Professional Documents
Culture Documents
1. DC Machine
2. Tacho-meter
3. Power Supply Unit
4. Terminal Board
5. Digital Multi-meter (DMM)
6. Load Bank
7. Rheostat
1. Voltage drop due to armature resistance: The armature current Ia which is the sum of the field
current If & the Load Current IL flows through the armature thus due to the armature resistance
IaRa voltage drop due occurs.
2. Voltage drop due to armature reaction: Reaction between the armature field (due to current I a)
and the main field (due to I f) gives rise to two fields at some angle to each other. Due to all this
there is a shift in the magnetic axis and redistribution of charges takes place in some of the
conductors thus producing a significant voltage drop. This voltage drop is named as the voltage
drop due to armature reaction.
3. Voltage drop due to field current reduction: When the voltage drop due to the above mentioned
reasons take place, the terminal voltage decreases which causes the field current to decrease
further as field current is given by I f Vt / Rf .Due to field current decrease, the magnetic field
strength decreases, thus less voltage is induced.
Circiut daigram:
Procedure
1. In this experiment we consider shunt dc generator and measure field current, terminal voltage and
load current.
2. To measure filed current milli-ampere meter is connected in series with the filed winding circuit
and in series with rheostat to control the filed current.
3. For terminal voltage voltmeter is connected in parallel with the armature winding and also for
load current ammeter is connected in series with voltmeter.
Observations
No Load Voltage = VtA = ____111___ V
IA=IL+IF
(A) (V)
102
Terminal volatge (V)
100
98
96
94
92
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Load current(A)
Table 3
(Calculation for all three components of voltage drops independently using Table 1 & Table 2)
Ans: Armature reaction increases with load because when load increases armature current increases to
fulfill the demand of load thus emf induces in the armature circuit opposite to the terminal voltage.
Which of the following drops would be present in separately excited generator and series Generator?
Discuss with reason?
Ans: Drop due to armature reaction is present in both series and shunt DC generator. As in series Dc
generator load current is equal to the field current, as field current increases voltage also increases but at
certain limit it starts decreasing because of the excessive demagnetization due to armature reaction.
Write all types of Losses occurring in a DC Generator?
1. Armature reaction
2. Increase in load/Drop in armature circuit
3. Decrease in filed current
4. Friction loss in bearings and in commutator.
Precautions
DC Motor acting as prime mover for the generator should not be over powered or underpowered so that it
goes beyond its prescribed speed. A suitable operating speed should be around 1500 rpm.And terminals of
field windings should be properly placed