HAPCO Bus Amps: 160 220/110 Volt, 3Phase 4Wire 60Hz

PRO-DUCT FACTORY Main: 160 MCCB


PANEL PB4-MECH. Equipments Mounting: SURFACE
CABLE SIZE (mm2) : 4 x 50 CU/XLPE/PVC+ 1 x 25 G No. of Ways: 24 Feeder Entrance: Bottom , Right Side ( behind meter )

CKT. Load KVA LOAD LOAD CABLE SIZE Bkr AMP/ CKT. Load KVA LOAD LOAD CABLE SIZE Bkr AMP/
PH
NO. Type Description R Y B (KVA) (mm2) Type POLE NO. Type Description R Y B (KVA) (mm2) Type POLE

1 M TAUROS-1 4.26 R 2 M 3.11


8.51 3x16 MCB 50/2
3 M 4.26 Y 4 M SHEAR MACHINE 3.11 9.34 4x10+1x10 MCB 32/3
5 M TAUROS-2 4.26 B 6 M 3.11
8.51 3x16 MCB 50/2
7 M 4.26 R 8 M 2.06
9 M TAUROS-3 4.26 Y 10 M LOCK FORMER-1 2.06 6.17 4x6+1x6 MCB 25/3
8.51 3x16 MCB 50/2
11 M 4.26 B 12 M 2.06
13 M SPOT WELD-1 2.42 R 14 M 2.06
4.84 3x10 MCB 32/2
15 M 2.42 Y 16 M LOCK FORMER-2 2.06 6.17 4x6+1x6 MCB 25/3
17 M SPOT WELD-2 2.42 B 18 M 2.06
4.84 3x10 MCB 32/2
19 M 2.42 R 20 M 0.64
21 M DRILL MACHINE 0.74 Y 22 M GROVING MACHINE 0.64 1.91 4x4+1x4 MCB 16/3
1.47 3x4 MCB 16/2
23 M 0.74 B 24 M 0.64
25 M SPARE MCB 16/1 R 26 M 5.08
27 M ELBOW BEND 1.02 Y 28 M CORNET MACHINE 5.08 15.24 4x16+1x16 MCB 50/3
2.05 3x4 MCB 16/2
29 M 1.02 B 30 M 5.08
31 M SPACE R 32 M 1.65
33 M SPACE Y 34 M DUCT ASSEMBLY 1.65 4.95 4x6+1x6 MCB 20/3
35 M SPACE B 36 M 1.65

Sub Feed Panel Load Total Connected Load 82.52 KVA Totals Connected Per Phase (KVA)
SUBTOTALS R Y B
REC Load KVA Receptacle Load 0.00 KVA Demand Factor 0.70 27.95 27.29 27.29
LTG Load KVA Lighting Load 0.00 KVA Demand Load 57.77 KVA
MECH Load KVA Mech/Equipment Load 82.52 KVA
Demand Load Amps 151.60 Ampere BRANCH FEEDERS TYPE : CU/PVC/PVC