Professional Documents
Culture Documents
Q.1. For the system shown in figure below determine the generator voltage .
Select base MVA equal to 100 MVA and base voltage 15 kVA of the generator
terminal.
(CSVTU April-May 2011)
Q.2. Draw the per unit impedance diagram for the power system shown in fig
and use a base of 100 MVA ,220 kV in 50 Ω line . The rating of the generator
motor and transformer are
(CSVTU April-May 2009)
''
Gen - 40 MVA 25 kV X =20 %
Motor - 50 MVA 11 kV X ' ' =30 %
Transformer - 40 MVA 33 y /220 y kV X = 15 %
Transformer - 30 MVA 11∆ /220 y kV X = 15 %
0
Ans: V g=0.9826 ∠ 13.20
Q.6. A 19 MVA ,11 kV three phase generator has a reactance of 25 % .The
generator supplies two motor through transformer and transmission line as
shown in fig . Taking the generator rating as a base rating draw reactance
diagram and indicate the reactance in per unit. The reactance of the line is 100
Ω (CSVTU April-May 2008, Nov-Dec 2009)
Data given
Transformer - 100 MVA , 11 /132 kV , 6 % reactance
Transformer - 30 MVA , 132/ 10 kV , 5 % reactance
Motor 1 - 50 MVA 10 kV , 15 % reactance
Motor 2 - 40 MVA 10 kV , 15 % reactance
=
Q.10. The one- line diagram of a three-phase power system is shown in Figure
1(c) .Select a common base of 100 MVA & 22 kV on the generator side. Draw
an impedance diagram with all impedances marked in per unit.
Q.11.
Q.12. A 100 MVA, 13.8 KV, 3-phase generator has a reactance of 20%. The
generator is connected to a 3-phase transformer T 1rated 100 MVA 12.5 KV 1110
KV with 10% reactance. The h.v. side of the transformer is connected to a
transmission line of reactance 100 ohm. The far end of the line is connected to
a step down transformer T 2 made of three single-phase transformers each
rated 30 MVA, 60 KV / 10 KV with 10% reactance the generator supplies two
motors connected on the l.v. side T 2 as shown in Fig.. The motors are rated at
25 MVA and 50 MVA both at 10 KV with 15% reactance. Draw the reactance
diagram showing all the values in per unit. Take generator rating as base.
Ans; The reactance diagram is shown in Fig.
Q .2. In a 3−ϕ 4 wire system, the currents R,Y,B, lines under abnormal
conditions of loading are as follows.
⃗
I R =100∠30 A , ⃗
0
I Y =50∠300 A , ⃗
0 0
I B=30 ∠ 180 A
Calculate the positive, negative and zero sequence in the R- line and return
current in neutral wire.
Solution:
Ans: I R0 =27.29∠ 4.692 , I R 1=57.98∠ 43.29, I R2 =18.92∠ 24.960 , I n =81.87 ∠ 4.69
Q .6. The current flowing in a line towards a balanced load connected in delta
0 0
I A=100 ∠ 0 , I B=141.4 ∠225 , I C =100 ∠90
Determine a general expression for the relation b/w the symmetrical
components of line currents and phase currents in load i.e. between I A 1 and I ab 1
& I A 2& I ab 2 . find I ab for its symmetrical components. (CSVTU Aril-May 2011)
Ans: I A 0=0 , I A 1=111.52 ∠−15 , I A 2=29.87 ∠105
Q .7 A delta connected balanced resistive load is connected across an
unbalanced 3−ϕ supply as shown in fig with currents in lines A & B specified,
find the symmetrical components of line current. Also find the symmetrical
components of delta currents. Do you notice any relationship between
symmetrical components of line and delta current comment? (CSVTU April-May
2011)
Q.8 A single phase resistive load of 100 KVA is connected across terminal BC of
balanced supply of 3KV. Calculate symmetrical component of the line current ?
Ans: I a 0=0 , I a 1=19.24 ∠−150 , I a 2=19.24 ∠ 300
Q.9. A delta connected resistive load is connected across a balanced 3−∅ supply
of 400 V as shown in figure. Find the symmetrical component of line current &
delta current.
Q.10. One conductor of a 3−∅ line is open. The current flowing through line a
is 10 A . the delta connected load is having z ohms per phase. The current in line
b is 10 A with phase difference of 1800 with current in line a, line c is open.
Find the symmetrical components of the line current . Assume line current in
line a as reference Draw suitable circuit diagram.
0
Ans: I a 0=0 , I a 1=5.77 ∠−30 , I a 2=5.77 ∠ 30
Q.11. The line volt across a three phase star connected load are 100V, 150Vand
200Vrespectively determine. The symmetrical components of delta and star
voltages. (CSVTU Nov-Dec 2008)
Ans: V a 0 =0 ,V a 1=−134− j 50.5 ,V a 2=34+ j50.5
Q. 2.Draw all the sequence networks for the system showing in figure.
Determine fault current when L-G fault occur at point F. The per unit
reactance all referred to the same base are as follows .Assuming all voltage is
per unit voltage.
Ans: I f =− j 6.42 p . u
Q.3. A 3-∅ 10 MVA 11KV synchronous generator with a solidly grounded neutral
point supply a feeder . The relevant impedance of the generator & feeder are
as follows
Generator Feeder
Positive j 1.2 Ω j 1Ω
Negative j 0.9 Ω jΩ
Zero j 0.4 Ω j3Ω
A fault from one phase to ground occur at the far end of the feeder . Determine
fault current .
Ans: I f =2.54 KAmp
Q.4.Two 11 KV, 20 MVA,3-ϕ star connected generator operates in parallel as
shown in figure . The positive ,negative & zero sequence reactance are J0.10 p.
unit . The star point of one of the generator is isolated & that of the earth is
through fault occur at the terminal of one of the generator. Estimate (a) fault
current (b) current in grounding resistor, and (c) the voltage across grounding
resistor
Q.5. A 3-∅, 11KV, 20MVA generation with +ve, -ve & zero sequence reactance
as j0.4 p.u. j0.4 p.u. & j0.1 p.u. respectively is grounded through a reactance
of 0.6Ω . Calculated the fault current for a single line to ground fault .
Ans: I f =2.506 ∠−90° p .u
Q.6. A salient pole generator without damper is rated 20 MVA ,13.8 KV &
has a direct axis sub transient reactance of 0.25J p.u. The negative & zero
sequence reactance’s are respectively 0.35J & 0.10J p.u. The neutral of
generator is solidly ground .Determine the sub transient current in the
generator & line to line voltage for sub transient cond n when line to line
fault occur at the generator terminal .
Ans: I f =2.887 ∠180° p .u . , V ab=1.751 p . u . ,V bc=0V ca=1.751 ∠180° p .u
Q. 7. Find the sub transient current & line to line voltage at the fault under
sub transient cond n when a line to line fault occur at the terminal of a
generator rated 20 MVA, 13.8 KV has a sub transient reactance of j0.5p.u. &
negative an zero reactance’s of j0.18 & j 0.2 respectively . The neutral is
solidly grounded.
Ans V ab=0.795 p . u .V bc=0 ,V ca =1.795 ∠180°
Q.8 A 25 MVA 13.2 alternator with solidly grounded neutral has a sub
transient reactance of j0.25 p.u. The negative & zero sequence reactance are j
0.35 p.u. & j0.1 p.u. respectively . A single line to ground fault occur at the
terminal of unloaded alternator. Determine the fault current & line to line
voltage (CSVTU Nov-Dec 2011, April-May 2012)
Ans: l f =4.286 ∠−90 °
Q.9. Determine the fault current and line to line voltage at the fault when a
line voltage at the fault occur at the terminal of alternator described in
precious example .
Ans: I f =2.887 ∠180° p .u
Q.10. A 50 MVA , 11KV ,3-∅ synchronous generator was subjected to different
types of fault. The fault are as follows ⟶
L-G fault ⟶ 4200 A, L-L fault ⟶ 2600 A, L-L-L fault ⟶ 2000 A
The generator neutral is solidly grounded . Find the per unit value of three
sequence reactance of generator . (CSVTU Nov-dec2009)
Ans: X 0 p .u .=0.126 p .u , X 1 p .u .=1.312 p .u , X 2 p .u .=0.43 p . u
Q.14. The section bar A & B are linked by a bus bar reactor rated at 6 MVA
with 10% reactance . On bus bar A there are two generators each of 12 MVA
with 10% reactance & on B two generators each of 10 MVA with 10%
reactance . Find short circuit MVA at fault point F as shown in fig
Ans:
(a) Sub transient current in the fault¿ 10705.037 A
(b) I m = j 1.6 p .u . , I g = j 2.495 p . u . , I f =8955.491 A
f f actual
Q.17. A 15 MVA, 6.9 kV generator, star connected hs positive, negative and zero
sequence reactance of 25%,25% and 8% respectively. In order to reduce the
current in case of a falut to ground an inductive reactor with 6% reactance
is corrected between neutral and ground. A line to line fault occurs at the
terminals of the generator when it is operating at rated voltage at no load
condition. Find the initial symmetrical line current and voltage drop from
line to neutral. (CSVTU April- may 2008)
(i) If the fault does not involve ground
(ii) If the fault is solidly grounded at the instant of its occurance
Q.2. For the system shown in figure, an inductor of reactance 0.6 p.u./phase is
connected at the midpoint of transmission line. Determine the steady state
power limit under the following conditions . When inductor switch S is open.
Ans: Pe =0.8 ∠−90 ° pu
Q.4. A loss free generator supply 5 to an infinite bus. The steady state limit of
the system being 100 MW. Determine whether the generator will remain in
synchronism If the prime mover input is increased by 30 MW.
(CSVTU Noe-Dec2009)
Ans: 1A < A 2 Hence system will remain in synchronism.
Q.5. A loss free generator supplying 80 MW to an infinite bus bar steady state
limit of system is 150 MW & prime mover input is increased by 40 MW.
Determine whether the system will remain in synchronism.
Ans: A1 < A2 ,Hence, system will remain in synchronism.
Q.6. A double circuit 3-ϕ feeder connected a single generator to large n/w The
power corresponding to limit of steady state stability for each circuit is 100
MW. The line is transmitting 80 MW. When one of the circuit is suddenly
switched off, determine with the appropriate diagram, whether the generator is
likely to remain in synchronism.
Ans: A1 < A2 Hence generator is likely to remain in Synchronism.
Q.9 Give the system of Fig. where a three-phase fault is applied at the point P
as shown.
Find the critical clearing angle for clearing the fault with simultaneous
opening of the breakers 1 and 2. The reactance values of various components
are indicated on the diagram. The generator is delivering 1.0 pu power at the
instant preceding the fault.
Ans: δ cr =55.80
Q .10.Find the critical clearing angle for the system shown in Fig. for a three-
phase fault at the point P The generator is delivering 1.0 pu power under
prefault conditions. (CSVTU April-May 2009)
0
Ans: δ cr =49.1
Q.2 On the System Consisting of two generating plant the incremental Cost in
d C1 150∧d C 2
Rs/M.W. Hrs With P1∧P2 in M.W. Hour =0.15 P 1+ =0.25 P 2+175 the
d P1 d P2
.∧d P L
System is operating on economic dispatch with P1=P2=200 M .W =0.2 .
d P2
Find the penalty Factor of plant 1.
Ans: L1=1.56
Q.3. A power System has 2 generating plant and the power being dispatch
economic with P1=150 M .W .∧P 2=275 M . W .the loss Co-efficient are B11=0.10 ×100
−2
, B12=−0.01 ×10−2 & B22=0.13 ×10−2. To rise the total load on the system by 1 M.W.
will Cost and additional Rs. 200 Per hours. (CSVTU April-May 2011)
Find:-
(a). Penalty Factor of plant 1.
(b). The additional Cost Per hours to increase the O/P of Plant 1 by 1 M.W.
d C1 Rs .
Ans: =151 M . W . hr .
d P1
Q.4. In a two plant System the entire load is located at plant 2 which is
connected by plant 1 by transmission Line. The Plant Supply 100 M.W. of a
power with a correspond mission Loss of 5 M.W. Calculate the Penalty factor
for the 2 Plant.
Ans : L2=1
Q.5. The two unit of a power System have Following Cost Curve.
2 Rs 2 Rs
C 1=0.1 P 1+ 40 P 1+120 & C 2=0.2 P 2+30 P2 +100 . The daily load Curve of a
hr hrs
power System as Shown in Fig.
Consider the 24 hours period from 6 a.m. morning to 6 a.m. next morning it be
more economic al to keep both the unit in Service for this 24 hours period or to
remove one of the unit service from 12 hours for the light load.
Assume that a cost of Rs.400 is increased in taking either unit of the line to
returning it is Service after 12 hours.
(CSVTU Nov-Dec 2012)
Ans: The total cost of expenditure option (i) is less it will be more economic to run both
genr Continuous for 24 hrs.
Q.6 A System Consist of two Plant Connected by a mission Line & load that is
located at Plant 2 data for the loss equation consist for the inform that 100
MW transmitted from plant 1 of the load result in a loss of 10 M. The
incremental fuel cost to the two unit can be show the following eqn.
d C1
=0.007 P1+ 4.1 Rs / MW . hrs
d P1
d C2
=0.014 P2 +4.6 Rs /MW .hrs .
d P2
Calculate the value listed below for the System λ=6.5 Rs/ MW . hrsCalculate :-
(a). P1∧P2 & Power deliver E0 the load for economic dispatch ( Loss is
considered)
(b). P1∧P2 If total Power is taken as Part (a) & Power deliver to the load for
economic dispatch (Loss is neglected)
Ans: P1=184.68 W ∧, P2 =56.62W
Q.10. The fuel input per hour of two plant are given as
F 1=0.2 P 21+ 40 P 1+120 Rs/ Hr
2
F 2=0.2 5 P2 +30 P2 +150 Rs / Hr
Determine the economic operating schedule and the corresponding
cost of generation if the maximum and minimum loading of each unit is 100
MW and 25 MW , the demand is 180 MW and the transmission losses are
neglected . if the load is equally shared by both unit , determine the saving
obtained by loading the unit as per equal incremental production cost.
(CSVTU April May 2009)
Ans: Saving=1.32 Answer
Q.11. For the System Shown below the voltage at bus C is V c =1.0 ∟0 p.u. The
Current in the line AC & BC are 1.05 ∟0 P .V . & 0.9 ∟0 P . V . respectively. The
line impedance are as follows.
Z AC =( 0.05+J 0.20 ) P . V .
Z BC =( 0.04+ J 0.16 ) P . V .
ZCD = ( 0.03+J 0.12 ) P .V .
Find the Loss Co-efficient and Mission Loss.
(CSVTU Nov –Dec 2009)
Ans: P L=0.207 P . U .
Q.12. On the System Consisting of two generating plant the incremental costs
in rupees per Mega Walt hours with P1∧P2 in Mega Walt are:-
d C1
=0.15 P 1+150
d P1
d C2
=0.25 P 2+17 5
d P2
MW ∧∂ PL
Given P1=P2=200 Find penality factot for plant 1.
∂ P2
Ans: L1=1.5625
Q.3. Determine Y BUS for 4-bus system shown in figure. The linae series
impedances are as follows:
Line(bus to bus) Impedance(pu)
1-2 0.25+ j1.0
1-3 0.20+ j0.8
1-4 0.3+ j 1.2
2-3 0.2+ j 0.8
3-4 0.15+ j 0.6
Ans:
[ ]
(0.725− j 2.9) −(0.235− j 0.94) −(0.294− j 1.176) −( 0.196− j0.784 )
−(0.235− j 0.94) 0.529− j 2.116 −( 0.294− j 1.176 ) 0
¿
−(0.294− j 1.176) −(0.294− j 1.176) (0.98− j 3.92) −(0.392− j 1.568)
−(0.196− j 0.784) 0 −(0.392− j 1.568) 0.588+ j2.352
Ans:
[ ]
5− j 15 −(1.66− j5) −(1.25− j3.75)
Y Bus = −(1.66− j 5) 2.91− j 8.75 −(1.25− j3.75)
−(1.25− j 3.75) −(1.25− j 3.75) 4.58− j13.75
Q.5. Per unit Impedance are indicated Shunt admittance be neglected.
Determine Y bus (CSVTU April-May 2010)
Ans :
[ ]
0.47−J 1.88 −2.35+ J 9.411 −0.588+J 2.35 0
¿ −2.35+ J 9.411 0.692−J 2.768 −0.294+ j 11.76 −1.470+ j 5.88
−0.588+ J 2.35 −0.294+ j 11.76 0.346−J 1.384 −1.176+ j 4.70
0 −1.470+ j5.88 −1.176+ j 4.70 0.653−J 2.614
Q.6. Determine Y bus for the five bus system shown in fig
Ans:
[ ]
− j12 j5 0 j2 j5
j5 − j9 j 4 0 0
Y bus = 0 j 4 − j7.33 j3.33 0
j2 0 j3.33 − j9.33 j 4
j5 0 0 j 4 − j9
Q.13. A three bus power system shown in figure .The relevant per unit line
admittances on 100 MVA base are indicated on diagram and bus data are
in table. Form Y and determine voltages at bus 2 and 3 bus after first
iteration using Gasuss-Seidal method. Take acceleration factor α =1.6 .
Ans :The voltage at the end of first iteration
(1 ) 0
V 1 =1.02∠ 0
V (12 )=.992− j0.0499
(1 )
V 3 =0.9536− j 0.1509
Q.14. Fig. shows the one-line diagram of a simple three bus power system with
generation at bus 1.The magnitude of voltage at bus 1 is adjusted to 1.05
p.u of line impedances are marked in p.u. on a 100 MVA base. Using Gauss-
Seidel method, determine the phasor values of the voltage at load buses 2
& 3 (P-Q buses) after first iteration.
(CSVTU April-May 2011)
(1 ) (1 )
Ans: V 2 =0.9825+ j. 09 V 3 =1.0011− j 0.0358
Q.15. The following data is the system data for a load flow solution. 7
Bus Code Admittance
1-2 2-j8.0
1-3 1-j4
2-3 0.666-j2.664
2-4 1-j4
3-4 2-j8
The schedule of active and reactive power.
Bus Code P Q V Remarks
1 - - 1.06 Slack bus
2 0.5 0.2 1+j0 PQ bus
3 0.4 0.3 1+j0 PQ
4 0.3 0.1 1+j0 PQ
Determine the voltage at the end of font iteration using Gauss –Siedal
method. Take α =1.6. (CSVTU Nov-Dec2011,April-May 2010,April-
May 2012)
Ans: V 3 acc =0.98864−0.0528 j
Q.16. For the n/w shown in Fig. Obtain the Complex bus bar voltage at bus 2 at
the end of the first iteration use Gauss-Seidel Method Line Impedance Shown in
Fig.
(CSVTU April –May2009)
V 1=1 . 0 ∟0 ° , P2 + j Q2=−5 . 96+ j1 . 46
¿ V 3∨¿ 1 . 02
Assume V 03=1. 02 ∟0 °∧V 02 =1∟ 0°
(1)
Ans :V 2 =0.995− j0.0312