LOAD FLOW ANALYSIS

Bus 1
Load Bus Voltage Bus Voltage Current (A) Apparent True and
Power (kV) (%) Power Reactive
Factor (kVA) Power
(kW+jkVAr)
100% 345 100 83.5 49893 49853+j1990
95% 345 100 82.5 49287 46221+j17113
90% 345 100 82.1 49055 43381+j22903
85% 345 100 81.8 48888 40695+j27091
80% 345 100 81.6 48755 38097+j30425
Table 1

Bus 2
Load Bus Voltage Bus Voltage Current (A) Apparent True and
Power (kV) (%) Power Reactive
Factor (kVA) Power
(kW+jkVAr)
100% 13.77 99.79 2087.4 49785 49785+j0
95% 13.603 98.57 2062 48584 46155+j15170
90% 13.539 98.11 2052.3 48128 43315+j20979
85% 13.493 97.78 2045.3 47800 40630+j25180
80% 13.456 97.51 2039.7 47540 38032+j28524
Table 2
Bus 1
Load MVA Bus Voltage Bus Voltage Current (A) Apparent True and
(kV) (%) Power Reactive
(kVA) Power
(kW+jkVAr)
50 345 100 83.5 49893 49853+j1990
40 345 100 66.8 39936 39916+j1275
30 345 100 50.1 29967 29958+j718
20 345 100 33.4 19987 19984+j319
10 345 100 16.7 9997 9997+j80
Table 3

Bus 2
Load MVA Bus Voltage Bus Voltage Current (A) Apparent True and
(kV) (%) Power Reactive
(kVA) Power
(kW+jkVAr)
50 13.77 99.79 2087.4 49785 49785+j0
40 13.778 99.84 1670.8 39873 39873+j0
30 13.785 99.89 1253.7 29934 29934+j0
20 13.791 99.93 836.2 19973 19973+j0
10 13.796 99.97 418.2 9994 9994+j0
Table 4
Figure 1