Professional Documents
Culture Documents
0
Date 18.01.2023.
Client Paharpur Cooling Towers Ltd
axial fans for THDC Khurja & NTPC
Project Rihand project
To,
Dear Sir,
We have gone thru same and herewith we are pleased to submit our offer as following.
We trust that you will find our offer as per your expectation level and however, if any further details / clarifications needed, kindly let us know.
Thanking You,
Best Regards,
S. Thiyagu
Attachments:
1. As above.
(A Joint Venture between M/s C. Doctor India Pvt. Ltd. & M/s Industries CBI, Italy)
CB DOCTOR VENTILATORS PRIVATE LIMITED
Date : 18.01.2023. Vendor hasn't quoted for the entire scope of supply for the projects.
Vendor to furnish complete offer w.r.t the quantities highlighted in the
fan questionnaire.
Vendor hasn't mentioned all the technical particulars for the fans
w.r.t to their parts viz. impeller, casing and accessories as filters. Offer No. : CBD / OC / 220488
Vendor to thereby either confirm compliance with the
requirememts of the enquiry spec or list down any deviations
w.r.t them. Rev : 0
It is understood that all fans listed
CLIENT : Paharpur Cooling Towers Ltd below will be tube axial type. Vendor to
confirm.
Project : axial fans for THDC Khurja & NTPC Rihand project
Sr. No Description Note Units Axial Fan 1 Axial Fan 2 Axial Fan 3
8 Quantity Nos. 1 1 1
9 Impeller Diameter Check quantities mentioned in the fan mm 1219 1219 1219
questionnaire. They are 6 nos. for each
model.
10 Impeller configuration - Aerofoil Blade Aerofoil Blade Aerofoil Blade
15 Recommonded Motor @ Optg. Temp. 2 KW / pole 7.5 kW / 4 Pole 7.5 kW / 4 Pole 7.5 kW / 4 Pole
17 Rotor GD2 Value Vendor to specify motor starting type Kg-m2 18.55 18.55 18.55
For motor ≤ 300 KW: As per ISO 14694, as For motor ≤ 300 KW: As per ISO 14694, as per BV- For motor ≤ 300 KW: As per ISO 14694, as per BV-
18 Vibration Level -
per BV-3 category (at site) 3 category (at site) 3 category (at site)
Note:
1 We understand that there is Nil dust coming to fan impeller and hence any wear protection is not considered in our scope.
2 Motor rating mentioned above is indicative and based on shaft power. Final motor rating will be confirmed having checked with motor supplier.
All above figures are subject to tolerance as per for Axial Fan IS 3588. All the values are guaranteed for site after proper installation of fan(s) with system connected.
Offer No. CBD / OC / 220488 Rev. 0
Date 18.01.2023.
Client Paharpur Cooling Towers Ltd
axial fans for THDC Khurja & NTPC Rihand
Vendor to specify MOC of casing
Project project
7 Painting: Conseal touch-up (Acrylic based paint) Total DFT: 50 microns. Shade RAL: 5009 Yes
STD. TEFC Sq. cage induction AC motor. (Non-FLP) (AC – 3 Phase, TEFC, 415V ± 10%, 50 Hz ±
8 Yes IE3 - Efficiency
5%, 60 °C ambient, F class insulation, IP 55 degree of protection, Foot mounted.
(A Joint Venture between M/s C. Doctor India Pvt. Ltd. & M/s Industries CBI, Italy)