Lu > Lc
Lu = L = unbraced length
Lc = unbraced length limit for compact
L 703270C b
Fb = 0.6 Fy
rT Fy
703270Cb L 3516330Cb
Fb = (eqn 506-6)
Fy rT Fy
L 3516330Cb
Fb = (eqn 506-7)
rT Fy
d 1d d
2 32 6
M1
M2
Sample:
50 kN
40 kN m
m
0.75
DFBA 10.5 0.46154
0.75 1
10.5 12
DFBC 0.53846
FEM’s
1
M BA 4010.5 2 1.5 551.25kN m
12
1
M BC 5012 2 600kN m
12
Final M’s
MA 0
M B 551.25 0.53846 600 0.46154 573.75kN m
0.53846
M C 600 600 551.25 613.12kN m
2
Span AB
wl M AB M BA 4010.5 573.75 w
VAB 155.36kN
2 L 2 10.5
wl M BA M AB x
VBA
2 L
Point of zero shear VA
x 3.8840m
M pos
1
155.36 3.884 301.70kN m F 0
2 VA wx
Span BC
VA
5012 573.75 613.12 x
VBC 296.72kN w
2 12
x 5.9344m
1
M pos 296.72 5.9344 573.75 306.68kN m
2
Using W24 and A-36 steel, determine the lightest section for the prismatic beam.
b. Assume that the lateral supports are at the vertical supports only.
(506-7)
1172100C b
Fb 2
65.162MPa
L
r
T
(506-8)
82740C b 827401.75 228.6 24.89
Fb 125.93MPa
Ld 10500 623.06
A
f
Fb 125.93MPa
Span BC
L = 12 m
L 12000
202.77
rT 59.18
M1 573.75kN m
M 2 613.12kN m
2
573.75 573.75
C b 1.75 1.05 0.3 1.0301
613.12 613.12
7032701.0301
54.047
248
35163301.0301
120.85 202.77
248
Use 506 7
827401.0301 228.6 24.89
Fb 64.861MPa
12000 623.06
1172100C b 1172100 1.0301
Fb 29.365MPa
L
2
202.77 2
r
T
0.75
DFBA 10.5 0.46154
0.75 1
10.5 12
DFBC 0.53846
FEM’s
1
M BA 4010.5 2 1.5 551.25 kN m
12
1
M BC M CB 5012 2 600 kN m
12
Final M’s:
MA 0
M B 551.25 0.53846 600 0.46154 573.75 kN m
1
M C 600 600 551.25 0.53846 613.13 kN m
2
Span AB:
4010.5 0 573.75
VBA 155.36 kN
2 10.5
155.36
x 3.8839 m
40
1
M pos 155.36 3.8839 301.70 kN m
2
40 3.5
2
10.5
@x 3.5 m, M 155.36 3.5 298.75 kN m
3 2
40 7
2
2
@x 10.5 7 m, M 155.36 7 107.50 kN m
3 2
Span BC:
5012 573.75 613.13
VBC 296.72 kN
2 12
296.72
x 5.9344 m
50
1
M pos 296.72 5.9344 573.75 306.68 kN m
2
50 4
2
@x 4 m, M 296.72 4 573.75 213.13 kN m
2
50 8
2
@x 8 m, M 296.72 8 573.75 200.01 kN m
2
W24 103
rt 59.18 mm
d 623.06 mm
b f 228.60 mm
t f 24.89 mm
Segment 1:
Design M = 298.75 kN-m, L = 3.5 m, L r 59.142
t
C b 1.75
703270C b
70.446 L
Fy rt
Fb 0.6Fy 0.6 248 148.8 MPa
M 298.75 10 6
Req' d Sx 2007.7 103 mm 3
Fb 148.8
Segment 2:
Design M = 301.70 kN-m, L = 3.5 m, L r 59.142
t
C b 1.0
703270Cb
53.252 L
Fy rt
3516330Cb
119.07 L
Fy rt
2 248 59.142 2
Fb 248 144.94 MPa 0.6Fy
3 105500001.0
M 301.70 10 6
Req' d Sx 2081.5 103 mm 3
Fb 144.94
Segment 3:
Design M = 573.75 kN-m, L = 3.5 m, L r 59.142
t
2
107.5 107.5
C b 1.75 1.05 0.3 1.9573 2.3
573.75 573.75
703270Cb
74.501 L
Fy rt
Fb 0.6Fy 148.8 MPa
M 573.75 10 6
Req' d Sx 3855.8 103 mm 3
Fb 148.8
Segment 4:
Design M = 573.75 kN-m, L = 4 m, L r 67.590
t
2
213.13 213.13
C b 1.75 1.05 0.3 2.1814 2.3
573.75 573.75
703270Cb
78.651 L
Fy rt
Fb 0.6Fy 148.8 MPa
M 573.75 10 6
Req' d Sx 3855.8 103 mm 3
Fb 148.8
Segment 5:
Design M = 306.68 kN-m, L = 4 m, L r 67.590
t
C b 1.0
703270Cb
53.252 L
Fy rt
3516330Cb
119.07 L
Fy rt
2 248 67.59
2
Fb 248 138.70 MPa 0.6Fy
3 105500001.0
M 346.05 106
Req' d Sx 2494.9 103 mm 3
Fb 138.70
Segment 6:
Design M = 613.13 kN-m, L = 4 m, L r 67.590
t
2
200.01 200.01
C b 1.75 1.05 0.3 2.1244 2.3
613.13 613.13
703270Cb
77.616 L
Fy rt
Fb 0.6Fy 148.8 MPa
M 613.13 106
Req' d Sx 4120.5 10 3 mm 3
Fb 148.8
Req' d Sx 4120.5 103 mm3
Use W21122, Sx 4474 103 mm3
Quiz # 2
1. Determine the lightest section for the rafters using A-50 steel. Assume full lateral
supports.
200
200 200
200 200
100 100
2.3 m
I I
1.5I 1.5I 4m
200 c cosθ
200
200
100
C 2.3 m
I 100 200 200
B
1.5I 4m A B C
4m m
A
M BC 2 232.93 kN m
5.1
c
c c c c
M CB
200
5.1 2
1.6 2 3.5 3.3 2 1.8 219.62 kN m
Final moments:
M B 232.93 0.67721 157.71 kN m
1
M C 219.62 232.93 0.32279 254.51 kN m
2
200c 3.5 1.8 157.74 254.51
VBC 188.87c
5.1 c c 5.1
c c
1.6
x from B
c
1.6
M pos 188.87c 157.74 144.45 kN m
c
M design M max 254.51 kN m
M 254.51 103
Req' d Sx 1117.7 10 3 mm 3
0.66Fy 0.66 345
Use W16 45, Sx 1191 103 mm 3
2. Determine the maximum uniform load w that the beam can carry using A-36
steel. The lateral supports are as shown below.
0.75
DFBA 9.5 0.38111
0.75 1
9.5 7.8
DFBC 0.61889
FEM’s:
1
M AB 0.8w 9.5 2 2.4067w
30
1
M BA 0.8w 9.5 2 3.61w
20
1
w 7.8 5.07w
2
M BC M CB
12
Final moments:
MA 0
2.4067
M B 0.61889 3.61 0.38111 5.07 4.9112w
2
1 2.4067
M C 5.07 5.07 3.61 0.61889 5.1525w
2 2
Span AB:
1
VAB 0.8w 9.5 4.9112w 0.74970w
3 2 9.5
0.8w
w x x
9.5
F 0
1
w x x 0.74970w
2
0.8x 2
0.74970
2 9.5
x 4.2196 m from A
2
M pos 0.7497w 4.2196 2.1090w
3
1 0.8w 2
M D 0.74970w 6 6 6 1.4666w
6 9.5
Span BC:
7.8w 4.9112 5.1525
VBC 3.8691w
2 7.8
x 3.8691 m from B
1
M pos 3.8691w 3.8691 4.9112w 2.5736w
2
w
M E 3.8691w 3.8 3.8 4.91112w 2.5714w
2
BW450 70 b f 150 mm
S x 1276 10 mm
3 3
t f 16 mm
rt 38.2 mm d 450 mm
200150
lc 1905.0 mm governs!
248
137900150 16
2965.6 mm
450 248
Panel AD
l b 6000mm lc , C b 1.0, M max 2.109w
l 6000
157.07
rt 38.2
7032701.0
53.252
248
35163301.0
119.07
248
1172100 1.0
Fb 47.509 MPa
157.07 2
827401.0 150 16
73.547 MPa
6000 450
0.6 248 148.8 MPa
Fb 73.547 MPa
Fb
M
Sx
2.109w 73.547 1276 103 10 6
w 44.498 kN
m
Panel DB
l b 3500mm l c
l 3500
91.623
rt 38.2
703270 2.0903
76.991
248
3516330 2.0903
172.16
248
2 248 91.623
2
Fb 248 141.92 MPa
3 10550000 2.0903
82740 2.090315016
263.55 MPa
3500 450
0.6 248 148.8 MPa
Fb 148.8 MPa
4.9112w 148.8 1276 103 10 6
w 38.660 kN
m
Panel BE
l b 3800 mm l c
M1
M 1 2.57w, M 2 4.9112w, 0.52329
M2
C b 1.75 1.05 0.52329 0.3 0.52329 2.3816 2.3
2
C b 2.3
l 3800
99.476
rt 38.2
703270 2.3
80.761
248
3516330 2.3
180.59
248
2 248 99.476 2
Fb 248 140.25 MPa
3 10550000 2.3
82740 2.3150 16
267.09 MPa
3800 450
0.6 248 148.8 MPa
Fb 148.8 MPa
4.9112w 148.8 1276 103 10 6
w 38.660 kN
m
Panel EC
l b 4000 mm l c
C b 2.3
l 4000
104.71
rt 38.2
703270 2.3
80.761
248
3516330 2.3
180.59
248
2 248104.71
2
Fb 248 137.54 MPa
3 10550000 2.3
82740 2.3150 16
253.74 MPa
4000 450
0.6 248 148.8 MPa
Fb 148.8 MPa
5.1525w 148.8 1276 103 10 6
w 36.850 kN
m
w 36.850 kN
m