Based on BS EN 12056-2:2000
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Stack Number :
Stack serving from Level : to
Number of floors served : 1
Fixtures Quantity Dischage Unit (DU) Total DU
(l/s) (l/s)
WC 0 2.0 0.0
Shower 0 0.8 0.0
Sink 0 0.8 0.0
Washing Machine 0 0.8 0.0
Wash Basin 0 0.5 0.0
Bidet 0 0.5 0.0
Sub-Total DU = 0.0
Total DU, SDU, l/s = 0.0 x 1 floors = 0
Waste water flowrate, Qww = K√(SDU) = #VALUE! l/s
Nominal Diameter for Stack & Stack Vent : mm -> Read From Pipe Size Sheet
Nominal Diameter for Secondary Vent : mm -> Read From Pipe Size Sheet
Description Definition
Sanitary appliances are connected to partly filled branch discharge
Single discharge stack system with partly pipes. The partly filled branch discharge pipes are designed with a
filled branch discharge pipes filling degree of 0.5 (50 %) and are connected to a single discharge
stack.
Sanitary appliances are connected to small bore branch discharge
Single discharge stack system with small pipes. The small bore branch discharge pipes are designed with a
bore discharge branch pipes filling degree of 0.7 (70 %) and are connected to a single discharge
stack.
Sanitary appliances are connected to full bore branch discharge
pipes. The full bore branch discharge pipes are designed with a
Single discharge stack system with full
filling degree of 1.0 (100 %) and each
bore branch discharge pipes
branch discharge pipe is separately connected to a single discharge
stack.
Drainage systems type I, II and III may also be divided into a black
Separate discharge stack system water stack serving WC’s and urinals and a grey water stack serving
all other appliances.
led branch discharge
are designed with a
to a single discharge
e branch discharge
e designed with a
d to a single discharge