TEMPERATURE & RELATIVE HUMIDITY TEST REPORT

PURPOSE

To check the capability of the area to maintain the air temperature level within the control limits

CUSTOMER DATA
Customer Block
Area of Test Date of Test
Area Classification AHU Number
INSTRUMENT USED FOR TESTING
Instrument Name Sling Psychrometer Make
Model Serial Number
Calibrated On Calibration Due On
OBTAINED TEST RESULTS
Measured Dry Bulb
Acceptance Criteria for
Temperature Result PASS/FAIL
Room Name Temperature
Readings
0 0
C C
Primary Change Room 21.5 23 + 30C PASS
0
Secondary Change Room 21.0 23 + 3 C PASS
LAF Room-1 21.3 23 + 30C PASS
0
LAF-1 Change Room 22.1 23 + 3 C PASS
LAF Room-2 22.5 23 + 30C PASS
0
LAF-2 Change Room 22.0 23 + 3 C PASS
Media Preparation Room 22.5 23 + 30C PASS
0
Clean Autoclave Room 21.8 23 + 3 C PASS
Office Room 21.5 23 + 30C PASS

Innstrumentation/ Incubator Room 22.8 23 + 30C PASS

Corridor-1 21.2 23 + 30C PASS


0
Store Room 22.8 23 + 3 C PASS

The above test Confirms that the Dry Bulb Temperature in the above specified Rooms are within the
INFERENCE:
acceptable Limit

TEST CONDUCTED BY TEST WITNESSED & APPROVED BY