LOI.NO. AEML/MTB/2021/LOA/291121
CONTENTS
1.0 GENERAL
1.1. INTRODUCTION
This document describes general requirement of various civil & structural design
parameters that will be considered in the analysis & design of building/structures and
other services/utilities for 220kV AIS to GIS conversion at Aarey EHV, Mumbai,
India.
All Designs shall be prepared in accordance with Indian Standard code of practice and
Project Specifications.
Various codes of practice being referred are listed below. Any other Indian code not
listed shall also be considered, wherever references shall be required.
Following codes shall be used for design.
D. Foundation Engineering
IS-1904:2021 -Design and construction of foundations in soil-General
IS-6403:2016 - Determination of bearing capacity on shallow foundations.
IS-2950:2018 -Design and construction of raft foundation.
IS-2974:2020 -Design and construction of machine foundation
IS-3764:2017 -Code of Safety for Excavation work
E. Reinforcement
IS-1786:2018 - High strength deformed steel bars & wire
IS 2502:2018 -Code of Practice for Bending and Fixing of Bars for
Concrete Reinforcement
F. Loading
Standards
IS-875 - Code of practice for Design loads.
220kV AIS TO GIS CONVERSION AT AAREY
DOCUMENT NO. CIVIL
EHV S/S
SVP010093-AEML-
SH 4 OF 11
AREY-C-DOC-001
All structures shall be designed to resist the loads and load combinations stipulated
below or as per IS875 whichever is maximum.
220kV AIS TO GIS CONVERSION AT AAREY
DOCUMENT NO. CIVIL
EHV S/S
SVP010093-AEML-
SH 5 OF 11
AREY-C-DOC-001
For design purpose, Dead loads shall be considered as per IS875 Part 1 or
Manufacturer’s specification whichever is stringent. Dead loads shall comprise of the
weight of the structure including weights of walls, floors, roofs, finishes, and services
such as ducts, pipe works etc. and other permanent construction. For design, following
unit weights of material will be considered.
For GIS Building basement wall, a surcharge of 10 kN/m2 shall be considered due to
vehicular traffic inside Substation.
Coefficient of Active Earth Pressure considered as 0.33
Coefficient of Earth Pressure at rest is considered as 0.5
Buildings and structures shall be designed in accordance with IS875 Part 3 and the
following parameters shall be considered:
Where,
Where,
Kd = Wind directionality factor (clause 7.2.1)
Ka = Area averaging factor (clause 7.2.2)
220kV AIS TO GIS CONVERSION AT AAREY
DOCUMENT NO. CIVIL
EHV S/S
SVP010093-AEML-
SH 7 OF 11
AREY-C-DOC-001
Seismic condition should be considered (if required) in the design in accordance with
IS 1893-2016.
Damping value = 5%
Seismic weight is generated with 100% Dead load +100% of Actual Equipment
operating + Appropriate reduction in total live load less actual equipment load.
Note:
Seismic force will be calculated by STAAD PRO V8i program. The base shear for
wind load and seismic load should be calculated and the design shall be carried out
for the governing load case.
4.0 DESIGN
4.1 MATERIALS
(a) Cement
(b) Concrete
The concrete grade used in the various works shall be as follows:
(c) Reinforcement
Steel reinforcement shall be TMT Fe 500 D as per IS-1786-2008 High Strength
Deformed Bars. Only TMT bars of TISCO, SAIL, RINL or equivalent shall be
used.
E250 Rolled section built up sections pipes tubes and plates etc as per IS 2062
Load combinations as per IS 875 Part 5 with appropriate load factors are listed below
for producing the worst loading conditions for design.
220kV AIS TO GIS CONVERSION AT AAREY
DOCUMENT NO. CIVIL
EHV S/S
SVP010093-AEML-
SH 9 OF 11
AREY-C-DOC-001
4.4 FOUNDATION
For foundation design following soil parameter shall be used for Aarey EHV. The
engineering properties shall be considered after conducting soil investigation.
220kV AIS TO GIS CONVERSION AT AAREY
DOCUMENT NO. CIVIL
EHV S/S
SVP010093-AEML-
SH 11 OF 11
AREY-C-DOC-001
5.0 FINISHES
All finishes shall be as per Technical Specifications in tender and shall be a part of
Architectural Drawings.