Professional Documents
Culture Documents
5.5m B
A
5.5m D C
o K = 1.2 for Slab supported on columns without beams (flat slab) (based on
longer span) (Table 7.4N), fck = 25Mpa
o = 0.005
i. The width of slab used to define the effective stiffness of the slab will depend upon the
aspect ratio of the panels and the type of loading, but the following provisions may be
applied in the absence of more accurate methods:
In the case of vertical loading, the full width of the Panel, and
For lateral loading, 40% the width of the panel may be used to calculate the
stiffness of the slab.
ii. The moment of inertia of any section of slab or column used in calculating the relative
stiffness of members may be assumed to be that of the cross section of the concrete
alone.
iii. Moments and forces within a system of flat slab panels may be obtained from analysis
of the structure under the single load case of maximum design load on all spans or
panels simultaneously, provided:
The ratio of the characteristic imposed load to the characteristic dead load does not
exceed 1.25.
The characteristic imposed load does not exceed 5.0kN/m2 excluding partitions.
iv. Where it is not appropriate to analyse for the single load case of maximum design load
on all spans, it will be sufficient to consider following arrangement of vertical loads:
All spans loaded with the maximum design ultimate load, and
Alternate spans with the maximum design ultimate load and all other spans loaded
with the minimum design ultimate load (1.0Gk).
v. Each frame may be analysed in its entirety by any elastic method. Alternatively, for
vertical loads only, each strip of floor and roof may be analysed as a separate frame
with the columns above and below fixed in position and direction at their extremities.
In either case, the analysis shall be carried out for the "appropriate design ultimate
loads on each span calculated for a strip of slab of width equal to the distance between
centre lines of the panels on each side of the columns.
In our case, there is only vertical load; hence each strip of floor can be analyzed as a separate
frame.
3.6m
A D
B C
3.6m
5.5m 5.5m
In our case, the characteristic imposed load does not exceed 1.25 times the characteristic dead
load we can use the single load case of maximum design load on all spans.
A B C D
248 .81
x= 2.75m
90.475
90.475 * 2.75 2
Mmax = 248.81*2.75 - 233 .18 = 108.94kNm.
2
Comparison of moments at support B show that left side moment is larger. Hence take
moment at the left face of support B.
Exterior span (panel)
90.4475kNm
158.57kNm
255.11kNm
A B
231.25kN 266.36kN
5.5m
90.475 x 2
Mx = 266.36x- 255 .11 , M+ve,max = 136.97kNm
2
Generally, for both methods of analysis, the negative moments greater than those at a distance
hc/2 from the centre-line of the column may be ignored provided the moment Mo obtained as
the sum of the maximum positive design moment and the average of the negative design
moments in anyone span of the slab for the whole panel width is such that:
( g d q d ) L2 ( L1 2hc ) 2
Mo 3
2
Where L1 is the panel length parallel to span, measured from centres of columns.
L2 is the panel width, measured from centres of columns
hc is the effective diameter of a column or column head
When the above condition is not satisfied, the negative design moments shall be increased.
1
Mo = 136.97+ (158 .57 255 .11) 343 .81kNm (average of negative and positive moment)
2
Gd = 1.35gk = 1.35*6.63 = 8.95kN/m2
Qd = 1.5qk = 1.5*5 = 7.5kN/m2
Pd = gd +qd = 16.45kN/m2
The effective diameter of a column or column head hc is the diameter of a circle whose area
equals the cross-sectional area of the column or, if column heads are used, the area of the
column head based on the effective dimensions. In no case shall hc be taken as greater than
one-quarter of the shortest span framing in to the column.
Acol = 450 * 450 = 202500mm2
2c 4 Acol 2 * 450
Acol hc = 2*450/ 3.141/2 = 508mm
4
hc = 508mm
L1 = L2 = 5.5m
-255.11
-158.57
0.508
0.254 m
136.97 2
90.475 2 90.475
Mc = 266.36x- x 255 .11 = 266.36*0.254- * 0.2542-255.11
2 2
= -190.37kNm.
Step 3: Apportioning moments in to column strips and middle strip:
Simplified apportionment of bending moment for a flat slab as per ES EN 1992: 2015 (Refer
Annex I Table I.1)
f yd
m= 23.98
0.8 f cd
Step 4: Check for flexural Design:
The largest moment, Mmax = -142.78kNm
b = 2750mm (for a column strip)
Minimum effective depth to avoid any compression steel (singly reinforced) is given by:
Assuming 25 mm cover, 12 mm diameter bars, the overall depth (D) of the slab is:
Used is …. Safe!
Step 5: Check d for punching shear
Based on the tributary area of the loaded floor
2dav
Dy = 199mm
450+4dav Dx = 187mm
5.5m 1
Deff = (dy+dx)
2
450+4dav
5.5m
The effective dimensions of a column head for use in calculation of hc are limited according
to the depth of the head. In any direction, the effective dimension of a head Lh shall be taken
as the lesser of the actual dimension Lho or Lh,max, where Lh,max is given by:
Lh,max = Lc + 2dh = 450mm +2*100mm = 850mm
The smaller dimension of the drop is at least one third of the smaller dimension of the
surrounding panels, Lx/3 and the drop may be 25 to 50 percent thicker than the rest of the
slab.
Thickness of slab around drop panel = 1.25ts = 1.25*220 = 275mm
Thickness of drop panel = Thickness of slab around drop panel - Thickness of slab outside of
drop panel
Thickness of drop panel = 275mm - 220mm = 55mm.
Actual dimension Lh0 = Lx/3 = 5500mm/3 = 1833.333mm
Lh,max = Lc + 2dh = 450mm +2*100mm = 850mm
In any direction, the effective dimension of a head Lh shall be taken as the lesser of the actual
dimension Lho or Lh,max. From these Lh = 850mm
Provide a square head of side length (Lh) = 850mm and depth, additional to that of the slab of
100mm. Since, it is out of the head neglect this critical perimeter. Consider critical perimeter
from the face of the drop.
2dav 2dav
Lh,max
Lho dh
450
Lc = 450mm
Lc Dh = 100mm
Lho = 850mm
Lhmax = Lc + 2dh = 450 + 2 * 100 = 650mm
Lh = 650mm
-158.57
-255.11
(-) (-)
x x
(+) 0.73345
0.3667 m
2
90.475 2
Mx = 266.36x- x -255.11
2
90.475
Mface = 266.36*0.3667- * 0.3667 2 255 .11 = -163.51kNm.
2
Total Bm BM on col.strip BM on middle strip
Direction of span
(kNm) (KNm) (kNm)
Ms = -163.51 0.75Ms = -122.63 0.25Ms = -40.88
Long direction
Mf = 108.94 0.55Mf = 59.92 0.45Mf = 49.02
Ms = -163.51 0.75Ms = -122.63 0.25Ms = -40.88
Short direction
Mf = 108.94 0.55Mf = 59.92 0.45Mf = 49.02
Flexural Reinforcement:
Since, design as a singly reinforced beam.
Sample calculation For Md = Mmax = 122.63kNm from column strip
,
, Then,
For slabs less than 200 mm thick the following maximum spacing rules apply:
Flat slab design Page 12
ASTU SoCEA Dep’t of Civil Engineering RC-II
Long direction and short direction are the same since the panel is square. However, there is
slight difference in spacing of reinforcements
Span length, l = 5500mm
Clear span, ln = 5500-450 = 5050mm
b = 0.20 ln = 0.20*5050 = 1010mm
c = 0.22ln = 0.22*5050 = 1111mm
d = 0.30ln = 0.3*5050 = 1515mm
e = 0.33ln = 0.33*5050 = 16667mm
Step 7: Reinforcement layout:
Exercise
Design the corner panel A and edge panel D.
Redo the above example by using Direct Design Method (DDM)