Essalud - Módulo N°12 Administración

HVAC Load Analysis


for

Prepared By:

miércoles, 28 de abril de 2021


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 2

General Project Data Input


General Project Information
Project file name: H:\A-PRONIS ICA\ESSALUD\MODULOS\cd - final\2.- MEMORIA
DE CALCULO\MODULO ESSALUD\REPORTE DE PROGRAMA
CARGA TERMICA\ESSALUD - MÓDULO N°12
ADMINISTRACIÓN.CHV
Project title: Essalud - Módulo N°12 Administración
Project date: miércoles, 28 de abril de 2021
Weather reference city: CHAO, PERU
Barometric pressure: 29.876 in.Hg.
Altitude: 42 feet
Latitude: -12 Degrees
Mean daily temperature range: 11.5 Degrees
Starting & ending time for HVAC load calculations: 8am - 6pm
Number of unique zones in this project: 5

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.50 Watts per square foot
Equipment requirements: 2.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 0 %
Zone latent safety factor: 0 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 9.00 feet
Building default wall height: 9.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
February 85 74 50% 74 46.39 -2
Winter 59 75

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 8 0.080 No No

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 C 0.080 M
2 C 0.010 M

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.080 18 20
2 0.010 10 20

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.100 1.100 1.000 1 0.650
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 4

Building Summary Loads


Building peaks in February at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 657 841 4.03 0 1,193 1,193 1.26
Wall 544 688 3.30 0 775 775 0.82
Glass 24 422 2.02 0 1,541 1,541 1.63
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 1,952 9.36 0 3,509 3,509 3.70
Lighting 1,203 0 0.00 0 4,443 4,443 4.69
Equipment 2,970 0 0.00 0 11,251 11,251 11.88
People 23 0 0.00 4,700 6,318 11,018 11.63
Partition 1,263 2,021 9.69 0 1,978 1,978 2.09
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 870 0 0.00 28,371 9,555 37,926 40.03
Heat. Vent. 870 15,011 71.96 0 0 0 0.00
Cool. Infil. 270 0 0.00 9,339 3,283 12,623 13.32
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 2,340 2,340 2.47
Reserve Cap. 0 0 0.00 0 6,841 6,841 7.22
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 1,876 9.00 0 2,095 2,095 2.21
Return Duct 0 0 0.00 0 719 719 0.76
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 20,860 100.00 42,410 52,332 94,742 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 15,011 71.96 28,371 9,555 37,926 40.03
Infiltration 0 0.00 9,339 3,283 12,623 13.32
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 3,973 19.04 4,700 34,339 39,039 41.21
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 1,876 9.00 0 5,154 5,154 5.44
Building Totals 20,860 100.00 42,410 52,332 94,742 100.00

Check Figures
Total Building Supply Air (based on a 19° TD): 1,908 CFM
Total Building Vent. Air (45.61% of Supply): 870 CFM
Total Conditioned Air Space: 657 Sq.ft
Supply Air Per Unit Area: 2.9036 CFM/Sq.ft
Area Per Cooling Capacity: 83.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0120 Tons/Sq.ft
Heating Capacity Per Area: 31.75 Btuh/Sq.ft
Total Heating Required With Outside Air: 20,860 Btuh
Total Cooling Required With Outside Air: 7.90 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 5

Air Handler #1 - CENTRAL DE COMUNICACIONES II - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
CENTRAL DE
100 659 4,682 2,775 Direct Direct
1 COMUNICACIONES II
6 55 237 0 55 55
3pm February
900 0.55 2.37 0 55 55

Zone Peak Totals: 100 659 4,682 2,775


Total Zones: 1 6 55 237 0 55 55
Unique Zones: 1 900 0.55 2.37 0 55 55
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 6

Air Handler #1 - CENTRAL DE COMUNICACIONES II - Total Load Summary


Air Handler Description: CENTRAL DE COMUNICACIONES II Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.11 HP
Fan Input: 65% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.64 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 85° DB, 74° WB, 109.54 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 3pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 4,682.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 659 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 949 Btuh 55 CFM
Supply Duct sensible loss: 119 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 1,726 Btuh
Heating Supply Air: 777 / (.998 X 1.08 X 13) = 55 CFM
Winter Vent Outside Air (100.0% of supply) = 55 CFM
Zone space sensible gain: 4,027 Btuh
Infiltration sensible gain: 644 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 260 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 4,931 Btuh
Cooling Supply Air: 4,942 / (.998 X 1.1 X 19) = 237 CFM
Summer Vent Outside Air (23.2% of supply) = 55 CFM
Return duct sensible gain: 130 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 664 Btuh 55 CFM
Blow-thru fan sensible gain: 291 Btuh
Total sensible gain on return side of coil: 1,085 Btuh
Total sensible gain on air handling system: 6,016 Btuh
Zone space latent gain: 1,200 Btuh
Infiltration latent gain: 1,594 Btuh
Outside air latent gain: 1,733 Btuh
Total latent gain on air handling system: 4,526 Btuh
Total system sensible and latent gain: 10,543 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 237 CFM
Total Air Handler Vent. Air (23.22% of Supply): 55 CFM
Total Conditioned Air Space: 100 Sq.ft
Supply Air Per Unit Area: 2.3683 CFM/Sq.ft
Area Per Cooling Capacity: 113.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0088 Tons/Sq.ft
Heating Capacity Per Area: 17.26 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,726 Btuh
Total Cooling Required With Outside Air: 0.88 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 7

Air Handler #2 - SALA DE TELECOMUNICACIONES - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
SALA DE
TELECOMUNICACIO 66 306 3,963 1,455 Direct Direct
2 NES 4 45 200 0 45 45
5pm February 594 0.68 3.04 0 45 45

Zone Peak Totals: 66 306 3,963 1,455


Total Zones: 1 4 45 200 0 45 45
Unique Zones: 1 594 0.68 3.04 0 45 45
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 8

Air Handler #2 - SALA DE TELECOMUNICACIONES - Total Load Summary


Air Handler Description: SALA DE TELECOMUNICACIONES Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.10 HP
Fan Input: 65% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.74 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: 84° DB, 74° WB, 110.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 306 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 776 Btuh 45 CFM
Supply Duct sensible loss: 97 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 1,179 Btuh
Heating Supply Air: 403 / (.998 X 1.08 X 8) = 45 CFM
Winter Vent Outside Air (100.0% of supply) = 45 CFM
Zone space sensible gain: 3,725 Btuh
Infiltration sensible gain: 238 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 220 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 4,183 Btuh
Cooling Supply Air: 4,183 / (.998 X 1.1 X 19) = 200 CFM
Summer Vent Outside Air (22.4% of supply) = 45 CFM
Return duct sensible gain: 110 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 494 Btuh 45 CFM
Blow-thru fan sensible gain: 246 Btuh
Total sensible gain on return side of coil: 850 Btuh
Total sensible gain on air handling system: 5,033 Btuh
Zone space latent gain: 800 Btuh
Infiltration latent gain: 655 Btuh
Outside air latent gain: 1,467 Btuh
Total latent gain on air handling system: 2,923 Btuh
Total system sensible and latent gain: 7,956 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 200 CFM
Total Air Handler Vent. Air (22.44% of Supply): 45 CFM
Total Conditioned Air Space: 66 Sq.ft
Supply Air Per Unit Area: 3.0378 CFM/Sq.ft
Area Per Cooling Capacity: 99.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0100 Tons/Sq.ft
Heating Capacity Per Area: 17.86 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,179 Btuh
Total Cooling Required With Outside Air: 0.66 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 9

Air Handler #3 - CENTRAL DE VIGILANCIA Y SEGURIDAD II - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
CENTRAL DE
VIGILANCIA Y 94 399 4,876 2,794 Direct Direct
3 SEGURIDAD II 6 50 247 0 50 50
4pm February 846 0.53 2.62 0 50 50

Zone Peak Totals: 94 399 4,876 2,794


Total Zones: 1 6 50 247 0 50 50
Unique Zones: 1 846 0.53 2.62 0 50 50
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 10

Air Handler #3 - CENTRAL DE VIGILANCIA Y SEGURIDAD II - Total Load


Summary
Air Handler Description: CENTRAL DE VIGILANCIA Y SEGURIDAD II Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.12 HP
Fan Input: 65% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.64 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: 84° DB, 74° WB, 110.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 4pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 4,876.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 399 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 863 Btuh 50 CFM
Supply Duct sensible loss: 108 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 1,369 Btuh
Heating Supply Air: 507 / (.998 X 1.08 X 9) = 50 CFM
Winter Vent Outside Air (100.0% of supply) = 50 CFM
Zone space sensible gain: 4,272 Btuh
Infiltration sensible gain: 584 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 271 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 5,127 Btuh
Cooling Supply Air: 5,147 / (.998 X 1.1 X 19) = 247 CFM
Summer Vent Outside Air (20.3% of supply) = 50 CFM
Return duct sensible gain: 135 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 549 Btuh 50 CFM
Blow-thru fan sensible gain: 303 Btuh
Total sensible gain on return side of coil: 987 Btuh
Total sensible gain on air handling system: 6,115 Btuh
Zone space latent gain: 1,200 Btuh
Infiltration latent gain: 1,639 Btuh
Outside air latent gain: 1,630 Btuh
Total latent gain on air handling system: 4,469 Btuh
Total system sensible and latent gain: 10,584 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 247 CFM
Total Air Handler Vent. Air (20.27% of Supply): 50 CFM
Total Conditioned Air Space: 94 Sq.ft
Supply Air Per Unit Area: 2.6240 CFM/Sq.ft
Area Per Cooling Capacity: 106.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0094 Tons/Sq.ft
Heating Capacity Per Area: 14.57 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,369 Btuh
Total Cooling Required With Outside Air: 0.88 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 11

Air Handler #4 - SALA DE EQUIPOS III - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
SALA DE EQUIPOS
162 1,197 12,344 6,507 Direct Direct
4 III
5 120 624 0 120 120
5pm February
1,458 0.74 3.85 0 120 120

Zone Peak Totals: 162 1,197 12,344 6,507


Total Zones: 1 5 120 624 0 120 120
Unique Zones: 1 1,458 0.74 3.85 0 120 120
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 12

Air Handler #4 - SALA DE EQUIPOS III - Total Load Summary


Air Handler Description: SALA DE EQUIPOS III Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.30 HP
Fan Input: 65% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.67 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: 84° DB, 74° WB, 110.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 1,197 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 2,070 Btuh 120 CFM
Supply Duct sensible loss: 259 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 3,527 Btuh
Heating Supply Air: 1,456 / (.998 X 1.08 X 11) = 120 CFM
Winter Vent Outside Air (100.0% of supply) = 120 CFM
Zone space sensible gain: 10,478 Btuh
Infiltration sensible gain: 1,866 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 686 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 13,030 Btuh
Cooling Supply Air: 13,030 / (.998 X 1.1 X 19) = 624 CFM
Summer Vent Outside Air (19.2% of supply) = 120 CFM
Return duct sensible gain: 343 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,318 Btuh 120 CFM
Blow-thru fan sensible gain: 766 Btuh
Total sensible gain on return side of coil: 2,427 Btuh
Total sensible gain on air handling system: 15,457 Btuh
Zone space latent gain: 1,100 Btuh
Infiltration latent gain: 5,407 Btuh
Outside air latent gain: 3,913 Btuh
Total latent gain on air handling system: 10,420 Btuh
Total system sensible and latent gain: 25,877 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 624 CFM
Total Air Handler Vent. Air (19.22% of Supply): 120 CFM
Total Conditioned Air Space: 162 Sq.ft
Supply Air Per Unit Area: 3.8546 CFM/Sq.ft
Area Per Cooling Capacity: 75.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0133 Tons/Sq.ft
Heating Capacity Per Area: 21.77 Btuh/Sq.ft
Total Heating Required With Outside Air: 3,527 Btuh
Total Cooling Required With Outside Air: 2.16 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 13

Air Handler #5 - ALMACÉN DE MATERIAL ESTÉRIL - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
ALMACÉN DE
235 1,412 5,005 400 Direct Direct
5 MATERIAL ESTÉRIL
2 600 599 0 600 600
5pm February
2,115 2.55 2.55 0 600 600

Zone Peak Totals: 235 1,412 5,005 400


Total Zones: 1 2 600 599 0 600 600
Unique Zones: 1 2,115 2.55 2.55 0 600 600
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 14

Air Handler #5 - ALMACÉN DE MATERIAL ESTÉRIL - Total Load Summary


Air Handler Description: ALMACÉN DE MATERIAL ESTÉRIL Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.29 HP
Fan Input: 65% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.97 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: 84° DB, 74° WB, 110.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 1,412 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 10,352 Btuh 600 CFM
Supply Duct sensible loss: 1,294 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 13,058 Btuh
Heating Supply Air: 2,706 / (.998 X 1.08 X 4) = 600 CFM
Winter Vent Outside Air (100.0% of supply) = 600 CFM
Zone space sensible gain: 5,005 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 658 Btuh
Reserve sensible gain: 6,841 Btuh
Total sensible gain on supply side of coil: 12,504 Btuh
Cooling Supply Air: 12,504 / (.998 X 1.1 X 19) = 599 CFM
Summer Vent Outside Air (100.1% of supply) = 600 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 6,590 Btuh 600 CFM
Blow-thru fan sensible gain: 735 Btuh
Total sensible gain on return side of coil: 7,325 Btuh
Total sensible gain on air handling system: 19,829 Btuh
Zone space latent gain: 400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 19,566 Btuh
Total latent gain on air handling system: 19,966 Btuh
Total system sensible and latent gain: 39,795 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 599 CFM
Total Air Handler Vent. Air (100.13% of Supply): 600 CFM
Total Conditioned Air Space: 235 Sq.ft
Supply Air Per Unit Area: 2.5498 CFM/Sq.ft
Area Per Cooling Capacity: 70.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0141 Tons/Sq.ft
Heating Capacity Per Area: 55.57 Btuh/Sq.ft
Total Heating Required With Outside Air: 13,058 Btuh
Total Cooling Required With Outside Air: 3.32 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 15

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-CENTRAL DE COMUNICACIONES II peaks (sensible) in February at 3pm, Air Handler 1
(CENTRAL DE COMUNICACIONES II ), Group 0, 100.0 x 1.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 100 0.50 14.5 0.080 116 1.280 128
Wall-1-NE-C-M 0 0.83 16.5 0.010 0 0.000 0
Wall-2-NE-C-M 71 0.83 16.5 0.080 94 1.280 91
Partition-3-1 187 18/20 0.080 269 1.600 299
Gls-NE-1-90-Tran 8.0 1.000 12 1.100 108 17.600 141
0%S-0-WS-Solar 8.0 0.650 154 0.250 200
Lights-Prof=1 200 1.000 682
Equipment-Prof=1 200 1.000 682 0
People-Prof=1 6.0 1.000 1,500 1,200
Cool. Infil.Direct CFM 50 604 1,575
Heat. Infil.Direct CFM 0 0.000 0
Sub-total 4,256 2,775 659
Safety factors: +10% +0% +0%
--------- --------- ---------
Total w/ safety factors: 4,682 2,775 659

Zone 2-SALA DE TELECOMUNICACIONES peaks (sensible) in February at 5pm, Air Handler 2 (SALA
DE TELECOMUNICACIONES), Group 0, 66.0 x 1.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 66 0.50 21.0 0.080 111 1.280 84
Wall-1-NE-C-M 79 0.83 19.0 0.080 120 1.280 101
Partition-2-1 75 18/20 0.080 108 1.600 120
Lights-Prof=1 150 1.000 512
Equipment-Prof=1 450 1.000 1,535 0
People-Prof=1 4.0 1.000 1,000 800
Cool. Infil.Direct CFM 20 216 655
Heat. Infil.Direct CFM 0 0.000 0
Sub-total 3,603 1,455 306
Safety factors: +10% +0% +0%
--------- --------- ---------
Total w/ safety factors: 3,963 1,455 306

Zone 3-CENTRAL DE VIGILANCIA Y SEGURIDAD II peaks (sensible) in February at 4pm, Air Handler 3
(CENTRAL DE VIGILANCIA Y SEGURIDAD II), Group 0, 94.0 x 1.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 94 0.50 17.5 0.080 132 1.280 120
Partition-1-1 174 18/20 0.080 251 1.600 278
Lights-Prof=1 250 1.000 853
Equipment-Prof=1 350 1.000 1,194 0
People-Prof=1 6.0 1.000 1,500 1,200
Cool. Infil.Direct CFM 50 585 1,594
Heat. Infil.Direct CFM 0 0.000 0
Sub-total 4,515 2,794 399
Safety factors: +8% +0% +0%
--------- --------- ---------
Total w/ safety factors: 4,876 2,794 399
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 16

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Zone 4-SALA DE EQUIPOS III peaks (sensible) in February at 5pm, Air Handler 4 (SALA DE EQUIPOS
III), Group 0, 162.0 x 1.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 162 0.50 21.0 0.080 272 1.280 207
Wall-1-SW-C-M 0 0.83 11.1 0.010 0 0.000 0
Wall-2-SW-C-M 146 0.83 11.1 0.080 130 1.280 187
Partition-3-1 414 18/20 0.080 596 1.600 662
Gls-SW-1-90-Tran 8.0 1.000 11 1.100 99 17.600 141
0%S-0-WS-Solar 8.0 0.650 186 0.820 793
Lights-Prof=1 250 1.000 853
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 5.0 1.000 1,250 1,000
Cool. Infil.Direct CFM 150 1,623 4,916
Heat. Infil.Direct CFM 0 0.000 0
Sub-total 10,734 5,916 1,197
Safety factors: +15% +10% +0%
--------- --------- ---------
Total w/ safety factors: 12,344 6,507 1,197

Zone 5-ALMACÉN DE MATERIAL ESTÉRIL peaks (sensible) in February at 5pm, Air Handler 5
(ALMACÉN DE MATERIAL ESTÉRIL), Group 0, 235.0 x 1.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 235 0.50 21.0 0.080 395 1.280 301
Wall-1-NE-C-M 7 0.83 19.0 0.010 1 0.160 1
Wall-2-NE-C-M 241 0.83 19.0 0.080 366 1.280 308
Partition-3-1 413 18/20 0.080 595 1.600 661
Gls-NE-1-90-Tran 8.0 1.000 11 1.100 99 17.600 141
0%S-0-WS-Solar 8.0 0.650 154 0.180 144
Lights-Prof=1 353 1.000 1,203
Equipment-Prof=1 470 1.000 1,604 0
People-Prof=1 2.0 1.000 500 400
Sub-total 4,907 400 1,412
Safety factors: +2% +0% +0%
--------- --------- ---------
Total w/ safety factors: 5,005 400 1,412
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 17

Air System #1 (CENTRAL DE COMUNICACIONES II ) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
One or more points or processes failed to be added to the chart:
Cooling process could not be added.

Results out of range.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 18

Air System #2 (SALA DE TELECOMUNICACIONES) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 19

Air System #3 (CENTRAL DE VIGILANCIA Y SEGURIDAD II) Psychrometric


Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
One or more points or processes failed to be added to the chart:
Cooling process could not be added.

Results out of range.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 20

Air System #4 (SALA DE EQUIPOS III) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition
One or more points or processes failed to be added to the chart:
Cooling process could not be added.

Results out of range.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Essalud - Módulo N°12 Administración
Hell Page 21

Air System #5 (ALMACÉN DE MATERIAL ESTÉRIL) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition