

Zone 9-Oficina D 104-204-304 peaks (sensible) in August at 1pm, Air Handler 9 (Oficina D 104-204-
304), Group 9, 32.0 x 18.0, Construction Type: 2 (Light)
Wall-2-E-F-M 132 0.83 38.6 0.323 1,647 1.615 213
Wall-3-S-F-M 175 0.83 20.3 0.323 1,148 1.615 282
Partition-1-1 314.88 10/10 0.323 1,017 3.230 1,017
Partition-4-1 177.12 10/10 0.323 572 3.230 572
Gls-E-1-90-Tran 45.0 1.000 16 0.800 589 4.150 187
0%S-0-NS-Solar 45.0 0.920 220 0.370 3,370
Gls-S-1-90-Tran 140.0 1.000 16 0.800 1,831 4.150 581
0%S-0-NS-Solar 140.0 0.920 55 0.650 4,605
Lights-Prof=1 576 1.000 1,965
Equipment-Prof=1 864 1.000 2,948 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 24,692 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 27,161 4,400 0

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 37

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 10-Oficina D 105-205 peaks (sensible) in August at 3pm, Air Handler 10 (Oficina D 105-205),
Group 10, 20.0 x 20.0, Construction Type: 2 (Light)
Wall-1-N-F-M 127 0.83 23.6 0.323 969 1.615 205
Wall-2-E-F-M 162 0.83 32.8 0.323 1,713 1.615 261
Wall-3-S-F-M 197 0.83 29.5 0.323 1,873 1.615 318
Partition-4-1 196.8 10/10 0.323 636 3.230 636
Gls-N-1-90-Tran 70.0 1.000 18 0.800 1,028 4.150 291
0%S-0-NS-Solar 70.0 0.920 82 0.820 4,330
Gls-E-1-90-Tran 35.0 1.000 18 0.800 514 4.150 145
0%S-0-NS-Solar 35.0 0.920 220 0.290 2,054
Lights-Prof=1 400 1.000 1,365
Equipment-Prof=1 600 1.000 2,047 0
People-Prof=1 12.0 1.000 3,000 2,400
Sub-total 19,528 2,400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 21,481 2,640 0

Zone 11-Oficina D 301 peaks (sensible) in August at 3pm, Air Handler 11 (Oficina D 301), Group 11,
43.0 x 12.0, Construction Type: 2 (Light)
Roof-1-1-Susp.C-L 516 0.50 42.5 0.330 7,233 1.650 851
Wall-1-N-F-M 283 0.83 23.6 0.323 2,163 1.615 457
Partition-2-1 118.08 10/10 0.323 381 3.230 381
Partition-3-1 423.12 10/10 0.323 1,367 3.230 1,367
Partition-4-1 118.08 10/10 0.323 381 3.230 381
Gls-N-1-90-Tran 140.0 1.000 18 0.800 2,055 4.150 581
0%S-0-NS-Solar 140.0 0.920 82 0.820 8,661
Lights-Prof=1 516 1.000 1,761
Equipment-Prof=1 774 1.000 2,641 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 31,642 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 34,806 4,400 0

Zone 12-Oficina D 302 peaks (sensible) in August at 3pm, Air Handler 12 (Oficina D 302), Group 12,
21.0 x 21.0, Construction Type: 2 (Light)
Roof-1-1-Susp.C-L 441 0.50 42.5 0.330 6,181 1.650 728
Wall-1-N-F-M 137 0.83 23.6 0.323 1,044 1.615 221
Partition-2-1 206.64 10/10 0.323 667 3.230 667
Partition-3-1 206.64 10/10 0.323 667 3.230 667
Partition-4-1 206.64 10/10 0.323 667 3.230 667
Gls-N-1-90-Tran 70.0 1.000 18 0.800 1,028 4.150 291
0%S-0-NS-Solar 70.0 0.920 82 0.820 4,330
Lights-Prof=1 441 1.000 1,505
Equipment-Prof=1 662 1.000 2,257 0
People-Prof=1 20.0 1.000 5,000 4,000
Sub-total 23,347 4,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 25,682 4,400 0

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 38

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 13-Oficina D 305 peaks (sensible) in August at 3pm, Air Handler 13 (Oficina D 305), Group 13,
20.0 x 20.0, Construction Type: 2 (Light)
Roof-1-1-Susp.C-L 400 0.50 42.5 0.330 5,607 1.650 660
Wall-1-N-F-M 127 0.83 23.6 0.323 969 1.615 205
Wall-2-E-F-M 162 0.83 32.8 0.323 1,713 1.615 261
Wall-3-S-F-M 197 0.83 29.5 0.323 1,873 1.615 318
Partition-4-1 196.8 10/10 0.323 636 3.230 636
Gls-N-1-90-Tran 70.0 1.000 18 0.800 1,028 4.150 291
0%S-0-NS-Solar 70.0 0.920 82 0.820 4,330
Gls-E-1-90-Tran 35.0 1.000 18 0.800 514 4.150 145
0%S-0-NS-Solar 35.0 0.920 220 0.290 2,054
Lights-Prof=1 400 1.000 1,365
Equipment-Prof=1 600 1.000 2,047 0
People-Prof=1 12.0 1.000 3,000 2,400
Sub-total 25,135 2,400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 27,648 2,640 0

Zone 14-Cu Sala De Reuniones peaks (sensible) in August at 2pm, Air Handler 14 (CU Sala De
Reuniones), Group 14, 20.0 x 13.0, Construction Type: 2 (Light)
Roof-1-1-Susp.C-L 260 0.50 42.0 0.330 3,601 1.650 429
Wall-1-N-F-M 61 0.83 22.0 0.323 432 1.615 98
Wall-3-S-F-M 61 0.83 26.1 0.323 513 1.615 98
Partition-2-1 127.92 10/10 0.323 413 3.230 413
Partition-4-1 127.92 10/10 0.323 413 3.230 413
Gls-N-1-90-Tran 136.0 1.000 17 0.800 1,888 4.150 564
0%S-0-NS-Solar 136.0 0.920 82 0.820 8,413
Gls-S-1-90-Tran 136.0 1.000 17 0.800 1,888 4.150 564
0%S-0-NS-Solar 136.0 0.920 55 0.650 4,473
Lights-Prof=1 260 1.000 887
Equipment-Prof=1 390 1.000 1,331 0
People-Prof=1 14.0 1.000 3,500 2,800
Sub-total 27,752 2,800 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 30,528 3,080 0

Zone 15-Cu Cafeteria peaks (sensible) in August at 1pm, Air Handler 15 (CU Cafeteria), Group 15, 13.0 x
11.0, Construction Type: 2 (Light)
Roof-1-1-Susp.C-L 143 0.50 39.0 0.330 1,839 1.650 236
Wall-1-N-F-M 28 0.83 19.5 0.323 178 1.615 46
Wall-2-E-F-M 40 0.83 38.6 0.323 498 1.615 64
Wall-3-S-F-M 28 0.83 20.3 0.323 185 1.615 46
Partition-4-1 127.92 10/10 0.323 413 3.230 413
Gls-N-1-90-Tran 80.0 1.000 16 0.800 1,046 4.150 332
0%S-0-NS-Solar 80.0 0.920 82 0.800 4,828
Gls-E-1-90-Tran 88.0 1.000 16 0.800 1,151 4.150 365
0%S-0-NS-Solar 88.0 0.920 220 0.370 6,590
Gls-S-1-90-Tran 80.0 1.000 16 0.800 1,046 4.150 332
0%S-0-NS-Solar 80.0 0.920 55 0.650 2,631
Lights-Prof=1 143 1.000 488
Equipment-Prof=1 215 1.000 732 0

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MIDTOWN 400 BLOQUE C
Hell Page 39

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
People-Prof=1 10.0 1.000 2,500 2,000
Sub-total 24,126 2,000 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 26,539 2,200 0

C:\ ...\MP-Pronobis Midtown 400 Bloque C.CHV sábado, septiembre 17, 2022, 03:18 PM