You are on page 1of 24

Energy Conversion and Management 271 (2022) 116284

Contents lists available at ScienceDirect

Energy Conversion and Management


journal homepage: www.elsevier.com/locate/enconman

Autonomous hydrogen-based solar-powered energy system for rural


electrification in Balochistan, Pakistan: An energy-economic
feasibility analysis
Tahir Khan , Muhammad Waseem , Mustafa Tahir , Shengyuan Liu , Miao Yu *
College of Electrical Engineering, Zhejiang University, Hangzhou, 310027, China

A R T I C L E I N F O A B S T R A C T

Keywords: This study proposed an off-grid PV-hydrogen energy system to electrify rural households in Balochistan,
Photovoltaic Pakistan. The system is designed, simulated, and optimized from a techno-economic perspective based on electric
Hydrogen load profile, geographical locations, and meteorological data. The optimal configurations and cost of the system
Cost of energy
components, i.e., solar panel, fuel cell, electrolyzer, hydrogen tank, and converter, are obtained. Sensitivity
Net present cost
Rural electrification
analysis is conducted to analyze the effect of system components’ cost, nominal discount rate and inflation rate,
and load variation on COE and NPC. Robustness analysis is also carried out to confirm the technical reliability of
the system. In addition, breakeven analysis is investigated to compare the cost of the grid extension scenario with
the proposed energy system. The results revealed that the proposed energy system is economically feasible and
technically reliable. Furthermore, the performance of the proposed system is compared with reported studies.
Finally, based on the obtained results, suggestions have been provided for effective policy implications to suc­
cessfully deploy the proposed energy system across the country.

energy systems; and (iii) seeking to produce energy economically.


1. Introduction Pakistan is in the midst of a transition period, with the growing
electricity demand resulting from the country’s economic growth. The
Energy is one of the key parameters of socio-economic progress in country’s peak electricity demand is 25,077 MW, which is expected to
any country. Accessibility to power has indeed been proven to boost rise to 36,369 MW by 2030 [2]. In Pakistan, a significant portion of
productivity and give prospects for economic growth. As a result, the electricity (60.82 %) is generated from imported fossil fuels, which are
generation of economical and environmentally sustainable electricity is neither economical nor environmentally friendly. Hydropower is the
critical for long-term development. Approximately 10 % (775 million second largest source of electricity generation, with a contribution of
people) of the global population has no access to electricity either from 29.01 %, whereas the share of nuclear power is 7.38 %. Pakistan utilizes
the grid or stand-alone generation system [1]. Out of 775 million people, a small percentage of RE sources in its power mix, having a share of 1.79
46.49 million people dwell in India, 42.8 million are inhabitants of % of wind energy, 0.5 % of biogas, and 0.5 % of solar energy, accounting
Pakistan, and 27.88 million reside in Bangladesh. The highest propor­ for less than 3 % (excluding hydropower)1 Fig. 1(a). Nonetheless, the
tion of the population without access to electricity is in Sub-Saharan power production stays between 18,000 and 20,000 MW, resulting in a
Africa, i.e., about 576.72 million. These statistics demonstrate insuffi­ 5000–7000 MW electricity shortfall [3]. Traditional electricity gener­
cient power generation capacity or lack of energy infrastructure in ating methods are insufficient to supply Pakistan’s massive electrical
aforesaid regions. Energy requirements are increasing enormously in demand. Several critical financial sectors, such as industries, commerce,
fast-expanding emerging economies to sustain their expanding econo­ and agriculture, have suffered due to the severe electrical shortage.
mies and achieve their development objectives. Developing countries Therefore, Pakistan has planned to generate 30 % of its total electricity
are presently confronted with three significant issues: (i) satisfying the generation capacity from renewable energy resources by 2030 [4] Fig. 1
basic energy demands of millions of citizens without access to elec­ (b). Authors [5–7] have discussed several aspects of GHG emissions and
tricity; (ii) partaking in the global transition to green and emission-free provided insights into various investigative questions related to CO2

* Corresponding author.
E-mail address: zjuyumiao@zju.edu.cn (M. Yu).
1
National Transmission & Despatch Company (NTDC), Power System Statistics 45th Edition 2021.

https://doi.org/10.1016/j.enconman.2022.116284
Received 14 June 2022; Received in revised form 23 September 2022; Accepted 24 September 2022
Available online 6 October 2022
0196-8904/© 2022 Elsevier Ltd. All rights reserved.
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Nomenclature Ie Electrolyzer current


ηf Faraday efficiency
Alphabets IFC Fuel cell current
C Cost Cf Fuel cost
F Faraday constant mH2 Hydrogen mass flow (kg/h)
S Solar radiations Thtci Hydrogen tank compressor inlet temperature
N Number ηhtc Hydrogen tank compressor efficiency
P Power/Pressure Phto Hydrogen tank outlet pressure
R Universal gas constant Phti Hydrogen tank inlet pressure
T Temperature SS Incident solar radiation at standard test conditions kW/m2
ST Incident solar radiation on PV array (kW/m2)
Abbreviation
f Inflation rate
ADB Asian Development Bank
Ypv Nominal capacity of PV
AEDB Alternative Energy Growth Board
i Nominal discount rate

COE Cost of energy


mH2 Nominal hydrogen mass flow (kg/h)

CPEC China Pakistan Economic Corridor
GDP Gross domestic product NC Number of cells in series
GHG Greenhouse gas emissions Ncell Number of cells in stack
HHV Higher heating value of Hydrogen (MJ/kg) n Number of years of useful life of the project
HOMER Hybrid optimization of multiple energy system CO&M Operation & maintenance cost
HRES Hybrid renewable energy system Copr Operating cost
LHV Lower heating value of hydrogen (MJ/kg) α perturbation factor
NPC Net present cost δd daily perturbation value
δh time step perturbation value
Subscript and symbols γ Polytrophic coefficient
TA Ambient temperature (◦C) QH2 Rate of hydrogen generated by the electrolyzer
TA,NOCT Ambient temperature at which NOCT is defined fpv Reduction factor
La,p Average primary load (kWh/d) Crep Replacement cost
VSC Average voltage of a stack of fuel cell τ Solar absorptance of the PV
Cht Capacity of the hydrogen tank (kg) HT,NOCT Solar radiation at which NOCT is defined
Ccap Capital cost α Solar transmittance of PV array cover
TC,NOCT Cell temperature at which NOCT is defined αP Temperature coefficient of power (%/◦ C)
UL Coefficient of heat transfer to the surrounding TC Temperature of the PV (◦ C)
AE ,BE Coefficient of the consumption curve (kW/kg/h) Ts Temperature of the PV under standard test conditions
Picon Converter input power (25 ◦ C)
Pocon Converter output power VhtanK Volume of hydrogen tank
ηhtanK Efficiency of hydrogen tank
ηC Efficiency of PV

Fig. 1. Pakistan’s renewable and non-renewable share of power generation sources.

emissions in the China region. There are three fundamental causes behind the province’s low electri­
The predicament is considerably worse in the rural districts of fication. Firstly, about 85 % of the population resides in rural areas, with
Balochistan, where electricity load shading remains for days. Balochi­ approximately 90 % of communities still unconnected with the power
stan has been underprivileged regarding adequate access to electricity grid [8]. These towns are dispersed across vast swaths of land. Con­
despite its abundant renewable and non-renewable energy resources. necting these regions to the national grid is costly and inefficient.

2
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Secondly, the power demand of rural dwellings is usually low in contrast According to [20], Balochistan has a rich solar energy potential,
to urban houses [9]. As a result, installing transmission lines for such having a maximum GHI is 2,300 kWh/m2, of which only a small portion
little demand is an expensive proposition, and policymakers see a slight is being utilized. Fortunately, the solar energy infrastructure is now
possibility of a transmission network in the coming decade. Lastly, improving because the government has recognized the significance of
stakeholders are hesitant to invest in rural Balochistan due to the solar energy. Pakistan’s Government has announced attractive in­
province’s isolation and lack of infrastructure amenities and energy- centives to install solar PV in the country. In addition, finance and tax
related data in each small town. Due to these reasons, solar energy perks are available for investors to entice them to this industry to suc­
provides the option for off-grid renewable power generation in Balo­ cessfully achieve the 2030 green energy goal of Pakistan. The present
chistan’s remote regions because the province obtains a higher amount energy situation of Pakistan calls for opportunities in renewable energy,
of solar irradiance over its broad terrain [10]. According to the World more specifically solar energy in Balochistan province, due to sever­
Bank, Balochistan has a daily average of 7–8 sunlight hours [11]. Owing al potential reasons, such as high irradiation, subsidies, zero duty for
to Pakistan’s high weather temperature, sustainability advocacy rec­ importing solar panels, and flexible investment schemes. Therefore, a
ommended that solar energy is a suitable option for electrification. wide variety of cutting-edge research is required, for instance, techno-
Furthermore, it was suggested that rather than expanding grid lines to economic feasibility analysis, hydrogen production potential from
remote locations, providing each house with solar energy is a relatively solar PV, household-owned hydrogen-based stand-alone PV system to
cost-effective way to improve the socio-economic situation of Balochi­ electrify remote villages, etc. Unfortunately, literature revealed that
stan’s rural people [12]. Similarly, the Asian Development Bank sug­ besides having a huge solar potential in Balochistan province, no study is
gested that an off-grid energy system is an economically feasible option conducted to delicately and broadly assess the hydrogen potential
to electrify Pakistan’s rural areas [13]. through solar energy. In addition, no study is available on hydrogen-
Nevertheless, solar energy is unreliable as it depends on the amount based RE system for Balochistan province. Authors [21–27] conducted
of sunshine the photovoltaic panels receive. Also, solar panels do not a feasibility study for hydrogen production in different regions of
receive enough sunlight in overcast weather, which causes power fluc­ Pakistan through various renewable energy resources. However, none of
tuations. In addition, solar energy is unavailable at night. Therefore, an the studies conducted research on PV-hydrogen RES for any region of
energy storage system is needed to utilize solar energy efficiently. Balochistan. Keeping in view the research gap and utmost need to
Various energy storage devices are available, including batteries, fly­ electrify the most resourceful yet underdeveloped province of Pakistan,
wheels, hydrogen storage, etc. [14]. Batteries are widely used ener­ the current study aims to investigate an in-depth techno-economic
gy storage devices as a backup in renewable energy systems. However, feasibility analysis of stand-alone PV-hydrogen energy system. This
energy leakage and low energy density issues are associated with bat­ would ultimately improve the living standard of the local inhabitants,
teries. Therefore, batteries are not feasible for prolonged operations and uplifting the socio-economic situation of the region and, in the long-
high storage. This battery constraint can be circumvented by employing term, increase the GDP of the Balochistan province as well as
a hydrogen fuel cell, which generates power using hydrogen as a fuel, Pakistan. This work is comprehensive in a way that it studied the largest
enhancing the overall performance of the renewable energy system province of Pakistan, accounting for 43.60 % of the country’s total land
[15]. In an autonomous PV-hydrogen fuel cell system, surplus electricity area. The outline of the contribution of the present study is as follows:
from the solar panel is used by an electrolyzer to produce hydrogen,
which is then stored in a hydrogen tank when energy demand is not a) Given the meteorological data and estimated energy consumption
high. Further, when solar radiation is insufficient or at night, the stored profile of households, a detailed hierarchal framework for the pro­
hydrogen is converted into power using a fuel cell to satisfy load de­ posed energy system is presented to obtain the optimal system con­
mand. An autonomous PV-hydrogen system could be advantageous for figurations, satisfying the load demand for each division of
residents in areas where electrical grid extension is backbreaking due to Balochistan. Furthermore, the electrical and hydrogen profiles of the
intense topographic constrictions. Also, the transportation and fuel costs optimized system configurations for all divisions are thoroughly
are reduced by producing hydrogen in situ using renewable energy investigated and compared.
sources. However, many important factors must be considered for b) The economy of the optimal system configuration for each division is
optimal, reliable, and safe operation of autonomous PV-hydrogen en­ obtained and contrasted in detail considering COE, NPC, initial
ergy systems, including system sizing and cost, availability of solar ra­ capital cost, operating cost, and overall cash flow of the system.
diation, prospective electrical loads, and safety and protection. c) Based on the obtained results of the present study, a comprehensive
policy implication is provided for the wider deployment of the pro­
1.1. Motivation and contribution of the present study posed system across the country.

Balochistan, Pakistan’s largest province, with an area of 347,190 2. Literature review


km2, accounts for 43.60 % of the country’s total land area. As per the
2017 census, its number of inhabitants is 12.34 million (5.9 % of the In literature, various authors have proposed rE-based energy systems
country’s total population), a very low population density/km2 [16]. for rural electrification or off-grid applications as an alternative to fossil
Although Balochistan is the country’s second-largest natural gas sup­ fuel-based energy systems, considering the availability of RE sources in
plier [17], yet the least developed. Balochistan’s location is strategically the studied regions. Due to their intermittent nature, energy storage
important because of its extended coastal line. Gwadar, a port city in devices are needed for rE-based energy systems. In this context, a battery
Balochistan, is the most direct route between the Middle East and energy storage system is widely used in the literature [28]. However, it
Central Asia. Gwadar has drawn various foreign investments and initi­ has inadequate energy density and power leakage issues. A diesel
ated several developmental projects due to its prominence [18]. As a generator system is also utilized as a backup energy system, but it causes
result, the energy demand in Balochistan has increased over the previous GHG emissions and adds high fuel transportation costs for rural areas
decade. The current electricity demand in the region is around 1,656 [29]. Thus, a fuel cell can be a viable option to use with rE-based energy
MW; however, approximately 596 MW (36 %) of energy demand is system. Whenever the power from RE sources is insufficient, the fuel cell
satisfied [19]. In urban areas, the huge electrical shortfall causes a converts hydrogen into power to meet the energy demand. The fuel cell
power shortfall of 10 to 12 h/day. Power outages are more severe in has been proved to be one of the most acceptable energy storage devices
rural areas, where 85 % (10.489 million) of Balochistan’s inhabitants because of its good efficiency, minimal maintenance requirement, and
live, but electricity is only accessible for 3 to 4 h/day in electrified vil­ lower GHG emissions [30].
lages [19]. Researchers around the globe investigated the techno-economic

3
T. Khan et al.
Table 1
Overview of selected studies from literature utilized HRES with hydrogen technologies.
Ref. Optimum system configuration Load COE TNPC Method Location Application Year
(kWh/d) ($/kWh) ($)
PV WT DG HKT BC EL HT FC BT
(kW) (kW) (kW) (kW) (kW) (kW) (kg) (kW) (kWh)

[46] 190 ⨯ ⨯ ⨯ 40 5 40 5 9645 485 1.051 3,446,346 HOMER Kirklareli, Turkey University Campus 2012
[47] 8.780 ⨯ ⨯ ⨯ NA 2 0.410 1 10.400 23.800 1.352 102,323 HOMER Tocantins, Brazil Research Center 2013
[48] 300 660 ⨯ ⨯ 150 200 400 100 ⨯ 1,875 0.685 9,863,963 HOMER Bozcaada, Turkey Residential Area 2014
[49] 4,200 ⨯ ⨯ ⨯ 2,000 3,400 955,000 2,000 ⨯ 16,000 0.120 8,942,636 HOMER Brest, Electrical Load of City 2014
France
[50] 3 3 3.500 2 0.250 0.010 1 25.200 18 0.505 39,557 HOMER Central India Police Station 2016
[51] 60 40 ⨯ ⨯ 35 40 40 15 ⨯ 90 0.862 361,115 HOMER Ontario, Building Electrical Load 2016
Canada
[29] 71 ⨯ ⨯ ⨯ 18 3 2 5 694,440 140 0.355 369,603 HOMER Sarawak, Malaysia Village Longhouse 2017
[52] 135 ⨯ ⨯ ⨯ NA 290 363 140 ⨯ 594 0.334 3,244,897 ABC, PSO, FPA Egypt Rural Area 2018
4

[53] 36 ⨯ ⨯ 15 10 10 10 ⨯ 25 5.600 0.254 138,672 HOMER Guayaquil, Ecuador Island Household 2018
kWp1
[54] 1,200 ⨯ 5,850 ⨯ 300 2,000 500 1,000 ⨯ 51, 020 0.260 4,500,000 TC2 NA UAE Cruise Ship 2019
[55] 500 ⨯ ⨯ ⨯ 500 10 10 20 8,040 1,093 1.536 7,727,992 HOMER Kunming, Community Center 2019
China
[56] 280 ⨯ ⨯ 80 10 10 20 10 ⨯ 374,94 0.400 348,665 HOMER Ecuadorian Amazon community Electric Load 2019
[57] 1.800 ⨯ ⨯ ⨯ 5 3.501 10 2.250 ⨯ 6.800 0.195 12,282 Iterative Baqubah, Household Electrical Load 2020
Iraq
[58] 1,790 400 ⨯ ⨯ 8.800 1206 24 490 9.600 295 0.289 9,395,142 JA, PSO Al.baha, University Campus 2020
KSA
[59] 80 ⨯ ⨯ ⨯ NA 50 20 20 ⨯ 200 0.161 148,371 HOMER Andhra Pradesh, India Household Electrical Load 2020
[60] 8,102 ⨯ 2,000 ⨯ 3,300 4,130 7,600 7,600 ⨯ 37,260 0.360 77,213,025 HOMER Khorfakkan, UAE Electrical Load of City 2021
[61] 54.700 14 3 8 7 61.540 0.041 41,455 HOMER Ekpoma, Nigeria University Lab 2021

Energy Conversion and Management 271 (2022) 116284


⨯ ⨯ ⨯ ⨯
1
5.6kWp is a peak load.
2
4,500,000 TC is a total cost of a system.
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 2 reliable and non-pollutant; however, the cost is still not competitive
Geographical locations, annual average GHI and AT of seven divisions. compared to the battery storage system. Zhang et al. [40] used three
Division Latitude Longitude Annual average Annual average metaheuristic techniques to optimize the various configurations of solar
radiation ambient temperature and wind HRES based on battery or hydrogen storage systems. The
(kWh/m2/day) (◦ C) finding revealed that the HRES with hydrogen energy system is reliable
Quetta 30◦ 12ʹ 67◦ 10ʹ E 5.40 16.53 and less pollutant, while the HRES with battery storage system is more
N economical.
Zhob 31◦ 34ʹ 69◦ 46ʹ E 5.18 16.83 Numerous scientists adopted hydrogen-based HRES to supply unin­
N
Loralai 30◦ 38ʹ 68◦ 59ʹ E 5.28 19.60
terruptible power to meet the load demand. The authors in [41] con­
N ducted a techno-economic analysis of the PV/WT/FC system to provide
Sibi 29◦ 55ʹ 67 88ʹ E

5.23 22.91 electricity to rural residential households. The results confirmed the
N reliability of the system is within an economical range. Devrim and Bilir
Nasirabad 27◦ 37ʹ 67◦ 91ʹ E 5.27 25.51
[42] investigated the application of a PV/WT/FC off-grid HRES for
N
Kalat 29◦ 05ʹ 66◦ 58ʹ E 5.52 16.80 residential electrification in Ankara, Turkey. The outcome of the study
N exhibited that the fuel cell system could compensate for power shortages
Makran 25◦ 30ʹ 64◦ 00ʹ E 5.33 25.89 throughout the year. To mitigate the power shortage problem in a tourist
N resort, Sammy et al. [43] proposed PV/WT/FC HRES as a backup energy
system that operates when the electricity from the grid is absent or
analysis, techno-economic-environmental analysis, comparative assess­ insufficient. The proposed system proved to be successful in overcoming
ment, and performance evaluation of HRES with hydrogen technologies the grid’s reliability problem. The COE of the backup energy system is
(electrolyzer, hydrogen tank, and fuel cell) for various capacities, re­ found to be less expensive than the COE of purchasing power from the
gions, and applications. Pal and Mukherjee [31] conducted technical grid. Singh and Baredar [44] proposed PV/FC-biomass HRES to electrify
feasibility and economic viability of standalone PV/hydrogen HRES educational institute in India. Simulation results indicated that the
systems for the electrification of different rural regions of India. The hybrid system satisfied the load demand throughout the year without
authors concluded that the adopted system economically satisfies the causing power outages within an economical range. Ozden and Tari [45]
energy demand of the studied regions. Ceran et al. [32] evaluated the examined off-grid PV/FC HRES to ensure that the system supplies power
cost-benefit analysis of a PV/WT/FC HRES for three different resi­ to the emergency room for an entire year during an emergency blackout.
dential electrical loads, which proved to be cost-effective. The findings demonstrated that the system is economically satisfying the
Since GHG emissions are a major environmental threat, various au­ desired power requirements.
thors investigated the environmental impact of utilizing hydrogen-based Apart from the literature discussed in this section, Table 1 presents a
energy systems. Kazim [33] conducted a viability analysis of utilizing comprehensive overview of further studies investigating hydrogen-
fuel cell energy system in homes and public buildings, considering based HRES for different applications. In Table 1, the total NPC and
economic and environmental factors. The findings showed that using a COE of the systems are observed to be different for two main reasons.
fuel cell to produce electrical energy can help to reduce GHG emissions Firstly, the cost of individual components of hydrogen-based HRES dif­
and save fossil fuels significantly. Zoulias and Lymberopoulos [34] fers across countries. Secondly, the cost of hydrogen-based HRES is
investigated the integration of solar energy system with fuel cell system profoundly dependent on the financial conditions (discount rate and
to electrify rural area in Greece. The results revealed that substituting a inflation rate) and renewable energy policies (tax incentives, subsidies,
fossil fuel-based power generation system with a PV/hydrogen system is exemption of customs duty, etc.) of the individual country.
technically feasible and environmentally friendly, but the cost is still
challenging. Ashourian et al. [35] proposed PV/WT/FC/battery HRES to 3. Solar radiation data, load and location
satisfy the energy demand of Malaysian island resorts. The results were
compared with the diesel generator (DG) energy system, which proved 3.1. Solar radiation data
that the proposed system is reliable and free from GHG emissions.
However, it is not cost-effective as DG until the fuel price reaches $2.10/ The satellite-driven solar radiation data and ambient air temperature
liter. To deal with growing energy demand in the residential sector, Ren of all seven divisions are taken from the NASA database [62]. The
et al. [36] proposed an optimization model for a PV/FC/battery HRES. geographic coordinates, annual average radiations, and annual average
The authors confirmed that implementing the proposed HRES yields ambient temperatures are presented in Table 2, and their corresponding
satisfactory financial, technical, and environmental outcomes. monthly average values are available in Table A1. The four seasons in
Researchers conducted a techno-economic comparative assessment Balochistan are usually; winter: from Dec to Feb; summer: from June to
among various hydrogen-based HRES to realize an optimal system for August; autumn: from Sep to November; and spring: from March to May.
their applications. Elkadeem et al. [37] conducted a techno-economic The summer season is usually hot, long, and dry, whereas the winter is
feasibility study through a decision-making approach for off-grid PV/ cold, short, and clear.
WT/diesel/FC HRES. Various possible HRES configurations were ­ The solar radiation data obtained from ground-based devices is more
modeled, assessed, and contrasted to find the most cost-effective and precise in contrast to satellite-driven data. Nevertheless, calibration
emission-free HRES. Among other configurations, PV/WT/FC HRES was errors, functional limitations, and equipment substitutions of ground-
found to be an optimum configuration due to the minimum cost, based devices induce assessment errors between 6 and 12 %, and data
reduced GHG emissions, and improved system reliability. Bezmalinovic gaps are occasionally unnoticed or uncertain [31]. On the other hand,
et al. [38] studied three different off-grid energy systems, including PV/ the veracity of satellite-based data and ground-based devices is in the
battery, PV/battery/FC, and PV/battery/DG, to provide a continuous range of 11 to 17 % [63]. In Pakistan, 9 ground-based solar measure­
power supply to the telecommunication network. The findings exhibited ment stations have been commissioned for the measurement of solar
that the PV/battery/FC system is favorable considering the reliability, radiation data, funded by the World Bank [20]. Out of 9 stations, 2 are
whereas the other two energy systems are economically feasible. Zhang installed in Quetta and Khuzdar cities of Balochistan province, which are
et al. [39] employed the simulated annealing algorithm to optimize six insufficient to measure solar radiations in all seven divisions of Balo­
different HRES configurations with different energy storage systems. chistan. This study uses NASA satellite-based solar radiation data to
The authors concluded that HRES with a hydrogen storage system is simulate the PV-hydrogen system. Many researchers [64–67] have
already utilized NASA satellite-based solar radiation data for their

5
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

electrical profile. Fig. 2 represents the scaled annual daily average load
profile of the household. The detailed calculation can be found in
Table A2.
The estimated energy consumption load is divided into 24 h based on
its usage to obtain the daily load profile. To produce the realistic type of
load data, HOMER employs day-to-day and hour-to-hour load fluctua­
tions, which are taken to be 2 % and 12 %, respectively, in the present
study.
α = 1 + δd + δh

α = 1 + δd + δh (1)
The daily average energy consumption of a typical single household
is calculated to be 6.91 kWh/day, with a peak load of 0.63 kW. The
average load demand is 0.29 kW. Fig. 3 represents the monthly average
load demand of a single house in a rural area of Balochistan. Further­
more, the daily average minimum and maximum load demand are ob­
Fig. 2. Scaled annual daily average load profile of household.
tained in the ranges of 0.12 kW to 0.14 kW and 0.48 kW to 0.50 kW
throughout the year. Moreover, the daily annual minimum and daily
studies, which is acceptable in the absence of ground-based data. annual maximum load demands are observed to be in the ranges of 0.09
kW to 0.11 kW and 0.56 kW to 0.62 kW over the year.
3.2. Location and load
4. System architecture, theoretical framework and economic
The Balochistan province is located in the South-West of Pakistan. modelling
The geographic coordinates of all seven divisions of Balochistan are
presented in Table 2. According to the 2017 census of Pakistan [16], 4.1. System architecture
each rural house in Balochistan is a constituent of an average of 7 family
members. Inhabitants in rural areas of Balochistan use electricity to To electrify the rural households in Balochistan, a stand-alone PV-
operate basic home appliances, for example, LED lights, fans, TV, fridge, hydrogen energy system is proposed, which includes PV, FC, electro­
water motor, washing machine, etc. The functional hours of electrical lyzer, hydrogen tank, and converter, as shown in Fig. 4. The PV panel is
appliances are calculated based on a probabilistic approach. The responsible for serving the load demand during the sunshine hours. The
schedule of home appliances’ usage in a rural area is also considered PV panel generates DC power which is converted into AC power through
while constructing the load profile. For instance, the fridge is normally the converter. The excess generated power is supplied to the electrolyzer
operated throughout the day, the washing machine and water motor are through the DC busbar. The electrolyzer converts input power into
counted to operate for minimum hours, and fans are considered to hydrogen through electrolysis, which is then stored in a hydrogen tank.
operate during the day and night depending on the need. LED bulbs are At night or whenever PV power is insufficient, FC utilizes stored
functional from 6:00p.m. to 11:00p.m. and early morning. Further, in hydrogen from the hydrogen tank and generates power to satisfy the
rural areas, inhabitants usually take a rest for an hour or two between load demand. The FC is also connected to the DC busbar, which is further
01:00p.m. and 4:00p.m. Therefore, only fans and fridges are operational connected to the converter to provide AC power to the load. The tech­
in this period. This way, a probabilistic approach is used to create an nical description and cost of each component are provided in Table 3.

Fig. 3. Monthly average load demand of a single house.

6
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. 4. Proposed PV-hydrogen energy system.

4.2. Theoretical framework ( )


TC,NOCT − TA,NOCT ( η )
TC = TA + ST 1− C (3)
ST,NOCT τα
4.2.1. PV panel
The PV cells convert the incoming solar radiation into DC power ­ The variation in the PV cell temperature can be obtained using (4).
output to meet the electric load demand of the consumers. In this study,
ταST = ηC ST + UL (TC − TA ) (4)
Canadian solar-CS3U-360P is used, which has the polycrystalline type of
cell. In literature, authors [31,68,69] used polycrystalline photovoltaic In the above equation, τα represents the effective absorption trans­
(PCPV) panels in their studies for rural electrification. On the other mittance of the PV panel. This value is taken as 0.9 NOCT by HOMER
hand, researchers [4,61,70] utilized monocrystalline photovoltaic software. In the fabrication testing process, nominal operating cell
(MCPV) panels to provide electricity to educational institutes. Since temperature (NOCT) is determined at the zero-load operating condition
MCPV panels need less space than PCPV panels, the research community with a solar radiation value of 0.8 kW/m2 at an ambient temperature of
prefers MCPV panels where space is limited. However, the cost of MCPV 20 ◦ C.
panels is higher than PCPV panels. In this work, PCPV is chosen because
space is not considered a constraint. In addition, the chosen PCPV has a 4.2.2. Electrolyzer
− 0.36 %/◦ C temperature coefficient, which means that for every 1 ◦ C The electrolyzer is an electrochemical device that takes power as
increase above the nominal operating cell temperature, which is 45 ◦ C, it input and produces hydrogen and oxygen molecules by splitting water
will lose 0.36 % of rated maximum power. Furthermore, the electrical via the electrolysis process [29]. Various types of electrolyzers are
efficiency is 18.2 %. These [31,68,69,71–73] studies utilized solar available, such as polymer electrolyte membrane (PEM) electrolyzer,
panels having a temperature coefficient range of − 0.36 to − 0.50 %/◦ C phosphoric acid electrolyzer, solid oxide electrolyzer, direct methanol
and an efficiency range of 13 % to16.9 % for a similar climate to this electrolyzer, and alkaline electrolyzer. Each of these is used for different
study. The chosen PCPV is easily available in Pakistani markets. The applications. The PEM electrolyzer is favored for small-capacity off-grid
PV power output is determined by the amount of incident solar radiation energy systems for rural applications [74]. Based on the higher heating
and other climatic factors such as ambient temperature and humidity. value, the PEM electrolyzer’s theoretical efficiency is reported to be up
HOMER evaluates the photovoltaic output power using (2) [56]. The to 94 %. However, this value is practically obtained as 85 % [31].
temperature of the PV cell can be calculated from (3). Therefore, a PEM electrolyzer with 85 % efficiency is considered in this
( ) study. The electrolyzer’s hydrogen production rate is estimated using
ST (5). Furthermore, the amount of input electrical energy needed by the
Ppv = Ypv fpv [1 + αP (TC − Ts) ] (2)
SS electrolyzer can be calculated as (6) [75].

7
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 3 4.2.4. Fuel cell


Technical parameters and expenditure of proposed system components [31,82]. The fuel cell used in this work is of PEMFC type. The author [77]
Components detail Description recommended PEMFC type in stand-alone energy systems. Also, various
authors have utilized PEMFC in stand-alone energy systems, a few of
PV panel
PV model Canadian solar-CS3U-360P them are [29,52,53,55,69,78], due to its good electrical efficiency,
PV capacity (W) 360 lower weight, high cell life, low operating temperature, quick start-up
Temperature coefficient (%/◦ C) − 0.36 speeds, minimum emissions, less maintenance, quiet operation, and
Nominal operating cell temperature (◦ C) 45 high flexibility [79]. In addition, PEMFC efficiency is observed to be in
Efficiency (%) 18.2
Derating factor (%) 85
the range of 40 to 60 %. Thus, in this study, fuel cell efficiency is esti­
Ground reflectance (%) 20 mated to be 51.3 %. The output power and efficiency of FC can be
Considered sizes for capacity optimization 0, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, 7.5, 8 calculated as (10) (11) [80].
Initial capital cost ($) 400
Replacement cost ($) 400 PFC = Vstack IFC = VSC Ncell IFC (10)
Operation & maintenance cost ($/year) 10
Useful life (years) 25 PFC
Electrolyzer ηFC = (11)
mH2 HHVH2
Minimum load ratio (%) 30
Efficiency (%) 85
Considered sizes for capacity optimization 0, 1, 1.5, 2, 2.5, 3 4.2.5. Converter
Initial capital cost ($) 1,100 The power output from the PV panel and fuel cell is DC power,
Replacement cost ($) 850 whereas the load in the present study is AC. Therefore, the converter is
Operation & maintenance cost ($/years) 10
required to convert DC power into AC power (inverter). The converter’s
Lifetime (years) 15
Hydrogen Tank efficiency is assumed as 90 % and can be determined using (12) [81].
Initial tank level with respect to tank size 10
Pocon
(%) ηcon = (12)
Considered sizes for capacity optimization 0, 1, 2, 3, 4, 5 Picon
Capital cost ($) 600
Replacement cost ($) 600
O&M cost ($/year) 10 4.3. Economic modeling
Useful life (years) 25
Fuel Cell 4.3.1. Total net present cost
Fuel type Stored hydrogen HOMER considers the net present cost in the simulation process to
Minimum load ratio (%) 30
prioritize the several possible RE system configurations. The total NPC of
Efficiency (%) 51.3
Considered sizes for capacity optimization 0, 0.5, 1, 1.5, 2 a system is the current value of all expenses of implementing and
Initial capital cost ($) 2000 operating the system components throughout the project life, exclu­
Replacement cost ($) 2000 ding the current cost of all profit generated throughout the project life.
Operation & maintenance cost ($/hour) 0.03
The profit earned by the system is through the salvage value of the
Useful life (hours) 15,000
Converter components. HOMER evaluates NPC of both individual components and
Efficiency (%) 90 a whole system. HOMER uses the following equation to compute NPC
Considered sizes for capacity optimization 0, 0.5, 1, 1.5, 2 (13) [83].
Initial capital cost ($) 200 [ ]
Replacement cost ($) 200 Ct
O&M cost ($/year) 0
NPC = (13)
CRF(i, n)
Useful life (years) 15
Where Ct is defined as the annualized cost of the system, CRF is the
( ) short form of capital recovery factor, and both can be evaluated as (14)
QH2 = ηf
NC Ie
(5) and (15) [84].
2F
Ct = Ccap + Crep + CO&M + Copr + Cf (14)

(6)

IE = AE .mH2 + BE .mH2 i(1 + i)n
CRF(i, n) = (15)
i(1 + i)n − 1
4.2.3. Hydrogen tank
A hydrogen tank is required to store the hydrogen produced by the 4.3.2. Real discount rate
electrolyzer. The power needed to compress the hydrogen inside the The real discount rate is employed to obtain the conversion between
hydrogen tank is shown in (7) [67]. The inner pressure of the hydrogen one-time cost and yearly cost. HOMER evaluates the real discount rate
tank is estimated as (8) [76]. In addition, HOMER evaluates hydrogen using the nominal discount rate and inflation rate given by (16) [85].
tank autonomy using (9), defined as the ratio of the energy capacity of
the hydrogen tank to the average electric load.

i − f
i= (16)
( ) ( )[( )γ− 1 ] 1+f
γ Thtci Phto γ
Pcom = R − 1 QH2 (7) In this study, the annual expected nominal discount rate and the
γ− 1 ηhtc Phti
annual expected inflation rate are taken as 14.75 % and 12.67 %,
( ) respectively. Both values are referred from the state bank of Pakistan.2
RThtci
PtanK = η (8)
VhtanK htanK
4.3.3. Cost of energy
[ ] Cost of energy is the average cost per kWh of utilizable electricity
Cht LHV(24h/d)
Aht = (9) generated by the system. It suggests the average minimum price at
La,p (3.6MJ/kWh)

2
https://www.sbp.org.pk/.

8
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. 5. Design framework of the proposed energy system.

which the electricity should be sold to cover its entire operating costs requirements of the community and the daily working routine of local
throughout its lifetime. It is used to evaluate and compare different inhabitants [87]. Keeping in view this concern, a thorough resource
energy systems in terms of cost, giving an idea of the economic feasi­ evaluation, socio-economic situation, and load demand of rural areas of
bility of the energy system. To compute the COE, HOMER takes the ratio Balochistan are extensively examined to model the PV-hydrogen system.
of the annual cost of generating electricity to the total utilizable elec­ This aids in understanding households’ energy consumption behavior
tricity generated (17) [86]. and load demand, which is essential for the successful design and
implementation of energy projects.
Ct
COE = (17)
Es
5.2. Techno-economic analysis
5. Methodology
HOMER software is adopted for the optimal sizing and techno-
The system is modeled, optimized, and analyzed using HOMER economic investigation of the present study. This software is devel­
software. The dispatch strategy adopted in this study is load flowing. In oped by the National Renewable Energy Laboratory,3 capable of con­
this strategy, if the PV system is not able to meet the load demand, the ducting technical as well as economic analysis for grid-connected and
fuel cell gets activated and satisfies the load demand. Furthermore, the off-grid HRES for different types of loads, such as commercial, indus­
maximum annual capacity shortage is set as 1 % only, which defines the trial and residential. In literature, various researchers have preferred
upper limit of permitted load shedding as a proportion of the overall HOMER software in their studies (Table 1). In HOMER, three main steps
load. In some situations, adjusting a capacity shortage drastically in­ are followed to successfully obtain the optimized results: system
fluences the economy of a system. It could happen if a high peak appears modeling, simulation and optimization, and sensitivity analysis. In the
for a brief period. In addition, the minimum operational reserve is set as first step, the RES is designed, including technical and economic pa­
10 % of the total load, which defines the minimum fraction of operating rameters according to the load demand and system specification. In
capacity that the system should be able to supply in case of an increment addition, average hourly data of load demand and solar radiation is
in load or deficit in available renewable energy. The project life is taken needed. In the second step, HOMER simulates various RES system con­
to be 25 years. figurations and ranks all the optimal configurations based on net present
cost as an economic criterion. In the final step, based on input values of
5.1. Pre-HOMER evaluation. sensitive parameters, HOMER reiterates the optimization procedure for
the individual input value of the parameter to evaluate how the results
Pre-evaluation of the chosen area is necessary to acquire the desired are influenced.
results and satisfy the energy need of the inhabitants. It is recorded in
the literature that energy initiatives in developing countries have not
been entirely successful due to a lack of insight into the domestic load 3
https://www.homerenergy.com.

9
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 4
Optimized PV-hydrogen system components and costs.
Divisions PV Electrolyzer Hydrogen tank (kg) FC Convertor TNPC COE Operating cost ($/year) Initial cost
(kW) (kW) (kW) (kW) ($) ($/kWh) ($)

Quetta 5.70 1.90 1.00 0.75 0.80 24,124 0.470 857.04 6,630
Zhob 5.75 1.90 1.00 0.75 0.80 24,400 0.475 864.70 6,650
Loralai 5.65 1.75 0.90 0.70 0.80 22,814 0.437 809.74 6,300
Sibi 5.50 2.00 1.05 0.75 0.80 24,275 0.473 863.41 6,650
Nasirabad 5.80 2.00 1.10 0.70 0.80 23,696 0.461 830.64 6,640
Kalat 5.50 1.80 0.90 0.70 0.80 22,741 0.433 805.44 6,285
Makran 5.60 1.85 1.10 0.70 0.80 23,494 0.458 832.75 6,495

system is modeled and simulated in HOMER to optimize the cost and size
of system components (section 6.2). Then, sensitivity analyses are con­
ducted considering the most uncertain parameters that potentially in­
fluence the cost of energy and net present cost of the proposed energy
system (section 6.3). Finally, robustness analyses are carried out to
verify the reliability of the proposed system in all four seasons (6.4).

6. Optimization results and discussion

An off-grid PV-hydrogen renewable energy system to electrify rural


households of all seven divisions of Balochistan is modeled, optimized,
and analyzed using HOMER software. HOMER suggests various system
configurations based on the input data provided in the search bound­
aries. The input parameters used for the modeling and optimization of
the proposed system are detailed in Table 3. In addition, solar radiation
data (Appendix A1), control parameters (section 6), and economic pa­
Fig. 6. Total NPC and COE of optimal system configurations for
rameters (section 5.2) were also included before running the simulation.
seven divisions.
The effect of ambient temperature on solar cells is also considered.
Further, a solar panel is used without a tracking system and has zero
5.3. Sensitivity analyses degrees azimuth position toward the south-west direction. Since the
proposed system is off-grid, electricity sale to the grid is not considered.
Sensitivity analyses are conducted to observe the effect of sensitive HOMER suggested hundreds of possible system configurations after the
parameters on the cost of a system. Fuel cell cost, nominal discount rate, optimization process; however, only one optimal system was shortlisted
inflation rate, and load demand are taken as sensitive parameters based for each division based on the lowest TNPC and COE, and minimum
on an extensive study of Pakistan’s electricity sector and economic capacity shortage value.
outlook. The effect of these sensitive parameters is analyzed concerning
NPC and COE of the PV-hydrogen energy system. Among the cost of
6.1. Optimal system configuration and its cost
other components, FC cost shares a significant percentage of cost in the
overall cost of the system, therefore, included as a sensitive parameter.
The winning energy system configuration for each division and
The nominal discount rate and inflation rate are chosen as sensitive
associated costs are presented in Table 4. The capacity of the converter is
parameters because emerging economies, such as Pakistan, are
found to be 0.8 kW for all divisions because of the same load demand for
extremely sensitive to discount and inflation rates, causing an impact on
each division. To satisfy the energy demand of the Quetta division,
the prices of all imported goods [88]. The rationale behind considering
HOMER suggested 5.70 kW of PV, 1.90 kW of EL, 1 kg of HT, and 0.75
these factors is to better understand the research outcome from the
kW of FC, while total NPC, COE, operating cost, and initial costs are
investor viewpoint to contribute to renewable energy initiatives in
optimized to be $ 24,124, 0.470 $/kWh, 857.04 $/yr, and $ 6,630. For
Pakistan.
Zhob division, the optimal system configuration obtained is the same as
Quetta division except for PV (5.75 kW), whereas the costs are observed
5.4. Robustness check to be $ 24,400 total NPC, 0.475 $/kWh COE, 864.70 $/yr operating cost,
and $ 6,650 initial system cost. To provide an uninterruptable power
This research also examines the reliability of the PV-hydrogen sys­ supply to the household in Loralai, the most optimal system combination
tem to observe whether the system produces sufficient energy to satisfy is found as 5.65 kW of PV, 1.75 kW of EL, 0.9 kg of HT, 0.70 kW of FC,
the energy demands of the chosen area. Technical reliability and eco­ and the associated costs of the system are noted as $ 22,814 total NPC,
nomic feasibility play an important role in successfully commissioning 0.437 $/kWh COE, 809.74 $/yr operating cost, and $ 6,300 initial sys­
the RES projects. The former is necessary to provide reliable electricity, tem cost. To fulfill the energy demand of the Sibi division, HOMER
which is the main intention of such projects, whereas the latter is suggested the optimal system having individual component capacity of
essential to make the energy system affordable for residents and for 5.50 kW PV, 2 kW EL, 1.05 kg HT, and 0.75 kW FC, whereas the total
stakeholders willing to invest in renewable energy projects. Thus, the NPC, COE, operating cost, and the initial cost of the system are $ 24,275,
robustness of the proposed system is verified by analyzing power gen­ 0.473 $/kWh, 863.41 $/yr, and $ 6,650. For Nasirabad division, the
eration profiles in all four seasons of Balochistan, including the months most feasible system components are observed to be 5.80 kW of PV, 2
with maximum average energy demand (April) and lowest solar radia­ kW of EL, 1.1 kg of HT, and 0.70 kW of FC, while the costs of the system
tions (December). are optimized to be $ 23,696 TNPC, 0.461 $/kWh COE, 830.64 $/yr
Fig. 5 represents the design framework of the proposed system. operating cost, and $ 6,640 initial system cost. To supply uninterruptible
Firstly, Pre-HOMER evaluation is conducted before beginning the power to Kalat division, HOMER recommended the system component
simulation in HOMER (section 6.1). Secondly, the proposed energy rating as 5.50 kW of PV, 1.80 kW of EL, 0.90 kg of HT, and 0.70 kW of

10
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 5
Electrical characteristics of PV-hydrogen system for seven divisions.
Division PV production Fuel cell AC primary Electrolyzer load Excess electricity Unmet electric Capacity Renewable
production load load shortage fraction

(kWh/ (%) (kWh/ (%) (kWh/ (%) (kWh/ (%) (kWh/ (%) (kWh/ (%) (kWh/ (%)
yr) yr) yr) yr) yr) yr) yr)

Quetta 10,239 84.62 1,859 15.41 2,513 33.32 5,029 66.74 4,277 35.34 8.95 0.35 12.41 0.49 1
Zhob 10,094 84.35 1,887 15.75 2,514 33.19 5,088 66.99 4,100 34.23 7.84 0.31 10.93 0.43 1
Loralai 9,877 84.53 1,811 15.52 2,514 33.27 4,832 66.86 4,063 34.85 8.35 0.47 12.14 0.47 1
Sibi 9,250 83.18 1,887 16.93 2,513 33.18 5,072 66.96 3,273 29.49 9.12 0.36 13.42 0.53 1
Nasirabad 9,720 84.34 1,812 15.71 2,516 34.13 4,865 65.95 3,872 33.60 6.53 0.25 9.75 0.38 1
Kalat 9,992 84.96 1,780 15.13 2,512 34.56 4,762 65.54 4,218 25.83 9.68 0.38 13.8 0.54 1
Makran 9,290 83.75 1,813 16.33 2,514 34.04 4,880 66.02 3,430 30.97 5.56 0.33 11.8 0.47 1

Fig. 7. Annual electricity production and consumption in seven divisions.

Fig. 9. Electricity production from PV and FC in seven divisions.

6.2. Electrical profile of optimal system configuration

The electrical profile of the optimal system configuration of each


division is presented in Table 5. In addition, Fig. 7 exhibits the annual
electricity production and consumption. It can be observed from Fig. 7
that the maximum electricity production (12,098 kWh/yr) and excess
electricity (4,277 kWh/yr) are observed in the Makran division, while
minimum electricity production (11,103 kWh/yr) is noticed in Quetta
division. The maximum electricity consumption (7,597 kWh/yr) and
minimum electricity consumption (7,274 kWh/yr) are observed in
Quetta and Makran. Fig. 8 shows the percentage of load sharing by AC
primary load and electrolyzer load for all divisions of Balochistan. It can
be seen from Fig. 8 that in all divisions of Balochistan, electrolyzer
shares a maximum proportion of load consumption in contrast to the AC
primary load. Further, the maximum (34.5 %) and minimum (33.1 %)
Fig. 8. Load sharing by AC primary load and electrolyzer in seven divisions. load sharing by AC primary load are in Kalat and Sibi divisions, while
the maximum (66.9 %) and minimum (65.5 %) load sharing by elec­
trolyzer load are in Sibi and Kalat divisions. In addition, the capacity
FC. On the other hand, the TNPC, COE, operating cost, and initial cost
shortage is within an acceptable limit in all divisions with a minimum
are estimated to be $ 22,741, 0.433 $/kWh, 805.44 $/yr, and $ 6,285. In
value of 9.75 kWh/yr in Nasirabad division and a maximum value of
Makran division, the optimal system configuration comprises 5.60 kW of
13.8 kWh/yr in Kalat division. Unmet electric load is observed in the
PV, 1.85 kW of EL, 1.10 kg of HT, and 0.70 kW of FC, while the costs of
range of 0.311 kWh/yr to 0.479 kWh/yr in all divisions. Since the
the system are evaluated as $ 23,494 TNPC, 0.458 $/kWh COE, 832.75
proposed system is solely based on PV-hydrogen, the renewable fraction
$/yr operating cost, and $ 6,495 initial system cost. On the one hand,
is 1 in all divisions. Even though little capacity shortage and unmet
Zhob accounts for the maximum TNPC, COE, operating cost, and the
electric load are observed, the optimal PV-hydrogen energy system is
initial cost of the winning PV-hydrogen system, among other divisions.
capable of producing electricity that fulfills the energy demand of all
On the other hand, Kalat has a minimum aforementioned costs of
seven divisions of Balochistan and producing excess electricity.
optimal system configuration, as shown in Fig. 6 and Table 4.
Fig. 9 illustrates the percentage share of electricity production from
PV and FC for overall electricity production. Maximum electricity pro­
duction share from PV and FC are observed in Kalat (84.9 %) and Sibi
(16.9 %), whereas corresponding minimum values are observed in Sibi

11
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. 10. Monthly average power produced by PV and FC.

Table 6
PV performance of PV-hydrogen system and comparison with the studies having similar solar radiations and system architecture.
Division Load Rated Mean output Maximum Capacity PV Operation Levelized
capacity output factor penetration hours cost
(kWh/ (kW) (kW) (kWh/ (kW) (%) (%) (hrs/yr) ($/kWh)
day) day)

Quetta 6.91 5.70 1.17 28.12 5.68 20.54 406 4,357 0.01
Zhob 6.91 5.75 1.15 27.77 5.71 20.02 400 4,376 0.01
Loralai 6.91 5.65 1.13 27.13 5.62 20.01 392 4,376 0.01
Sibi 6.91 5.50 1.06 25.34 5.46 19.22 367 4,352 0.01
Nasirabad 6.91 5.80 1.11 26.61 5.69 19.17 385 4,392 0.01
Kalat 6.91 5.55 1.14 27.40 5.52 20.62 396 4,390 0.01
Makran 6.91 5.60 1.06 25.52 5.58 18.91 368 4,385 0.01
Eight North East Indian states 138 110–120 17–21 413–515 105–118 15.00–18.71 299–373 4,372–4,403 0.04–0.05
[31]
Andhra Paradesh India [59] 200 80 — — 78 22.60 — 4,386 —

Ekpoma, 61.54 54.74 9.93 226 — 17.26 — 4,415 —


Nigeria[61]
Bhopal, 70 5 — 22.78 3.90 — — 3,475 —
India [89]
Teleghan, 27 10 — 49.81 — — — 4,498 —
Iran [90]

(83.1 %) and Kalat (15.1 %) divisions. Fig. 10 represents the monthly output power from PV is found to be minimum in July (1.03 kW), and
average power produced by PV panels and fuel cells in all divisions. In corresponding FC power is noticed in November and December (0.22
Quetta, the maximum values of monthly average output power from PV kW). In Kalat, on the one hand, the monthly average power output from
and fuel cell are observed in March (1.23 kW) and Dec (0.23 kW), PV is observed to be highest (1.23 kW) in April and lowest (1.0 kW) in
whereas the minimum values are noticed in Dec (1.09 kW) and from Dec. On the other hand, the monthly average output power from FC is
April to June (0.20 kW). In Zhob, the highest values of monthly average observed to be highest (1.0 kW) in February, November, and December
output power from PV and fuel cell are detected in Feb (1.26 kW), and in and lowest (0.22 kW) from April to July. In Makran, the highest monthly
November and December (0.23 kW), whereas the lowest values are seen average PV power (1.10 kW) is observed in April, while the lowest
in July (1.07 kW) and May (0.20 kW). The monthly average output power (0.97 kW) is found in December. In November and December,
power from PV is detected to be maximum (1.21 kW) in February and maximum average FC power (0.22 kW) is detected, whereas minimum
minimum (1.06 kW) in July and August. On the other hand, the monthly power (0.20 kW) is observed from April to July.
average output power from FC is observed to be maximum (0.23 kW) in
December and minimum (0.20 kW) from April to July and August. In 6.2.1. Performance of PV panel
Nasirabad, the apex of monthly average output power from PV is The PV panel output profile of the optimal PV-hydrogen system for
examined in Feb (1.09 kW), while corresponding FC power is detected all seven divisions is presented in Table 6. Furthermore, Fig. 11 exhibits
from April to June and Oct (0.20 kW). In addition, the monthly average the monthly average output power from PV and fuel cell. From the rated

12
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. 11. Monthly average output power from PV and FC in seven divisions.

capacity of the PV panel, the annual mean output power and daily mean and 25.52 kWh/day in Makran, respectively. The maximum PV output
output energy are observed as 1.17 kW and 28.12 kWh/day in Quetta, power is found to be 5.68 kW in Quetta, 5.71 kW in Zhob, 5.62 kW in
1.15 kW and 27.77 kWh/day in Zhob, 1.13 kW and 27.13 kWh/day in Loralai, 5.46 kW in Sibi, 5.69 kW in Nasirabad, 5.52 kW in Kalat, and
Loralai, 1.06 kW and 25.34 kWh/day in Sibi, 1.11 kW and 26.61 kW h/ 5.58 kW in Makran, respectively. The capacity factor is defined as the
day in Nasirabad, 1.14 kW and 27.40 kWh/day in Kalat, and 1.067 kW fraction of the mean electrical power generated by a PV panel to its rated

13
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

capacity. The maximum capacity factor is observed to be 20.62 % in


Kalat division, while the minimum (18.91 %) in Makran division. In
other divisions, it varies from 19.17 % to 20.54 %. PV penetration is the

generation
ratio of power generation from a PV panel to the total power generation

($/hr)

0.123
0.123
0.114
0.119
0.114
0.114
0.114
Fixed

cost
in a given time. Maximum PV penetration is recorded in Quetta with a
value of 406 %, while a minimum (367 %) is observed in Sibi. It can be
Capacity deduced from Table 6 that daily mean energy output is proportional to
factor the PV penetration. The operating hours of PV can be interpreted as the

28.31
28.74
29.56
29.52
29.61
29.03
29.65
number of hours in a year in which PV panel is generating power. The
(%) operating hours are in the range of 4,352 to 4,392 in all divisions.
Operational

6.2.2. Performance of fuel cell


The fuel cell is mainly providing electricity from dawn to sunset.
2.38
2.36
2.35
2.31
2.33
2.37
2.30
(yr)
life

Also, it is monitored to provide electricity during the day for a short


period whenever the load is at a peak or solar radiations are not suffi­
cient for PV to generate power. The fuel cell output profile of the optimal
(starts/
No of
starts

PV-hydrogen system for all seven divisions is presented in Table 7. The


406
404
399
392
397
411
399
yr)

electrical efficiency of FC is described as the electrical output energy


divided by the fuel (hydrogen) energy input, which is set as 51.3 % in
this work. Specific fuel consumption of fuel cell is described as the
operation
Hours of

(hrs/yr)

average quantity of fuel (hydrogen) consumed by the fuel cell to produce


6,308
6,352
6,374
6,504
6,443
6,331
6,522

1 kWh of electricity. The minimum electrical output from the fuel cell is
observed as 0.26 kW in Quetta and Zhob divisions, whereas it is
inspected to be 0.24 kW in all other divisions. The maximum electrical
output from the fuel cell is monitored as 0.70 kW in all divisions. The
efficiency
electrical

mean electrical output from fuel cell is detected in the range of 0.27 kW
51.30
51.30
51.30
51.30
51.30
51.30
51.30
Mean

(%)

to 0.29 kW. The specific fuel consumption is observed to be 0.059 kg/


kWh in all divisions, whereas annual hydrogen consumption ranges
from 102 kg/yr to 109 kg/yr. The lowest input fuel energy (3,560 kWh/
(kWh/yr)
energy

yr) is inspected in Kalat division, whereas the corresponding highest


3,718
3,774
3,622
3,774
3,624
3,560
3,626
input
Fuel

value (3,774 kWh/yr) is observed in Zhob and Sibi divisions. The


maximum FC operational hours are recorded as 6,522 hr/yr in Makran
Specific hydrogen

division, while the minimum (6,308 hr/yr) in Quetta division. The


number of fuel cell starts throughout the year in all divisions is found to
consumption

be in the range of 392 h to 411 h. The fuel cell should replace after every
(kg/kWh)

2.38 years in Quetta, which is the operational life of the fuel cell. In the
0.059
0.059
0.059
0.059
0.059
0.059
0.059

rest of all divisions, the operational life of the fuel cell is between 2.30 yr
and 2.37 yr. FC hourly performance throughout the year can be
visualised in Fig. B1.
consumption
Hydrogen

6.2.3. Performance of electrolyzer


Table 8 represents the electrolyzer output profile of the optimal PV-
(Kg)

108
109
104
109
104
102
105

hydrogen system for all divisions. Maximum input power and maximum
output hydrogen production in all divisions are in the range of 1.75 kW
to 2 kW and 0.03 kg/hr to 0.04 kg/hr. In addition, mean input power
electrical

and mean output hydrogen production are in the range of 0.54 kW to


output
Mean

(kW)

0.29
0.29
0.28
0.29
0.28
0.28
0.27

0.58 kW and 0.01 kg/hr to 0.012 kg/hr. It is also observed from Table 8
that the total input energy is between 4,762 kWh/yr and 5,088 kWh/yr.
The maximum and minimum hydrogen production are noted in Zhob
(110 kg/yr) and Kalat (103 kg/yr). Specific fuel consumption is
FC profile of PV-hydrogen system for seven divisions.
Maximum
electrical

approximately 46.40 kWh/kg in all divisions. The maximum capacity


output

factor is 31.54 % in Loralai, whereas the minimum capacity factor is


(kW)

0.70
0.70
0.70
0.70
0.70
0.70
0.70

observed as 27.85 % in Nasirabad. In all other divisions, it varies from


28.61 % to 30.2 %. The operational hours of the electrolyzer are in the
range of 6,451 hr/yr to 6,698 hr/yr.
Minimum
electrical
output

6.2.4. Performance of hydrogen tank


(kW)

0.26
0.26
0.24
0.24
0.24
0.24
0.24

Table 9 illustrates the hydrogen tank profile for all divisions. The
initial tank level relative to the tank size is set at 10 %. Hydrogen at the
start of the year in hydrogen tank is 0.10 kg in Quetta, Zhob, and Sibi
capacity

divisions, 0.11 kg in Nasirabad and Makran divisions, and 0.09 kg in


Rated

(kW)

0.75
0.75
0.70
0.75
0.70
0.70
0.70

Loralai and Kalat divisions. Hydrogen level at the end of the year is
noted to vary from 0.53 kg to 0.93 kg. Hydrogen tank autonomy is
Nasirabad

maximum (127 hr) in Nasirabad and Makran divisions, while minimum


Division

Makran
Loralai
Table 7

Quetta

Kalat

(104 hr) in Loralai and Kalat divisions. In Quetta, Zhob and Sibi di­
Zhob

Sibi

visions, hydrogen tank autonomy is 116 hr.

14
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 8
Electrolyzer profile of PV-hydrogen system for seven divisions.
Divisions Rated Minimum Maximum Mean Total Capacity Hours of Minimum Maximum Mean Total Specific
capacity input input input input factor operation output output output production consumption
power energy

(kW) (kW) (kW) (kW) (kW h/ (%) (Hr/yr) (kg/hr) (kg/hr) (kg/ (kg/yr) (kWh/kg)
yr) hr)
Quetta 1.90 0 1.90 0.57 5,029 30.23 6,622 0 0.04 0.01 108 46.40
Zhob 1.90 0 1.90 0.58 5,088 30.61 6,698 0 0.04 0.01 110 46.40
Loralai 1.75 0 1.75 0.55 4,832 31.54 6,591 0 0.03 0.01 104 46.40
Sibi 2.00 0 2.00 0.57 5,072 28.92 6,513 0 0.04 0.01 109 46.40
Nasirabad 2.00 0 2.00 0.55 4,865 27.85 6,451 0 0.04 0.01 105 46.40
Kalat 1.80 0 1,80 0.54 4,762 30.20 6,479 0 0.03 0.01 103 46.40
Makran 1.85 0 1,85 0.55 4,880 30.14 6,620 0 0.03 0.01 105 46.40

is compatible with AC primary load. Table 10 shows the inverter profile


Table 9 of the optimal PV-hydrogen system for all divisions. It can be noticed
Hydrogen tank profile of PV-hydrogen system for seven divisions.
that the maximum output power (0.63 kW), mean output power (0.28
Division Hydrogen Energy Tank Hydrogen Hydrogen kW), and capacity factor (35.9 %) are the same for all considered di­
storage storage autonomy at the at the
visions. Since the efficiency of the inverter is taken as 90 % in the present
capacity capacity start of the end of the
year year study, the energy input and output are observed to be in the range of
2,792 kWh/yr to 2,795 kWh/yr and 2,513 kWh/yr to 2,516 kWh/yr.
(Kg) (kWh) (hr) (kg) (kg)
Quetta 1.00 33.35 116 0.10 0.83
Furthermore, electrical losses are between 272 kWh/yr and 279 kWh/yr
Zhob 1.00 33.32 116 0.10 0.83 in all divisions.
Loralai 0.90 30.04 104 0.09 0.66
Sibi 1.00 35.02 116 0.10 0.63
Nasirabad 1.10 36.71 127 0.11 0.93 6.3. Sensitivity analysis
Kalat 0.90 30.09 104 0.09 0.53
Makran 1.10 36.72 127 0.11 0.72 Various sensitive parameters influence the total NPC, COE, and
technical performance of the system. Therefore, HOMER provides an
option to specify sensitive parameters, and their corresponding values
can be included in HOMER. The results can be further evaluated to see
how the parameters affect the financial and technical results. For the
present study, the most uncertain parameters are estimated to be the fuel
cell cost, household load demand, and the nominal discount and infla­
tion rates.

Fig. 12. Monthly average inverter power profile and load throughout the year.

6.2.5. Performance of inverter


The monthly average input and output power of an inverter
throughout the year are presented in Fig. 12. The former is in the range
of 0.315 kW to 0.325 kW, while the latter is between 0.285 kW and Fig. 13. Effect of variation in cost of proposed energy system components
0.295 kW. It is also noticed from Fig. 12 that the capacity of the inverter on COE.

Table 10
Inverter profile of PV-hydrogen system for seven divisions.
Division capacity Minimum output Maximum output Mean output Capacity factor Hours of operation Input energy Output energy losses

(kW) (kW) (kW) (%) (hrs/yr) (kWh/yr) (kWh/yr) (kWh/yr)


Quetta 0.80 0 0.63 0.28 35.90 8,724 2,792 2,513 276
Zhob 0.80 0 0.63 0.28 35.90 8,729 2,794 2,514 279
Loralai 0.80 0 0.63 0.28 35.90 8,729 2,793 2,514 274
Sibi 0.80 0 0.63 0.28 35.90 8,727 2,792 2,513 272
Nasirabad 0.80 0 0.63 0.28 35.90 8,727 2,792 2,513 279
Kalat 0.80 0 0.63 0.28 35.90 8,735 2,795 2,516 276
Makran 0.80 0 0.63 0.28 35.90 8,725 2,793 2,514 275

15
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

noticed from Fig. 14 that by decreasing the cost of FC by 60 %, TNPC and


COE were reduced by 31.12 % and 23.40 %. It may be declared that the
proposed system will be more economical, provided the cost of FC is
minimal. Currently, the cost of FC is high, but it is expected to drop
significantly with the advancement and massive production of FC
technology.

6.3.2. Electric load


There is a high probability that, with time, the local inhabitants of
the considered divisions may consume more electricity by adding more
electrical appliances, such as electric cookers, microwave ovens, and
water heaters. Thus, the electric load is also taken as the sensitive
parameter. Fig. 15 illustrates the effect of varying electric loads on TNPC
and COE. The electric load increased by 10 % from its initial value of
Fig. 14. Effect of variation in FC cost on TNPC and COE. 6.91 kWh/day to 7.60 kWh/day, which caused TNPC to increase by
1.37 % and reduced COE by 8.91 %. The results revealed that the pro­
posed system would be more economical for large-scale electric load, for
example, community load, village load, etc.

6.3.3. Nominal discount rate and inflation rate


The nominal discount rate and inflation rate in Pakistan have
significantly deviated in past years, affecting both TNPC and COE. In this
study, rather than using assumed values of the nominal discount rate
and inflation rate as sensitive variables, the historical trend of variation
in the nominal discount rate and inflation rate over the past 25 years has
been included.4 It can be observed from Fig. 16 that the nominal dis­
count rate varies from 5 % to 15 %, which leads to a decrease in the
TNPC by half and an increase in the COE by 26.90 %. In addition, by
varying the inflation rate from 2 % to 22 %, TNPC increases almost 4
times, while COE decreases by 89.93 %. Conclusively, the nominal
discount rate and inflation rate significantly impact the energy system’s
Fig. 15. Effect of variation in load on TNPC and COE. economy. The proposed system can be more cost-effective if the eco­
nomic condition of Pakistan tends to be more stable. The effect of eco­
6.3.1. Fuel cell nomic parameters on the prices of commodities is comprehensively
Firstly, the effect of each component’s cost on TNPC and COE is discussed in [91]. Cash flow summary of each component of the pro­
analyzed. It can be observed from Fig. 13 that, except for the FC cost, posed energy system is presented in Fig. B2.
none of the components’ costs significantly influence the TNPC and
COE. Therefore, FC cost is taken as one of the sensitive parameters.
TNPC and COE are decreasing linearly as the cost of FC decreases. It is

Fig. 16. Effect of variation in nominal discount rate on TNPC and COE.

4
https://www.sbp.org.pk/.

16
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. 17. Electrical profile and stored hydrogen in all four seasons.

the reliability of the proposed system. Fig. 17 represents the daily


average maximum electrical profile of the proposed system during all
four seasons in Balochistan. The PV output power remains above the
load demand during the day, and FC output power is consistently above
the load demand from dawn to sunset. Thus, the proposed energy system
satisfies the load demand during all four seasons. In addition, the min­
imum level of stored hydrogen in the hydrogen tank is more than 70 %
during all four seasons. Therefore, the authors confirmed that the pro­
posed PV-hydrogen energy system is technically robust to electrify rural
houses of the seven divisions of Balochistan.

7. Comparison of the proposed energy system

7.1. Cost comparison with grid extension


Fig. 18. Break-even distance of proposed PV-hydrogen system.
All the seven regions investigated in this work belong to rural areas
where grid electricity is unavailable. Therefore, to compare the cost of
Table 11 the proposed PV-hydrogen energy system with the grid electricity cost,
Break-even distance and corresponding NPC and COE. the breakeven distance is calculated by investigating the grid extension
Division Breakeven distance (km) NPC COE analysis. It is worth noting that the proposed energy system is for a
(M$) ($/kWh) single household load, which is cost-effective in contrast to grid exten­
Quetta 43.73 1.85 0.372 sion. Thus, to make the comparison, a load of a single household taken in
Zhob 44.85 1.87 0.376 this study is extended to 100 households (691 kWh/day). All the asso­
Loralai 40.24 1.80 0.345
ciated grid extension costs are taken by conducting a formal interview
Sibi 44.42 1.86 0.374
Nasirabad 42.12 1.82 0.364
with a representative of the concerned authority, NTDC,5 because the
Kalat 39.27 1.78 0.342 cost details are not publicly available. Grid extension cost, including HV
Makran 41.69 1.81 0.362 transmission lines, substation, distribution transformer, civil work,
consultancy, contingencies cost, etc., for 1 km is $ 301,625. The annual
O&M cost is taken as 2 % of the capital cost. The COE is 0.12 $/kWh in
6.4. Robustness of the system
urban areas of the studied regions, assumed for this analysis. Fig. 18
revealed the breakeven distance for all seven divisions. It can be
Since solar radiations and household load consumption may vary
throughout the year depending on weather conditions and load de­
mands, a robustness analysis is performed in all four climates to observe
5
National Transmission & Despatch Company (NTDC).

17
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table 12
Comparison of the proposed energy system with other similar studies having identical system architecture.
Ref. Load Nominal discount rate Inflation rate COE NPC Excess electricity Capacity shortage Unmet electric load

(kWh/day) (%) (%) ($/kWh) ($) (%) (%) (%)


[34] 50 68 — 1.7209 363,0009 19.51 1.08 —
[31] 138 61 — 0.509–0.689 3,27,557–4,43,004 21.40–41.10 0 0
[49] 16,000 10 — 0.120 8,942,636 — — —
[52] 594 12.25 17 0.334 3,244,897 — — —
[57] 6.80 6 8 0.195 12,282 — — —
[61] 61.54 — 12 0.041 41,455 — — 0.40
[89] 70 — — 0.196 56,970 — 0.02 1.70
[90] 27 12 — 3.35 237,509 — — —
[92] 42 68 — 2.4362 — — 1 0.80
[93] 21 6.75 — 0.43 20,570 — — —
This study 6.91 14.5 12.67 0.433–0.475 22,741–24,400 29.41–35.33 0.38–0.54 0.25–0.47
1
Real discount rate.
2
€/kWh.

observed in Table 11 that the proposed PV-hydrogen energy system is rate, and cost of components. On the other hand, the reliability of the
more economical than grid extension if the grids are located beyond the system is dependent on the individual’s system design parameters and
distances of 39.27 km to 44.85 km in seven divisions. configurations. It is also worth noting that the various authors have
taken the hypothetical value of the real discount rate as 6 %. However,
in the present work, the discount rate and inflation rate are taken from
7.2. Comparison with other studies the state bank of Pakistan to reflect the real cost of the energy system.

Table 1 represents the overview of previous studies conducted on 8. Safety and protection considerations of utilizing H2 based
hydrogen-based renewable energy systems. In contrast, Table 12 com­ energy system
pares this work with similar studies having identical system architec­
ture. Among other studies in Table 1, [31,49,52,57] studied the PV- Firstly, the proposed energy system is based on hydrogen, which has
hydrogen system, the same as the energy system modeling of the pre­ low viscosity, is highly diffusible, and has a wide flammability range.
sent study. In [31], the authors considered 138 kWh/day daily load Secondly, fuel cell requires careful maintenance for safe and optimal
demand. NPC and COE were in the range of $ 3,27,557– 4,43,004 and operation, which needs technical expertise. Therefore, safety and pro­
0.509–0.689 $/kWh for all states of India. Excess electricity produced by tection precautions must be considered, which are highlighted as
the system was between 41.1 % and 21.4 %, while the capacity shortage follows:
and the unmet electric load were reported to be between 0 and 1 %. The
nominal discount rate was assumed to be 6 %. However, in present a) Fuel cells should be employed, operated, and maintained in a suit­
study, the COE and NPC ranged from 0.433 $/kWh to 0.475 $/kWh and able place to ensure safe operation. In the planning phase of the FC
$ 22,741 to $ 24,400. The COE of the present study seems to be better system deployment, it should be considered whether it is required to
than [31], while no considerable difference is found in excess electricity, separate the fuel cell occupied room from other rooms. Rooms con­
capacity shortage, and unmet electric load. In [49], researchers pro­ nected to the fuel cell occupied space must be gas tight.
posed a PV-hydrogen system to satisfy the 16,000 kWh/day load de­ b) Hydrogen leakage is a significant operational problem associated
mand of a city in France. The nominal discount rate was taken as 10 %. with hydrogen-based systems. Hydrogen can leak from high-pressure
The COE and NPC were 0.12 $/kWh and $ 8,942,636. The reason for storage tanks almost three times as quickly as methane gas. However,
such low COE is that the authors have taken the cost of FC as $ 3,000/ the risk of leakage can be considerably reduced by using adequate
5kW, which is 75 % lower than the cost of FC in the present study. In sealing interfaces and equipment.
section 6.3, it has been evaluated that the cost of FC plays a crucial role c) Hydrogen ignites with an invisible flare; therefore, it is challenging
in both TNPC and COE. The authors [52] have studied rural areas of to spot. Even so, it is possible to avoid the generation of potentially
Egypt having a daily load of 594 kWh/day. The nominal discount and explosive compounds by utilizing proper ventilation if a hydrogen
inflation rates were taken as 12.25 % and 17 %, respectively. The COE system is employed in a confined room.
and NPC were calculated to be 0.334 $/kWh and $ 3,244,897, which is d) Since hydrogen is a colorless and odorless gas, it cannot be sensed by
comparable with the economy of the present study. No information humans; hence, tools should be available to detect its presence in
about excess electricity, capacity shortage, and unmet electric load was potential spots where the leakage is possible. In addition, employing
provided. In [57], the load was taken to be 6.8 kWh/day, a typical a hydrogen detection system is crucial to activate the alarms, safe
household load. The nominal discount and inflation rates were consid­ operations, and when necessary, the safe evacuation of individuals.
ered 6 % and 8 %. As a result, the COE and NPC were estimated to be e) Adequate tools and expertise are needed to allow safe cleaning,
0.195 $/kWh and $ 12,282. No detail was found in the article for excess testing, and servicing of the hydrogen system. Therefore, it is highly
electricity, capacity shortage, and unmet electric load. After comparing recommended that consumers acquire basic training for smooth, safe
the present study with the previously published articles, it can be and optimal operation of the hydrogen-based energy system.
concluded that the economy of the reported energy systems is signifi­
cantly affected by economic parameters, such as discount rate, inflation

18
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

9. Policy implications 10. Conclusion and future recommendations

The Government of Pakistan may contribute a vital role in electri­ Motivated by the 2030 green energy goal of Pakistan and the
fying remote areas having no access to grid electricity with the hydrogen production potential of Balochistan through solar energy, this
hydrogen-based renewable energy system. To successfully deploy the study proposed the PV-hydrogen energy system to electrify rural
proposed energy system across the country, the policy implications households in all seven divisions of Balochistan. The proposed system is
based on the obtained results are presented as follows: thoroughly investigated using HOMER software. Sensitivity analysis is
conducted to analyze the impact of uncertain variables on the system’s
a) Fig. 13 and Fig. 14 show that the cost of FC significantly affects the economy. In addition, robustness analysis is carried out to confirm the
COE and NPC. Therefore, the government should provide incentives technical reliability of the system. Breakeven distance is also estimated
and tax relaxations to consumers to purchase FC and other hydrogen to compare the cost of the proposed off-grid system with grid extension.
equipment. It will improve the individual consumers’ purchasing The simulation results verified that the proposed system is optimally
capacity and increase the employment of hydrogen-based RES sized, economically feasible, and technically reliable. The key points of
among the local inhabitants. the investigation of the proposed system are summarized as follows:
b) Fig. 15 represents that the COE decreases linearly with an increase in
load, which calls for the mass-scale deployment of such projects. In a) To satisfy the daily annual load demand of 6.91 kWh/day of a typical
this context, policymakers should consider employing a hydrogen- household in all divisions of Balochistan, the optimal system con­
based distributed energy system to serve the large-scale load, such figurations were found to be in the range of 5.50–5.80 kW for solar
as community load and village load. panel, 0.70–0.75 kW for fuel cell, 1.75–2 kW for electrolyzer,
c) Fig. 17 shows that the proposed system is technically reliable to 0.9–1.10 kg for hydrogen tank capacity, and 0.8 kW for an inverter.
satisfy the load demand. In addition, the breakeven analysis in b) NPC and COE of the optimal system configurations were observed to
Fig. 18 showed that the proposed system is more economical than be in the range of $ 22,741 to $ 24,400 and 0.433 $/kWh to 0.475
grid extension for rural areas. Therefore, policymakers should pro­ $/kWh. Zhob division accounts for the highest NPC ($ 24,400) and
mote hydrogen-based RES for rural electrification by providing COE (0.475 $/kWh). Contrarily, NPC ($ 22,471) and COE (0.433
attractive financial schemes to investors and stakeholders to invest in $/kWh) are estimated to be the lowest for Kalat division.
mega projects. In addition, the government should provide subsidies c) The annual energy demand is mainly satisfied by PV panels during
to relevant microfinancing projects in rural regions. Moreover, non- the day, having an electricity production share of 83.18 % to 84.96
profit organizations that help rural villages in employing rE-based %. In contrast, FC met the energy demand mostly during the night,
energy systems should be given tax relaxation and subsidized with electricity production share between 15.04 % and 16.82 %,
equipment to encourage them to expand hydrogen-based RES respectively.
projects. d) The excess annual electricity produced is between 29.49 % and
d) In this study, satellite-based solar radiation data is utilized due to the 35.34 %. The capacity shortage and unmet electric load are less than
unavailability of ground-based solar radiation data in the studied 0.479 % and 0.549 %, respectively.
region. Currently, nine ground-based solar measurement stations are e) Electrolyzer shares a maximum percentage of load consumption
installed in four provinces of Pakistan, which are insufficient. (65.54 % to 66.99 %) in contrast to AC primary load (33.18 % to
Therefore, it is of utmost need to install enough ground-based solar 34.56 %).
radiation measurement stations across the country, and relevant data f) The hydrogen production from the electrolyzer is in the range of 103
should be made available for researchers to conduct cutting-edge kg/yr to 110 kg/yr. In addition, the hydrogen level relative to the
research and investors to make decisions for profitable investments. tank size remains above 70 % throughout the year.
e) It is also worth noting that the O&M of fuel cell and protection of the g) Sensitivity analyses showed that FC significantly impacts the sys­
high-pressure hydrogen tank is challenging. Thus, the concerned tem’s economy among other components of the proposed energy
regulatory authority must arrange hands-on consumer training system. COE and NPC decrease linearly as the FC cost decreases. An
before providing a permit for hydrogen-based RES. In addition, the increase in load demand by 10 % causes COE to reduce by 4.2 %,
government should arrange mass-level training sessions, workshops, while increasing NPC by 1.5 %. Furthermore, by decreasing the
etc., for different types of consumers (residential, commercial, and nominal discount rate from 15 % to 5 %, the COE decreases by 26.9
industrial) to effectively use hydrogen-based energy system. %, and NPC doubles.
Furthermore, policymakers must ensure that only authorized com­ h) Robustness analysis confirmed that the proposed PV-hydrogen sys­
panies are employing hydrogen-based RES, and after-sales O&M tem is technically robust to supply continuous electricity to satisfy
services are supposed to be provided. the energy load demand throughout the year.
f) The proposed hydrogen-based energy system can help to achieve the i) Breakeven analysis revealed that the proposed energy system is more
2030 green energy goal of Pakistan. Therefore, the government economical than grid extension if the grids are located beyond the
should start state-level R&D programs aiming to explore the poten­ distances of 39.2 km to 44.8 km in seven divisions.
tial of hydrogen production through different RE resources to meet
the energy demand of the country and encourage relevant ministries Based on the findings of this study, it can be concluded that the
to implement such projects successfully. proposed PV-hydrogen system is a feasible solution to electrify rural
households in Balochistan in terms of cost, performance, and reliability.
The Government of Pakistan should consider the policy implication,
enlightened in this work (section 10), for the wider deployment of

19
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

hydrogen-based energy systems. Recommendations for future studies in

4.870
6.900

7.050
11.920
17.720
23.020
26.630
27.140
25.610
22.340
16.760
11.600
line with the present work are suggested as follows:

AT
a) The scope of the present study can be further expanded by incor­
porating a wide range of loads, such as villages, university campuses,

3.630
4.400
5.190
6.480
7.130
7.410
6.970
6.560
6.000
5.080
3.990
3.390
hospitals, factories, and the whole city.

DR
b) For different regions of Pakistan, other renewable energy resources,
for example, wind, hydro, and biomass, can be included in the pro­
posed energy system in the future.

0.598
0.604
0.586
0.631
0.642
0.651
0.622
0.623
0.644
0.657
0.630
0.596
Kalat
c) This work can be further extended to study utility scale economic

CI
models, such as sale and purchase of electricity to and from the grid,
wherein the profits earned are a function of the costs associated with

13.310
15.940
21.690
27.670
32.970
35.390
34.600
32.810
30.530
25.730
20.170
15.300
several input parameters. To study the cause and effect process with

AT
the simultaneous variation of different cost factors, the Monte Carlo
simulation tool can be used to generate the probability distribution
function for each input variable under a localized scenario to study

3.860
4.680
5.270
6.170
6.640
6.620
6.120
5.880
5.460
4.960
4.060
3.540
DR
their effect on the profits earned.
d) Stochastic TEA data analysis can be performed to evaluate the eco­

Nasirabad
nomic model in a decision-oriented manner to predict the process

0.617
0.629
0.588
0.599
0.599
0.583
0.547
0.557
0.581
0.630
0.624
0.603
economics based on the changes in assumptions and input variables

CI
to facilitate its real-time implementation, therefore, minimizing the
risk and uncertainties associated with the system.

10.240
12.690
18.310
24.570
30.220
33.180
32.880
31.350
28.380
23.070
17.460
12.510
e) Researchers can further explore the safety and protection aspects of

AT
hydrogen-based energy systems, specifically for domestic consumers
and generally for all types of consumers.

3.590
4.340
4.960
6.150
6.720
6.920
6.430
6.020
5.650
4.780
3.910
3.290
The proposed energy system can be successfully employed in other

DR
rural areas across the globe, provided that solar energy resources, load
profile, and climate conditions are quite similar to the considered di­

0.599
0.602
0.563
0.601
0.605
0.607
0.573
0.572
0.610
0.624
0.626
0.588
visions in the present study.

Sibi

CI
CRediT authorship contribution statement

7.030
9.410

9.310
14.920
21.020
26.780
29.850
29.700
28.480
25.140
19.570
14.020
AT

Tahir Khan: Conceptualization, Methodology, Software, Writing –


original draft, Investigation. Muhammad Waseem: Visualization,
Monthly data of clearness index, daily solar radiation, and ambient temperature for seven divisions.

Validation, Writing – review & editing. Mustafa Tahir: Formal analysis,


3.650
4.560
5.250
5.990
6.750
6.830
6.410
5.950
5.620
4.910
3.980
3.460
DR

Investigation. Shengyuan Liu: Writing – review & editing, Investiga­


tion. Miao Yu: Supervision, Funding acquisition, Visualization.
Loralai

0.623
0.643
0.602
0.587
0.608
0.598
0.570
0.567
0.611
0.650
0.650
0.634
CI

Declaration of Competing Interest

The authors declare that they have no known competing financial


11.670
17.680
23.610
27.330
27.750
26.350
22.740
16.860
11.120
4.140
6.270

6.390
interests or personal relationships that could have appeared to influence
AT

the work reported in this paper.


3.620
4.490
5.150
5.830
6.600
6.650
6.280
5.890
5.530
4.840
3.850
3.370

Data availability
DR

Data will be made available on request.


0.640
0.649
0.599
0.575
0.594
0.580
0.558
0.563
0.608
0.654
0.650
0.641
Zhob

Acknowledgment
CI

This work was supported by the National Natural Science Foundation


4.230
6.230

6.550
11.320
17.290
22.800
26.670
27.350
25.900
22.300
16.520
11.200

of China under grant number 52077194. The first author would like
AT

thank his mother for her moral support and kind prayers for this work.
3.610
4.460
5.340
6.230
6.940
7.140
6.670
6.210
5.760
4.990
4.080
3.420

Appendix A
DR

Table A1Table A2.


Quetta

0.644
0.627
0.611
0.610
0.625
0.625
0.594
0.591
0.625
0.658
0.664
0.623
CI
Table A1

Month

May

Nov
Mar

Aug

Dec
Apr

Jun
Feb

Sep
Jan

Oct
Jul

20
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Table A2
Daily load consumption calculation of household.
Equipment Consumption (W/unit) Quantity Daily operating hours (Kwh/day) (Kwh/month)

LED lights 24 5 10 1.2 36


Fan 50 2 18 1.8 54
Television 60 1 4 0.24 7.2
Cell phone Charger 10 2 1 0.02 0.6
Computer 250 1 4 1 30
Washing Machine 1000 1 0.3 0.3 9
Iron 1500 1 0.3 0.3 12
Water pump 250 1 1 0.25 7.5
fridge 100 1 24 2.4 72
Total/house 6.91 207.3

Appendix B

Fig. B1Fig. B2.

Fig. B1. FC hourly performance throughout the year in seven divisions.

21
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Fig. B2. Cash flow summary of each component of the proposed energy system.

22
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

Appendix C. Supplementary data [31] Pal P, Mukherjee V. Off-grid solar photovoltaic/hydrogen fuel cell system for
renewable energy generation: An investigation based on techno-economic
feasibility assessment for the application of end-user load demand in North-East
Supplementary data to this article can be found online at https://doi. India. Renew Sustain Energy Rev 2021;149:111421.
org/10.1016/j.enconman.2022.116284. [32] Ceran B, Hassan Q, Jaszczur M, Sroka K. An analysis of hybrid power generation
systems for a residential load. E3S Web Conf., vol. 14, EDP Sciences; 2017.
[33] Kazim A. Economical and environmental assessments of proton exchange
References membrane fuel cells in public buildings. Energy Convers Manag 2001;42:763–72.
[34] Zoulias EI, Lymberopoulos N. Techno-economic analysis of the integration of
[1] Mbiankeu Nguea S, Kaguendo UVE, Noumba I. Are growth effects of foreign capital hydrogen energy technologies in renewable energy-based stand-alone power
significant for increasing access to electricity in Africa? Energy Policy 2022;168: systems. Renew Energy 2007;32:680–96.
113129. [35] Ashourian MH, Cherati SM, Mohd Zin AA, Niknam N, Mokhtar AS, Anwari M.
[2] Raza MA, Khatri KL, Ul Haque MI, Shahid M, Rafique K, Waseer TA. Holistic and Optimal green energy management for island resorts in Malaysia. Renew Energy
scientific approach to the development of sustainable energy policy framework for 2013;51:36–45.
energy security in Pakistan. Energy Rep 2022;8:4282–302. [36] Ren H, Wu Q, Gao W, Zhou W. Optimal operation of a grid-connected hybrid PV/
[3] Lin B, Raza MY. Analysis of electricity consumption in Pakistan using index fuel cell/battery energy system for residential applications. Energy 2016;113:
decomposition and decoupling approach. Energy 2021;214:118888. 702–12.
[4] Ahmed A, Bin NT, Naqvi AA, Siddiqui MA, Khan MH, Bin Zahid MS, et al. [37] Elkadeem MR, Wang S, Azmy AM, Atiya EG, Ullah Z, Sharshir SW. A systematic
Investigation of PV utilizability on university buildings: A case study of Karachi, decision-making approach for planning and assessment of hybrid renewable
Pakistan. Renew. Energy 2022;195:238–51. energy-based microgrid with techno-economic optimization: A case study on an
[5] Xu B, Chen J. How to achieve a low-carbon transition in the heavy industry? A urban community in Egypt. Sustain Cities Soc 2020;54:102013.
nonlinear perspective. Renew Sustain Energy Rev 2021;140:110708. [38] Bezmalinović D, Barbir F, Tolj I. Techno-economic analysis of PEM fuel cells role in
[6] Xu B, Lin B. Can expanding natural gas consumption reduce China’s CO2 photovoltaic-based systems for the remote base stations. Int J Hydrogen Energy
emissions? Energy Econ 2019;81:393–407. 2013;38:417–25.
[7] Xu B, Lin B. Investigating drivers of CO2 emission in China’s heavy industry: A [39] Zhang W, Maleki A, Rosen MA, Liu J. Optimization with a simulated annealing
quantile regression analysis. Energy 2020;206:118159. algorithm of a hybrid system for renewable energy including battery and hydrogen
[8] Samad H, Zhang F. Electrification and Household Welfare. Electrif Househ Welf storage. Energy 2018;163:191–207.
Evid from Pakistan 2018. [40] Zhang W, Maleki A, Rosen MA, Liu J. Sizing a stand-alone solar-wind-hydrogen
[9] Bhutto AW, Bazmi AA, Zahedi G. Greener energy: Issues and challenges for energy system using weather forecasting and a hybrid search optimization
Pakistan—Solar energy prospective. Renew Sustain Energy Rev 2012;16:2762–80. algorithm. Energy Convers Manag 2019;180:609–21.
[10] Sadiqa A, Gulagi A, Breyer C. Energy transition roadmap towards 100% renewable [41] Sanchez VM, Chavez-Ramirez AU, Duron-Torres SM, Hernandez J, Arriaga LG,
energy and role of storage technologies for Pakistan by 2050. Energy 2018;147: Ramirez JM. Techno-economical optimization based on swarm intelligence
518–33. algorithm for a stand-alone wind-photovoltaic-hydrogen power system at south-
[11] Rafique MM, Kang YT, Rafique MM, Rehman S, Alhems LM. Assessment of solar east region of Mexico. Int J Hydrogen Energy 2014;39:16646–55.
energy potential and its deployment for cleaner production in Pakistan. J Mech Sci [42] Devrim Y, Bilir L. Performance investigation of a wind turbine–solar photovoltaic
Technol 2020 348 2020;34:3437–43. panels–fuel cell hybrid system installed at İncek region – Ankara. Turkey Energy
[12] Mirza UK, Mercedes Maroto-Valer M, Ahmad N. Status and outlook of solar energy Convers Manag 2016;126:759–66.
use in Pakistan. Renew Sustain Energy Rev 2003;7:501–14. [43] Samy MM, Mosaad MI, Barakat S. Optimal economic study of hybrid PV-wind-fuel
[13] Shah SAA, Das VG, Memon AA, Laghari AN, Jalbani NB, Strait JL. Techno- cell system integrated to unreliable electric utility using hybrid search optimization
economic analysis of solar PV electricity supply to rural areas of Balochistan, technique. Int J Hydrogen Energy 2020;46:11217–31.
Pakistan. Energies 2018;11. [44] Singh A, Baredar P. Techno-economic assessment of a solar PV, fuel cell, and
[14] Rahman MM, Oni AO, Gemechu E, Kumar A. Assessment of energy storage biomass gasifier hybrid energy system. Energy Rep 2016;2:254–60.
technologies: A review. Energy Convers Manag 2020;223:113295. [45] Ozden E, Tari I. Energy–exergy and economic analyses of a hybrid solar–hydrogen
[15] Jin L, Wang XJ, Zhu JW, Wang CF, Zhou TT, Zhang XW. Sensitivity analysis of renewable energy system in Ankara. Turkey Appl Therm Eng 2016;99:169–78.
proton exchange membrane fuel cell performance to operating parameters and its [46] Dursun B. Determination of the optimum hybrid renewable power generating
applicability assessment under different conditions. Energy Convers Manag 2021; systems for Kavakli campus of Kirklareli University. Turkey Renew Sustain Energy
228:113727. Rev 2012;16:6183–90.
[16] Pakistan census 2017. n.d. [47] Silva SB, Severino MM, De Oliveira MAG. A stand-alone hybrid photovoltaic, fuel
[17] Jamil F. Impact of different public E&P policies on natural gas reserves and cell and battery system: A case study of Tocantins. Brazil Renew Energy 2013;57:
production in Pakistan. Resour Policy 2012;37:368–74. 384–9.
[18] Ahmad R, Akif SAA. Technocratic Solutions versus Political Realities: [48] Kalinci Y, Hepbasli A, Dincer I. Techno-economic analysis of a stand-alone hybrid
Implementing Governance Reforms in the Balochistan Province of Pakistan. Policy renewable energy system with hydrogen production and storage options. Int J
Soc 2007;26:83–108. Hydrogen Energy 2015;40:7652–64.
[19] Raza MA, Khatri KL, Israr A, Ul Haque MI, Ahmed M, Rafique K, et al. Energy [49] Mohammed OH, Amirat Y, Benbouzid M, Elbaset AA. Optimal design of a PV/fuel
demand and production forecasting in Pakistan. Energy Strateg Rev 2022;39: cell hybrid power system for the city of Brest in France. 2014 1st Int Conf Green
100788. Energy, ICGE 2014 2014:119–23.
[20] Stökler S, Schillings C, Kraas B. Solar resource assessment study for Pakistan. [50] Khare V, Nema S, Baredar P. Optimization of hydrogen based hybrid renewable
Renew Sustain Energy Rev 2016;58:1184–8. energy system using HOMER, BB-BC and GAMBIT. Int J Hydrogen Energy 2016;41:
[21] Zhao J, Patwary AK, Qayyum A, Alharthi M, Bashir F, Mohsin M, et al. The 16743–51.
determinants of renewable energy sources for the fueling of green and sustainable [51] Khalid F, Dincer I, Rosen MA. Analysis and assessment of an integrated hydrogen
economy. Energy 2022;238:122029. energy system. Int J Hydrogen Energy 2016;41:7960–7.
[22] Chien FS, Kamran HW, Albashar G, Iqbal W. Dynamic planning, conversion, and [52] Samy MM, Barakat S, Ramadan HS. A flower pollination optimization algorithm for
management strategy of different renewable energy sources: A Sustainable an off-grid PV-Fuel cell hybrid renewable system. Int J Hydrogen Energy 2019;44:
Solution for Severe Energy Crises in Emerging Economies. Int J Hydrogen Energy 2141–52.
2021;46:7745–58. [53] Lata-García J, Jurado F, Fernández-Ramírez LM, Sánchez-Sainz H. Optimal
[23] Wu B, Zhai B, Mu H, Peng X, Wang C, Patwary AK. Evaluating an economic hydrokinetic turbine location and techno-economic analysis of a hybrid system
application of renewable generated hydrogen: A way forward for green economic based on photovoltaic/hydrokinetic/hydrogen/battery. Energy 2018;159:611–20.
performance and policy measures. Environ Sci Pollut Res 2021. [54] Ghenai C, Bettayeb M, Brdjanin B, Hamid AK. Hybrid solar PV/PEM fuel Cell/
[24] He W, Abbas Q, Alharthi M, Mohsin M, Hanif I, Vinh Vo X, et al. Integration of Diesel Generator power system for cruise ship: A case study in Stockholm. Sweden
renewable hydrogen in light-duty vehicle: Nexus between energy security and low Case Stud Therm Eng 2019;14:100497.
carbon emission resources. Int J Hydrogen Energy 2020;45:27958–68. [55] Li C. Techno-economic study of off-grid hybrid photovoltaic/battery and
[25] Shah SAA. Feasibility study of renewable energy sources for developing the photovoltaic/battery/fuel cell power systems in Kunming, China. Energy Sources,
hydrogen economy in Pakistan. Int J Hydrogen Energy 2020;45:15841–54. Part A Recover Util Environ Eff 2019;41:1588–604.
[26] Gondal IA, Masood SA, Khan R. Green hydrogen production potential for [56] Arévalo P, Benavides D, Lata-García J, Jurado F. Energy control and size
developing a hydrogen economy in Pakistan. Int J Hydrogen Energy 2018;43: optimization of a hybrid system (photovoltaic-hidrokinetic) using various storage
6011–39. technologies. Sustain Cities Soc 2020;52:101773.
[27] Azhar N, Kousar F, Kalsoom S, Akhtar Y. Resolution of Wind Energy and Power in [57] Hassan Q. Optimisation of solar-hydrogen power system for household
Coastline of Balochistan. Pakistan J Comput Theor Nanosci 2017;14:5882–7. applications. Int J Hydrogen Energy 2020;45:33111–27.
[28] Arsalis A, Papanastasiou P, Georghiou GE. A comparative review of lithium-ion [58] Tazay AF, Samy MM, Barakat S. A Techno-Economic Feasibility Analysis of an
battery and regenerative hydrogen fuel cell technologies for integration with Autonomous Hybrid Renewable Energy Sources for University Building at Saudi
photovoltaic applications. Renew Energy 2022;191:943–60. Arabia. J Electr Eng Technol 2020;15:2519–27.
[29] Das HS, Tan CW, Yatim AHM, Lau KY. Feasibility analysis of hybrid photovoltaic/ [59] Pal P, Mukherjee V, Kumar P, Elizabeth MM. Viability analysis of direct current
battery/fuel cell energy system for an indigenous residence in East Malaysia. (DC) standalone hybrid photovoltaic (PV)/ hydrogen fuel cell (HFC) energy
Renew Sustain Energy Rev 2017;76:1332–47. system: A techno-economic approach. Mater Today Proc 2020.
[30] Daud WRW, Rosli RE, Majlan EH, Hamid SAA, Mohamed R, Husaini T. PEM fuel [60] Salameh T, Abdelkareem MA, Olabi AG, Sayed ET, Al-Chaderchi M, Rezk H.
cell system control: A review. Renew Energy 2017;113:620–38. Integrated standalone hybrid solar PV, fuel cell and diesel generator power system

23
T. Khan et al. Energy Conversion and Management 271 (2022) 116284

for battery or supercapacitor storage systems in Khorfakkan, United Arab Emirates. [77] Felseghi RA, Carcadea E, Raboaca MS, Trufin CN, Filote C. Hydrogen Fuel Cell
Int J Hydrogen Energy 2021;46:6014–27. Technology for the Sustainable Future of Stationary Applications. Energies 2019,
[61] Okundamiya MS. Size optimization of a hybrid photovoltaic/fuel cell grid Vol 12, Page 4593 2019;12:4593.
connected power system including hydrogen storage. Int J Hydrogen Energy 2021; [78] Duman AC, Güler Ö. Techno-economic analysis of off-grid PV/wind/fuel cell
46:30539–46. hybrid system combinations with a comparison of regularly and seasonally
[62] Modern-Era Retrospective analysis for Research and Applications V 2. MERRA-2 n. occupied households. Sustain Cities Soc 2018;42:107–26.
d. https://gmao.gsfc.nasa.gov/reanalysis/MERRA-2/ (accessed June 5, 2022). [79] Barbir F. Fuel Cell Applications. PEM. Fuel Cells 2005:337–97.
[63] Ramachandra TV, Krishnadas G, Jain R. Solar Potential in the Himalayan [80] Ghenai C, Bettayeb M. Modelling and performance analysis of a stand-alone hybrid
Landscape. ISRN Renew Energy 2012;2012:1–13. solar PV/Fuel Cell/Diesel Generator power system for university building. Energy
[64] Islam MD, Alili AA, Kubo I, Ohadi M. Measurement of solar-energy (direct beam 2019;171:180–9.
radiation) in Abu Dhabi. UAE Renew Energy 2010;35:515–9. [81] Brka A, Al-Abdeli YM, Kothapalli G. Predictive power management strategies for
[65] Aliana A, Chang M, Østergaard PA, Victoria M, Andersen AN. Performance stand-alone hydrogen systems: Operational impact. Int J Hydrogen Energy 2016;
assessment of using various solar radiation data in modelling large-scale solar 41:6685–98.
thermal systems integrated in district heating networks. Renew Energy 2022;190: [82] KuMax high efficiency poly module n.d. https://www.solar-security.co.za/
699–712. product/kumax-high-efficiency-poly-module/ (accessed June 15, 2022).
[66] Alam Hossain Mondal M, Sadrul Islam AKM. Potential and viability of grid- [83] Bhatt A, Ongsakul W, Madhu MN. Optimal techno-economic feasibility study of
connected solar PV system in Bangladesh. Renew. Energy 2011;36:1869–74. net-zero carbon emission microgrid integrating second-life battery energy storage
[67] Luta DN, Raji AK. Optimal sizing of hybrid fuel cell-supercapacitor storage system system. Energy Convers Manag 2022;266:115825.
for off-grid renewable applications. Energy 2019;166:530–40. [84] Maisanam AKS, Biswas A, Sharma KK. Integrated socio-environmental and techno-
[68] Shahzad MK, Zahid A, Rashid T, Rehan MA, Ali M, Ahmad M. Techno-economic economic factors for designing and sizing of a sustainable hybrid renewable energy
feasibility analysis of a solar-biomass off grid system for the electrification of system. Energy Convers Manag 2021;247:114709.
remote rural areas in Pakistan using HOMER software. Renew Energy 2017;106: [85] Abdin Z, Mérida W. Hybrid energy systems for off-grid power supply and hydrogen
264–73. production based on renewable energy: A techno-economic analysis. Energy
[69] Rad MAV, Ghasempour R, Rahdan P, Mousavi S, Arastounia M. Techno-economic Convers Manag 2019;196:1068–79.
analysis of a hybrid power system based on the cost-effective hydrogen production [86] Das VG, Uqaili MA, Memon HUR, Samoo SR, Mirjat NH, Harijan K. Overcoming
method for rural electrification, a case study in Iran. Energy 2020;190:116421. electricity crisis in Pakistan: A review of sustainable electricity options. Renew
[70] Nesamalar JJD, Suruthi S, Raja SC, Tamilarasu K. Techno-economic analysis of Sustain Energy Rev 2017;72:734–45.
both on-grid and off-grid hybrid energy system with sensitivity analysis for an [87] Kumar A, Sah B, Singh AR, Deng Y, He X, Kumar P, et al. A review of multi criteria
educational institution. Energy Convers Manag 2021;239:114188. decision making (MCDM) towards sustainable renewable energy development.
[71] Ahmad J, Imran M, Khalid A, Iqbal W, Ashraf SR, Adnan M, et al. Techno economic Renew Sustain Energy Rev 2017;69:596–609.
analysis of a wind-photovoltaic-biomass hybrid renewable energy system for rural [88] Ali F, He RR, Jiang YX. Size, Value and Business Cycle Variables. The Three-Factor
electrification: A case study of Kallar Kahar. Energy 2018;148:208–34. Model and Future Economic Growth: Evidence from an Emerging Market. Econ
[72] Mokhtara C, Negrou B, Settou N, Bouferrouk A, Yao Y. Design optimization of grid- 2018, Vol 6, Page 14 2018;6:14.
connected PV-Hydrogen for energy prosumers considering sector-coupling [89] Khemariya M, Mittal A, Baredar P, Singh A. Cost and size optimization of solar
paradigm: Case study of a university building in Algeria. Int J Hydrogen Energy photovoltaic and fuel cell based integrated energy system for un-electrified village.
2021;46:37564–82. J Energy Storage 2017;14:62–70.
[73] Vishnupriyan J, Manoharan PS. Prospects of hybrid photovoltaic–diesel standalone [90] Shiroudi A, Taklimi SRH, Mousavifar SA, Taghipour P. Stand-alone PV-hydrogen
system for six different climate locations in Indian state of Tamil Nadu. J Clean energy system in Taleghan-Iran using HOMER software: Optimization and techno-
Prod 2018;185:309–21. economic analysis. Environ Dev Sustain 2013;15:1389–402.
[74] Dincer I, AlZahrani AA. Electrolyzers Compr Energy Syst 2018;4–5:985–1025. [91] Lin B, Xu B. How to effectively stabilize China’s commodity price fluctuations?
[75] Singh A, Baredar P, Gupta B. Techno-economic feasibility analysis of hydrogen fuel Energy Econ 2019;84:104544.
cell and solar photovoltaic hybrid renewable energy system for academic research [92] Tzamalis G, Zoulias EI, Stamatakis E, Varkaraki E, Lois E, Zannikos F. Techno-
building. Energy Convers Manag 2017;145:398–414. economic analysis of an autonomous power system integrating hydrogen
[76] Khan T, Yu M, Waseem M. Review on recent optimization strategies for hybrid technology as energy storage medium. Renew Energy 2011;36:118–24.
renewable energy system with hydrogen technologies: State of the art, trends and [93] Hossain MS, Alharbi AG, Islam KZ, Islam MR, Elavarasan M, Nadarajah M, et al.
future directions. Int J Hydrogen Energy 2022;47:25155–201. Techno-Economic Analysis of the Hybrid Solar PV/H/Fuel Cell Based Supply
Scheme for Green Mobile Communication. Sustain 2021, Vol 13, Page 12508 2021;
13:12508.

24

You might also like