CT Test Report
Tested object
3366957 Test time 2017-6-16 9:34
number
Excitation、Ratio、
Winding level PR Test item
Error、Transient
Parameter
Winding serial
Rated frequency 50Hz
number
Rated burden (VA) 10VA Power factor 0.5
Rated primary Rated secondary
30A 0.5A
current (A) current (A)
Complex error ALF 11.73828
Result
Resistance result
Measured resistance Converted
(Ω) resistance 75℃(Ω)
Excitation result
Knee point voltage Knee point current
205.7664 0.03335325
(V) (A)
Unsaturated Remanence
16.1941 95.4911
inductor Lu(H) coefficient Kr(%)
Secondary Limit electromotive
0.8152183 400
time-constant Ts(S) force Eal(V)
Instantaneous peak
Complex error
error
Accuracy limit Instrument safety
11.73828
factor factor
Symmetrical
Transient area
short-circuit
factor
current multiple
Calculation Rated knee point
coefficient potential Ek
Ek Corresponding Ie Rated Ual
Test report 2/5
Ual Corresponding
Ial
Ratio result
Measured ratio 30.0106 Polarity Same polarity
Ratio error (%) Angle error (') -0.6548288
Turns ratio
Test report 3/5
Designate
d
I(A) U(V) I(A) U(V) I(A) U(V) I(A) U(V)
Test report 4/5
Test report 5/5
Test: Audit: