HVAC Load Analysis


for

Prepared By:

Ing. Carlos Uceda

jueves, 12 de Setiembre de 2019


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 2

General Project Data Input


General Project Information
Project file name: C:\Users\Usuario\Desktop\bbraun\ISTORE MALL
PUROCHUCO\CALCULO TERMICO DE ISTORE
PURUCHUCO.CHV
Project title: ISTORE
Designed by: Your Name
Project date: Wednesday, Agosto 29, 2019
Project comment: To create a template from an existing project, open the project
and select 'File
Weather reference city: ISTORE
Company representative: Ing. Carlos Uceda
Barometric pressure: 29.876 in.Hg.
Altitude: 42 feet
Latitude: -12 Degrees
Mean daily temperature range: 11.5 Degrees
Starting & ending time for HVAC load calculations: 6pm - 12am
Number of unique zones in this project: 1

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 2.80 Watts per square foot
Equipment requirements: 0.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 250 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 0 %
People diversity factor: 80 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 8.50 feet
Building default wall height: 10.60 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 0 0 0 0 0 0 0 C C C C C C C C C C C 0 0 0 0 0 0
2 C C C C C C C C C C C C C C C C C 0 0 0 0 0 0 0
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
January 85 75 50% 75 50.29 -3
February 85 75 50% 75 50.29 -3
March 85 75 50% 75 50.29 -3
Winter 57 72

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 4 0.350 No Sí
2 4 0.350 No Sí
3 4 0.350 No Sí

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0.350 D

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.350 10 0
2 0.350 10 0
3 1.100 10 0

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 1.100 0.700 2 0.700
2 1.000 1.000 0.400 1 0.400
3 1.000 1.000 0.600 1 0.600

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name:
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Package fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 80
Static pressure across fan (in.wg.): 2.20
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 10.000
Hot water temp difference (deg.F): 20.000
Cooling ventilation: 0 AC/Hr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 AC/Hr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
January 85 75 50% 75 50.29 -3
February 85 75 50% 75 50.29 -3
March 85 75 50% 75 50.29 -3
Winter 57 72

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 5

Zone Input
Zone 1: PLANO DE PLANTA ISTORE (691.2 sq.ft) (Group 0)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 64.00 Zone width (feet): 10.80
Lighting Watts: 1,935 Equipment Watts: 200
Number of people in zone: 5 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 8.50 Heating safety factor (%): 0
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 220.000
Cooling infiltration method: Direct Cooling infiltration value: 220.000
Heating ventilation method: AC/Hr Heating ventilation value: 0.000
Heating infiltration method: AC/Hr Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 691 Exposed floor slab perimeter (ft): 0
Cooling loads only are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 4 0.350 No 26.24 26.24 688.5 Sí

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.350 D 26.24 10.80 283.4 N
2 1 A 0.350 D 26.24 10.80 283.4 W
3 1 A 0.350 D 26.24 10.80 283.4 S

Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 1.000 0.700 10.00 20.00 1 200.0 0 90 1

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 6

Building Summary Loads


Building peaks in March at 6pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 689 0 0.00 0 5,434 5,434 12.39
Wall 650 0 0.00 0 2,630 2,630 5.99
Glass 200 0 0.00 0 6,193 6,193 14.11
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 14,257 14,257 32.49
Lighting 1,935 0 0.00 0 7,264 7,264 16.56
Equipment 200 0 0.00 0 751 751 1.71
People 4 0 0.00 1,100 1,100 2,200 5.01
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 220 0 0.00 7,095 1,691 8,787 20.03
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 220 0 0.00 8,336 2,016 10,352 23.59
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 267 267 0.61
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 16,531 27,346 43,878 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 7,095 1,691 8,787 20.03
Infiltration 0 0.00 8,336 2,016 10,352 23.59
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 1,100 23,639 24,739 56.38
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 0 0 0.00
Building Totals 0 0.00 16,531 27,346 43,878 100.00

Check Figures
Total Building Supply Air (based on a 20° TD): 1,168 CFM
Total Building Vent. Air (18.84% of Supply): 220 CFM
Total Conditioned Air Space: 691 Sq.ft
Supply Air Per Unit Area: 1.6897 CFM/Sq.ft
Area Per Cooling Capacity: 189.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0053 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.66 Tons

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 7

Air Handler #1 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
PLANO DE PLANTA
691 0 25,663 9,711 None Direct
1 ISTORE
5 0 1,168 0 0 220
6pm March
5,875 0.00 1.69 0 0 220

Zone Peak Totals: 691 0 25,663 9,711


Total Zones: 1 5 0 1,168 0 0 220
Unique Zones: 1 5,875 0.00 1.69 0 0 220

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 8

Air Handler #1 Total Load Summary


Air Handler Description: Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.73 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in March.
Outdoor Conditions: Clg: 83° DB, 74° WB, 115.48 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.998 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 23,372 Btuh
Infiltration sensible gain: 2,016 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 267 Btuh
Total sensible gain on supply side of coil: 25,655 Btuh
Cooling Supply Air: 25,655 / (.998 X 1.1 X 20) = 1,168 CFM
Summer Vent Outside Air (18.8% of supply) = 220 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,691 Btuh 220 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,691 Btuh
Total sensible gain on air handling system: 27,346 Btuh
Zone space latent gain: 1,100 Btuh
Infiltration latent gain: 8,336 Btuh
Outside air latent gain: 7,095 Btuh
Total latent gain on air handling system: 16,531 Btuh
Total system sensible and latent gain: 43,878 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,168 CFM
Total Air Handler Vent. Air (18.84% of Supply): 220 CFM
Total Conditioned Air Space: 691 Sq.ft
Supply Air Per Unit Area: 1.6897 CFM/Sq.ft
Area Per Cooling Capacity: 189.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0053 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.66 Tons

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 9

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-PLANO DE PLANTA ISTORE peaks (sensible) in March at 6pm, Air Handler 1, Group 0, 64.0
x 10.8, Construction Type: 1 (Light)
Roof-1-4-Susp.C-L 689 0.50 20.5 0.350 4,940 5.250 3,615
Wall-1-N-A-D 83 1 12.3 0.350 358 5.250 438
Wall-2-W-A-D 283 1 15.3 0.350 1,513 5.250 1,488
Wall-3-S-A-D 283 1 5.3 0.350 521 5.250 1,488
Gls-N-1-90-Tran 200.0 1.000 9 1.000 1,850 16.500 3,300
0%S-0-NS-Solar 200.0 0.700 75 0.360 3,780
Lights-Prof=1 1,935 1.000 6,604
Equipment-Prof=1 200 1.000 682 0
People-Prof=1 5.0 1.000 1,250 1,250
Cool. Infil.Direct CFM 220 1,833 7,578
Heat. Infil.AC/hr 0 0.000 0
Sub-total 23,330 8,828 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 25,663 9,711 0

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 10

Air System #1 () Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 52.844 55.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 9,436 11.899 25,388 19.792 1,156
Sensible Reserve 267 0.208 12
Zone Condition 9,436 64.743 25,655 75.000 1,168
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 220 CFM 7,095 9.255 1,691 1.319
Blow-Thru Fan 0 0.000
Entering Coil Condition 16,531 73.998 27,346 76.319 1,168

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.998 x 1.10 x 1,168 x( 76.319 - 55.000 ) = 27,346 Btuh


TLH = 0.998 x 0.68 x 1,168 x( 73.998 - 52.844 ) = 16,775 Btuh
---------
-
SUM = 44,121 Btuh
GTH = 0.998 x 4.50 x 1,168 x( 29.893 - 21.395 ) = 44,591 Btuh
Total System Load = 43,878 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 44,591 / ( 10.00 x 500 ) = 8.9 GPM
Heating GPM = 0 /( 20.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.32 Dry bulb temperature: 72.00
Wet bulb temperature: 64.94
Relative humidity: 54.59
Enthalpy: 29.89 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 72.00
Wet bulb temperature: 52.00
Relative humidity: 82.22
Enthalpy: 21.40 Btu/lbm

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 11

Building Pie Charts


Building peaks in March at 6pm.

Reserve Cap. - 0.61%


Roof - 12.39%

Cool. Infil. - 23.59%


Wall - 5.99%

Building
Net Gain Glass - 14.11%
43,878
Btuh

Cool. Vent. - 20.03%

Lighting - 16.56%
Equipment - 1.71% People - 5.01%

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
ServiParamo Ltda. ISTORE
Barranquilla, Page 12

Zone #1 - PLANO DE PLANTA ISTORE - Pie Charts


Zone #1 peaks in March at 6pm

Roof - 15.36%

Cool. Infil. - 29.26%

Wall - 7.43%

Zone #1
Net Gain
35,374
Btuh

Glass - 17.51%
People - 7.77%

Equipment - 2.12%

Lighting - 20.54%

C:\ ...\CALCULO TERMICO DE ISTORE PURUCHUCO.CHV jueves, 12 de Setiembre de 2019, 05:19 a. m.