Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 2

General Project Data Input


General Project Information
Project file name: C:\Users\Desktop\AT- PLAZA EL SOL.CHV
Project title: Apuesta Total - Plaza El Sol
Designed by: E. S. S.
Project date: 26/04/2019
Project location: PIURA, PERU
Client name: Bravo&Julca
Client city: Lima
Company name: Grupo Vargas S.A.C
Company representative: E.S.S
Company city: Lima
Company phone: 912 335 012
Barometric pressure: 29.876 in.Hg.
Altitude: 42 feet
Latitude: -12 Degrees
Mean daily temperature range: 11.5 Degrees
Starting & ending time for HVAC load calculations: 9am - 10pm
Number of unique zones in this project: 1

Building Default Values


Calculations performed: Both heating and cooling loads
Lighting requirements: 2.30 Watts per square foot
Equipment requirements: 2.60 Watts per square foot
People sensible load multiplier: 580 Btuh per person
People latent load multiplier: 625 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 10 %
People diversity factor: 80 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 9.0 feet
Building default wall height: 9.0 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 85 75 50% 75 50.29 -3
Winter 58 75

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 6 0.150 Sí Sí

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 E 0.350 D
2 G 0.062 L
3 G 0.032 L

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.350 14 53

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 1.000 0.400 2 0.000

Master Shading Devices


Dist Dist Dist Dist Dist Dist Ht Dist Dist Ht
Horiz Beyond Beyond Overh Right R-Fin Of Left L-Fin Of
Shade Overh Right Left Above Fin Beyond Right Fin Beyond Left
No. Projects W.Edge W.Edge Wind Proj W.Edge Fin Proj W.Edge Fin
1 2.00 0.00 0.00 0.60 0.00 0.00 0.00 0.00 0.00 0.00
2 2.00 1.00 1.00 0.60 0.00 0.00 0.00 0.00 0.00 0.00

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 4

Building Envelope Report


Envelope Report Using Summer U-Factors
Material Gross Glass Net -U- Area x Average
Types Area Area Area Factor U-Factor U-Factor
Roof 1 198.0 0.0 198.0 0.150 29.700 0.150
Tot.Roof 198.0 0.0 198.0 N/A 29.700 0.150
Wall 1 559.8 132.0 427.8 0.350 149.730 0.350
Tot.Wall 559.8 132.0 427.8 N/A 149.730 0.350
Glass 1 132.0 N/A 132.0 1.000 132.000 1.000
Tot.Glass 132.0 N/A 132.0 N/A 132.000 1.000
Totals 757.8 311.430 0.411

Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 80.1 0.0 80.1 0.350 0.000 0.000
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 199.8 68.0 131.8 0.350 1.000 0.400
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 80.1 64.0 16.1 0.350 1.000 0.400
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 199.8 0.0 199.8 0.350 0.000 0.000
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 559.8 132.0 427.8 0.350 1.000 0.400

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 5

Building Summary Loads


Building peaks in August at 6pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 198 555 6.69 0 1,527 1,527 5.79
Wall 428 2,800 33.74 0 5,580 5,580 21.17
Glass 132 2,468 29.75 0 3,244 3,244 12.31
Floor Slab 62 582 7.01 0 0 0 0.00
Skin Loads 6,405 77.19 0 10,351 10,351 39.27
Lighting 454 0 0.00 0 1,706 1,706 6.47
Equipment 514 0 0.00 1,100 1,928 3,028 11.49
People 5 0 0.00 3,300 3,062 6,362 24.14
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 36 0 0.00 1,147 273 1,420 5.39
Heat. Vent. 45 825 9.94 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 1,231 1,231 4.67
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 757 757 2.87
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 712 8.58 0 1,002 1,002 3.80
Return Duct 0 356 4.29 0 501 501 1.90
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 8,298 100.00 5,547 20,811 26,358 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 825 9.94 1,147 273 1,420 5.39
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 6,405 77.19 4,400 17,804 22,204 84.24
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 1,068 12.87 0 2,733 2,733 10.37
Building Totals 8,298 100.00 5,547 20,811 26,358 100.00

Check Figures
Total Building Supply Air (based on a 20° TD): 912 CFM
Total Building Vent. Air (3.90% of Supply): 36 CFM
Total Conditioned Air Space: 198 Sq.ft
Supply Air Per Unit Area: 4.6164 CFM/Sq.ft
Area Per Cooling Capacity: 89.9531 Sq.ft/Ton
Cooling Capacity Per Area: 0.0111 Tons/Sq.ft
Total Heating Required With Outside Air: 8,298 Btuh
Total Cooling Required With Outside Air: 2.20 Tons

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 6

Air Handler #1 - Sala De Ventas - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Sala De Ventas 198 6,405 17,812 5,225 7.5/P 0.18/ft²
6pm August 6 330 913 0 45 36
1,778 1.67 4.62 0 45 36
Runout duct size: 6in. dia, Diffusers: 7, CFM/runout: 130, Velocity: 664.0 ft/min, Pressure drop: 0.280 in.wg./100ft
Zone Peak Totals: 198 6,405 17,812 5,225
Total Zones: 1 6 330 913 0 45 36
Unique Zones: 1 1,778 1.67 4.62 0 45 36
Main trunk duct size: 14in. h x 12in. w, Velocity: 853.2 ft/min, Pressure drop: 0.105 in.wg./100ft

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 7

Air Handler #1 - Sala De Ventas - Total Load Summary


Air Handler Description: Sala De Ventas Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.49 HP
Fan Input: 65% motor and fan efficiency with 2.2 in. water across the fan
Sensible Heat Ratio: 0.82 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in August.
Outdoor Conditions: 83° DB, 74° WB, 115.48 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 6,405 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 825 Btuh 45 CFM
Supply Duct sensible loss: 712 Btuh
Return Duct sensible loss: 356 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 8,298 Btuh
Heating Supply Air: 7,117 / (.998 X 1.08 X 20) = 330 CFM
Winter Vent Outside Air (13.6% of supply) = 45 CFM
Zone space sensible gain: 17,047 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,231 Btuh
Supply duct sensible gain: 1,002 Btuh
Reserve sensible gain: 757 Btuh
Total sensible gain on supply side of coil: 20,036 Btuh
Cooling Supply Air: 20,036 / (.998 X 1.1 X 20) = 912 CFM
Summer Vent Outside Air (3.9% of supply) = 36 CFM
Return duct sensible gain: 501 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 273 Btuh 36 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 774 Btuh
Total sensible gain on air handling system: 20,811 Btuh
Zone space latent gain: 4,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,147 Btuh
Total latent gain on air handling system: 5,547 Btuh
Total system sensible and latent gain: 26,358 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 912 CFM
Total Air Handler Vent. Air (3.90% of Supply): 36 CFM
Total Conditioned Air Space: 198 Sq.ft
Supply Air Per Unit Area: 4.6164 CFM/Sq.ft
Area Per Cooling Capacity: 89.9531 Sq.ft/Ton
Cooling Capacity Per Area: 0.0111 Tons/Sq.ft
Total Heating Required With Outside Air: 8,298 Btuh
Total Cooling Required With Outside Air: 2.20 Tons

C:\User\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 8

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Sala De Ventas peaks (sensible) in August at 6pm, Air Handler 1 (Sala De Ventas), Group 0, 22.2 x
8.9, Construction Type: 5 (Light)
Roof-1-6-Susp.C-D 198 1.00 46.8 0.150 1,388 2.550 505
Wall-1-E-E-D 132 1 27.8 0.350 1,280 5.950 784
Wall-2-W-E-D 200 1 38.8 0.350 2,710 5.950 1,189
Wall-3-N-E-D 80 1 35.8 0.350 1,002 5.950 477
Wall-4-S-E-D 16 1 14.3 0.350 80 5.950 96
Gls-E-1-90-Tran 48.3 1.000 9 1.000 447 17.000 821
29%S-1-NS-Solar 48.3 0.400 212 0.190 778
SGls-E-1-90-Tran 19.7 1.000 9 1.000 182 17.000 335
29%S-1-NS-Solar 19.7 0.400 46 0.840 305
Gls-S-1-90-Tran 64.0 1.000 9 1.000 592 17.000 1,088
0%S-1-NS-Solar 64.0 0.400 30 0.840 645
Lights-Prof=1 454 1.000 1,551
Equipment-Prof=1 514 1.000 1,753 1,000
People-Prof=1 6.0 1.000 3,480 3,750
Floor slab 62 8.500 529
Sub-total 16,193 4,750 5,823
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 17,812 5,225 6,405

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 9

Air System #1 (Sala De Ventas) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 57.634 55.000
Draw-Thru Fan 1,231 1.229 56
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 1,002 1.000 46
Zone Loads 4,400 7.105 17,047 17.016 776
Sensible Reserve 757 0.756 34
Zone Condition 4,400 64.739 20,036 75.000 912
Return Air Duct 501 0.500
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 36 CFM 1,147 1.916 273 0.253
Blow-Thru Fan 0 0.000
Entering Coil Condition 5,547 66.655 20,811 75.753 912

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.998 x 1.10 x 912 x( 75.753 - 55.000 )= 20,791 Btuh


TLH = 0.998 x 0.68 x 912 x( 66.655 - 57.634 )= 5,586 Btuh
----------
SUM = 26,377 Btuh
GTH = 0.998 x 4.50 x 912 x( 28.606 - 22.138 )= 26,506 Btuh
Total System Load = 26,358 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 26,506 / ( 10.00 x 500 ) = 5.3 GPM
Heating GPM = 8,298 / ( 20.00 x 500 ) = 0.8 GPM
Steam Req. = 8,298 / 970 = 8.6 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.75 Dry bulb temperature: 71.82
Wet bulb temperature: 63.21
Relative humidity: 50.18
Enthalpy: 28.61 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 53.25
Relative humidity: 89.53
Enthalpy: 22.14 Btu/lbm

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 10

Air System #1 (Sala De Ventas) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 11

Building Pie Charts


Building peaks in August at 6pm.

Return Duct - 1.90%


Roof - 5.79% Supply Duct - 3.80%
Reserve Cap. - 2.87%
Draw-Thru Fan - 4.67%

Wall - 21.17% Cool. Vent. - 5.39%

Building
Net
Gain
26,358
Btuh
People - 24.14%
Glass - 12.31%

Lighting - 6.47%
Equipment - 11.49%

Roof - 6.69% Return Duct - 4.29%


Supply Duct - 8.58%

Heat. Vent. - 9.94%

Building Wall - 33.74%


Loss Floor - 7.01%
8,298
Btuh

Glass - 29.75%

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Apuesta Total - Plaza El Sol
College Station, TX 77845 Page 12

Air Handler #1 Pie Charts


Air Handler #1 peaks in August at 6pm.

Return Duct - 1.90%


Roof - 5.79% Supply Duct - 3.80%
Reserve Cap. - 2.87%
Draw-Thru Fan - 4.67%

Wall - 21.17% Cool. Vent. - 5.39%

Air
Handler
#1
Net
Gain
26,358
People - 24.14%
Btuh
Glass - 12.31%

Lighting - 6.47%
Equipment - 11.49%

Roof - 6.69% Return Duct - 4.29%


Supply Duct - 8.58%

Heat. Vent. - 9.94%

Air
Handler Wall - 33.74%
#1 Floor - 7.01%
Loss
8,298
Btuh

Glass - 29.75%

C:\Users\Desktop\AT- PLAZA EL SOL.CHV viernes, 26 de Abril de 2019, 3:19 a.m.