You are on page 1of 63

STUDY OF 440KV ISOLATORS

A MINI PROJECT REPORT


Submitted to Jawaharlal Nehru Technological
University, Hyderabad
in partial fulfillment of the requirement
for the award of the degree of
BACHELOR OF TECHNOLOGY
By
1.G.DURGA SANTOSH (09N75A0201)
2.R.SURESH KUMAR REDDY (08N71A0222)
3.SESHU.K.R (09N75A0203)
4.V.SANDEEP (08N71A0230)
Under the esteemed guidance of

Internal Guide External Guide


SAKTHI SREEDEVI.S M.MANOHAR

Department of Electrical and Electronics Engineering


D.R.K. INSTITUTE OF SCIENCE AND TECHNOLOGY
Bowrampet (v),Via Air Force Academy, Hyderabad-43.

2011-2012

1
Department of Electrical and Electronics Engineering
D.R.K. INSTITUTE OF SCIENCE AND TECHNOLOGY

Bowrampet (v), via Air Force Academy, Hyderabad-43

CERTIFICATE
This is to certify that the mini project work entitled “STUDY
OF 440KV ISOLATORS” submitted to Jawaharlal Nehru
Technological University, Hyderabad in partial fullfillment of
the requirements for the award of degree of BACHELOR OF
TECHNOLOGY in the Dept. of ELECTRICAL AND
ELECTRONICS ENGINEERING during the academic year
2011-12 is bonafied work by
1. G.DURGA SANTOSH (09N75A0201)

2. R.SURESH KUMAR REDDY (08N71A0222)

3. SESHU.K.R (09N75A0203)

4.V.SANDEEP (08N71A0230)

This work has been carried out under the guidance of

Sri. D. SRINIVASULU SAKTHI SREEDEVI.S

Associate Professor & HOD Assistant Professor


Dept. of Electrical&Electronics engg. Internal Guide,
D.R.K Inst. of Science and Tech. D.R.K Inst. of Science and Tech,
Bowrampet-500043. Bowrampet-500043.

2
3
4
5
6
ACKNOWLEDGEMENTS
With great pleasure, we want to take this opportunity to
express our heart-felt gratitude to all the people who helped in
making this mini-project a grand success.

We are indebted to SIEMENS Ltd. (Hyderabad works) for


giving us this opportunity to do this project. We express our
deep sense of gratitude to Mr. M. Manohar (HR) and Mr.D.
Satish (HR) for their constant support during the entire period
of this mini-project.

We also like to thank Mr. G. Ravi Kumar (Manager –


Manufacturing), Mr. G.Srinivas (Grad. Trainee –
Manufaturing), for taking us through the production process of
isolators.

We would like to express our happiness to Mr. Gopal


Panigrahy (Manager – Quality), Mr. Ravi Chandra (Graduate
Trainee – Quality) for their constant encouragement and support
that they extended throughout our project.

We profoundly thank our HOD, of Electrical and Electronics


Engineering, Mr.D.SRINIVASULU and Smt.SAKTHI
SREEDEVI.S, Asst.Professor & Internal Guide, for their
cooperation during our mini-project.

G.Durga Santosh – 09N75A0201

R.Suresh Kumar Reddy – 08N71A0222

Seshu.k.r – 09N75A0203

V.Sandeep – 08N71A0230

7
ABSTRACT

Dis-connector or Isolator switch is used to make sure that an


electrical circuit can be completely de-energized for service or
maintenance, such switches are often found in electrical
distribution and industrial applications, where machinery must
have its source of driving power removed for adjustment or
repair. High-voltage isolation switches are used in electrical
substation to allow isolation of apparatus such as circuit
breaker, transformers and transmission lines for maintenance.

Isolators come in many shapes and sizes. Different types of


isolators are used based on the operating voltage of a power
system, current rating of the system, kind of sub-station, type of
operation used, amount of insulation required. Some of the
isolators are centre-break disconnectors, double-side break
disconnectors, knee type disconnectors, pantograph and semi-
pantograph disconnectors, vertical break disconnectors. The
isolators are tested for proper functioning of the device. In this
study project, a detailed and in-depth analysis of a 440KV (HV)
isolator is carried out. Their types, design, operation,
production, testing of isolator are considered.

8
CONTENTS

1. INTRODUCTION.……..……………………..…..…..13

1.1. Scope ……………………………………..….…..….13

1.2. Definition.…………………………………….……...13

1.3. Functionality………………………………..……….13

1.4. Importance ...…………………………..……………14

1.5. Types of disconnectors…….………………………..14

2. TYPES AND RATINGS.…………………...…..…….16

2.1. Types………………………………………………....17

2.2. Ratings ...…………………………………………….18

3. DESIGN AND OPERATION ………….……..……..21

3.1. Introduction ………………………………………...21

3.2. Design Criteria …………………………….……….21

3.3. Design and Operation of Disconnectors ...…………26

3.3.1. Design & Operation of HCB Disconnector...……. .26

3.3.3. Design & Operation of Double Break Dis…………32

3.3.4. Design & Operation of Pantograph Dis…………... 39

3.4. Earth Switch ..……………………………………….39

9
4. CONSTRUCTION AND ASSEMBLY …………..…40

4.1. Introduction …………………………………………40

4.2.Construction & Assembly of HCB Disconnector……..42

4.3. Construction and Assembly of DBR Disconnector....46

4.4. Construction and Assembly of PG Disconnector…….50

5. OPERATING MECHANISM AND TESTING….....53

5.1. Introduction………………………………………….53

5.2. Types of Operating Mechanism……………………...53

5.2.1. Manual Operating System without Gear …………..53

5.2.2. Manual Operating System with Gear ……………...54

5.2.3. Motor Operating System …………………………..54

5.3. Testing ……………………………………………….58

6. CONCLUSION..……………………………………...62

BIBLIOGRAPHY ..……………………………………...63

10
LIST OF FIGURES
SNO FIG NO DESCRIPTION PG NO
1 1.1 H.C.B 14
2. 1.2 D.B.R 14
3. 1.3 P.G 14
4. 1.4 Substation Layout 15
5. 3.1 Aluminium contact 22
6. 3.2 Copper contact 22
7. 3.3 HCB DISCONNECTOR 26
8. 3.4 Parts of HCB 26
9. 3.5 Operation of HCB 28
10. 3.6 Skeleton view of HCB 28
11. 3.7 DBR Disconnector 29
12. 3.8 Operation of DBR 31
13. 3.9 Skeleton view of DBR 32
14. 3.10 PG Disconnector 33
15. 3.11 Parts of PG 34
16. 3.13 Gear Box of PG 35
17. 3.14 Operation of PG 37
18. 3.15 Structural diagram of PG 38
19. 3.16 Earth switch 39
20. 5.1 MOM box 55
21. 5.2 Circuit diagram of MOM box 56

11
LIST OF TABLES

SNO TABLE DESCRIPTION PG NO

1. 2.1 Standard voltage ratings 19

2. 3.1 Voltage ratings 22

3. 3.2 HCB Operating limits 28

4. 3.3 Dimensions and ratings of HCB 29

5. 3.4 Dimensions and ratings of DBR 32

6. 3.5 Operating values of PG 38


Disconnector

7. 3.6 Dimensions and ratings 38


of PG disconnector

12
1. INTRODUCTION

1.1 SCOPE:

This report applies to 440KV high voltage disconnectors


which operate at 50Hz frequency and used only for outdoor installation.
It also discusses the various types which can be implemented in the sub-
stations operation at this high voltage.

1.2 DEFINITION:

An Isolator or a Disconnector is a device employed in switchyard


to isolate the required section from the supply point. And it is also used
to divert this power flow from one section to another section. The names
‘isolator’ and ‘disconnector’ are used inter-changeably.

It is used to make sure that an electrical circuit can be


completely de-energized for service or maintenance. Such switches are
often found in electrical distribution and industrial applications, where
machinery must have its source of driving power removed for adjustment
or repair. High-voltage isolation switches are used in electrical
substations to allow isolation of apparatus such as circuit breakers,
transformers and transmission lines for maintenance.

1.3 FUNCTIONALITY:

• All Disconnectors are used to switch-in or switch-out only on no-load


conditions.

• A Disconnector is to carry rated current flowing through the system.

• It should also be capable of carrying the fault current in case of a


fault occurring in the power system, which may be for a short time like

13
one second or three seconds as per the switchyard fault current
calculations.

1.4 IMPORTANCE:

In the modern period, the switchyards are going for unmanned


stations and with the advent of digital relays, the systems are totally
computerized. All the operations are being carried out away from the
switchyard through remote operation controls, SCADA systems etc.

1.5TYPES OF DISCONNECTORS:

1) Horizontal centre break

Fig 1.1 horizontal centre break

2) Double Break disconnector

Fig 1.2 Double break disconnector

3) Pantograph Disconnector

Fig 1.3 Pantograph disconnector

14
Fig 1.4 420KV Sub-station layout

15
2. TYPES AND RATINGS

2.1 TYPES

2.1.1 Introduction:

The function of disconnectors in high voltage power systems, is


to provide electrical and visible isolation of one part of the system. The
isolation generally takes two forms:

1. Isolation related to normal day-to-day operation of the power system.


For example, shunt reactors required only during light load periods are
switched out using circuit breakers and then isolated by disconnectors
during peak load periods.

2. Isolation related to repair or maintenance on transmission lines or


station equipment such as transformers, circuit breakers and so on.

In the latter regard, the disconnectors are a major contributor to


personnel safety. In any power system safety practices require a so-
called guaranteed point of isolation with a visible break. And a
disconnector mechanically locked in the open position meets this
requirement.

If the disconnector is motor-operated, then the electrical circuit of


the operator is also visibly isolated by means of a knife switch or a
removable fuse link.

To serve the purpose of isolation, disconnectors are required


to have a greater voltage withstand capability across the open gap than
to ground. The purpose of this is to ensure that surge voltages originating
in the power system or due to lightning activity will more likely
cause flashover to ground than across the open gap. At system voltages of

16
245 kV and below, this requirement adds at least 10% above the line to
ground voltage withstand capability. At system voltages of 300 kV and
above the requirement is stated as a bias voltage test, (i.e.) an AC
voltage applied to one side of the disconnector and a switching or
lightning surge applied to the other.

High voltage disconnectors come in a variety of types and


mounting arrangements. The most commonly found are given below

• Horizontal Centre Break Disconnector

• Double Break Disconnector

• Pantograph Disconnector

2.1.2 Horizontal Centre Break Disconnector:

The horizontal Centre Break Disconnector is also a simple


design of two post insulators which rotate and join the two
conducting parts. Centre Break disconnectors are used in outdoor high
voltage sub-stations. The disconnector is designed to operate under
severe cold conditions.

2.1.3 Double-Break Disconnector:

The Double Break Disconnector is a variation of the centre


break isolator. It has three columns of post insulators and the centre
post is movable and the remaining two are fixed. The movable
contact rotates and closes the fixed contacts. It is also used in
outdoor high voltage Sub-stations.

2.1.4 Pantograph Disconnector:

The Pantograph Disconnector is a divided support single


column disconnector with vertical isolating distance. It is used in

17
outdoor high voltage Sub-stations. This type of disconnector permits
the design of modern switchgear installations with minimum-space
requirement.

2.2 RATINGS

The common ratings used for disconnectors, including their


operating devices and auxiliary equipment, are given below

• Rated Voltage (Ur)

• Rated Insulation level

• Rated frequency (fr)

• Rated normal current (Ir)

• Rated short-time withstand current(Ik)

• Rated peak withstand current (Ip)

• Rated duration of short circuit (tk)

• Rated supply voltage of closing and opening devices and of auxiliary


circuits (Ur)

• Rated supply frequency of closing and opening devices and of auxiliary


circuits

2.2.1 Rated voltage(Ur):

The rated voltage indicates the upper limit of the highest voltage
of systems for which the disconnector is intended. Standard values of rated
voltages are given below:

18
Range 1(for rated voltages of ≤ Range 2(for rated voltage >
245kv)
245kv)

3.6 KV - 7.2 KV - 12 KV - 17.5 KV – 300 KV – 362 KV – 420 KV – 550 KV –


24 KV - 36 KV - 52 KV - 72.5 KV – 800 KV
100 KV - 123 KV - 145 KV - 170 KV -
245 KV

Table 2.1 Standard voltage ratings

2.2.2 Rated Insulation Level


The rated insulation level is specified by the rated lightning
impulse withstand voltage phase to earth. For most of the rated voltages,
several rated insulation levels exist to allow for application of different
performance criteria or over voltage patterns. The choice should be
made considering the degree of exposure to fast-front and slow-front
over-Voltages, the type of neutral earthing of the system and the type of
over-voltage limiting devices.

2.2.3 Rated frequency (fr)


The standard values of the rated frequency are 16.66 Hz, 25 Hz,
50 Hz and 60 Hz.

2.2.4 Rated normal current (Ir)


The rated normal current of disconnectors is the r.m.s. value
of the current which disconnectors shall be able to carry continuously
under specified conditions of use and behaviour.

2.2.5 Rated short-time withstand current (Ik)


The r.m.s. value of the current which the disconnector can
carry in the closed position during a specified short time under
prescribed conditions of use and behaviour.

19
2.2.6 Rated peak withstand current(Ip)

The peak current associated with the first major loop of the
rated short-time withstand current which disconnectors can carry in
the closed position under prescribed conditions of use and behaviour.

2.2.7 Rated duration of short circuit (tk)

The interval of time for which a disconnector can carry, in the


closed position, a current equal to its rated short-time withstand current.

2.2.8 Rated supply voltage of closing and opening devices


and of auxiliary and control circuits (Ur):

The supply voltage of closing and opening devices and


auxiliary and control circuits is understood to mean the voltage
measured at the circuit terminals of the apparatus itself during its
operation, of opening and closing of the contacts.

The supply system is preferably referenced to earth (i.e. not


completely floating) in order to avoid the accumulation of dangerous
static voltages. The location of the earthing point is defined as a good
practice. It should be noted that normal operation of equipment is
assured when the supply voltage is within the tolerances.

2.2.9 Rated supply frequency of closing and opening devices


and of auxiliary circuits:

The standard values of rated supply frequency are DC, 50 Hz and


60 Hz.

20
3.DESIGN AND OPERATION

3.1 Introduction

This chapter discusses about the design criteria and


constructional features of each and every type of disconnector.

3.2 Design Criteria

To design a disconnector, a lot of standards, specifications,


limitations, conditions are discussed and adopted in the best possible
way. The various types of disconnectors, which were discussed in the
previous chapter, have evolved because of these factors. Some of these
factors are discussed below.

3.2.1 Operating Conditions

• Ambient Temperature and Humidity

• Icing Conditions

• Wind Loads

• Seismic factor

• Altitude

• Induced electromagnetic disturbances

• Pollution factors (corrosive environment)

3.2.2 Application / Installation

The disconnectors can be installed in two ways

1. Outdoor Installation

2. Indoor Installation

21
3.2.3 Current Path / Main Contacts Design:

The current path and the main contacts are designed using two metals.
They are

1. Copper

2. Aluminium

The metal used is dependent on many factors ranging from cost of the
disconnector to current rating and safety standards. The current path
design specifications are given by the user or customer.

Fig 3.1 Aluminium contact Fig 3.2 Copper contact

3.2.4 Types of mounting

Depending on the site layout, the mounting arrangement of the


disconnectors is classified utilize the available space in the switchyard or
substation to the best proximity. The different types of mounting are

• Upright (normal / staggered / series)

• Beam mounting / Gantry mounting / High-level mounting

• Vertical / Wall mounting

• Under Hung

• Pole mounting

22
3.2.5 Voltage Rating

As per the high voltage switch gear products standards, and the
voltage ratings are categorized into two ranges

Range 1(for rated voltage ≤ 245kv) Range 2(for rated voltage > 245kv):

3.6 KV - 7.2 KV - 12 KV - 17.5 KV – 300 KV – 362 KV – 420 KV – 550 KV –


24 KV - 36 KV - 52 KV - 72.5 KV – 800 KV
100 KV - 123 KV - 145 KV - 170 KV -
245 KV

Table 3.1 Voltage Ratings

3.2.6 Current Ratings

• Rated normal current(Ir)

The rated normal current of main contacts is the R.M.S. value of


the current which the disconnector shall be able to carry continuously
under specified conditions of use and behaviour.

• Temperature rise:

The temperature rise of any part of the disconnector at an ambient


air temperature shall not exceed the temperature-rise limits .

3.2.7 Short Time Current Rating

• Rated short time withstand current(Ik)

The R.M.S. value of the current which the disconnector can carry
in the closed position during a specified short time under prescribed
conditions of use and behaviour.

23
• Rated Peak withstand current(Ip)

The peak current associated with the first major loop of the rated
short-time withstand current which disconnector can carry in the closed
position under prescribed conditions of use and behaviour.

• Rated Duration of short circuit(tk)

The interval of time for which the disconnector can carry a current
equals to its rated short time withstand current in the closed position. The
standard value of rated duration of short circuit is 1sec or 3secs.

3.2.8 Number of poles

The design of a disconnector is also dependent on the number of


poles used. The design may be implemented in the following ways.

• Single pole/one pole disconnector

• Double pole disconnector

• Triple pole disconnector

Though the 3-pole disconnector (required for 3-phase system)


design is standard in practice, in some cases like neutral earthing, single
pole/double pole disconnectors are also used.

3.2.9 Number of associated Earth switches

The disconnectors are equipped with earth switches to discharge


residual voltage, surge currents to the earth. Sometimes, due to many
factors like cost, space etc, earth switches are not at all used. Therefore,
the disconnectors could be

24
• Without earth switch

• With one earth switch

• With two earth switches

3.2.10 Mode of Operation

The disconnectors/earthing switches can be operated with two


types of drive mechanisms depending on the requirements.

• Motor operated:

The motor coupled with a 2-stage reduction Worm-Spur gear to


increase the output torque. Motor can be a 3-phase 220/380/400/415/440
Volts AC, 50/60 Hz supply or DC 110/125/220 V supply depending on the
requirements.

• Manual operated

Handle operation: simply one lever is used to operate the equipment.

Crank handle operation with reduction gear mechanism.

3.2.11 Ganging Method

Ganging is said to be implemented when two or more


disconnectors are mounted side by side in a series of connected wall
boxes. It means that a group of disconnectors can be moved or controlled
by a single operating box. The disconnectors can be ganged in two ways:

• Mechanical Ganging

• Electrical Ganging

25
3.3 Design and Operation of Disconnectors:

3.3.1 Design of HCB disconnector:

The horizontal Centre Break Disconnector is also a simple design of two


post insulators which rotate and join the two conducting parts. In this type
of disconnector, there are two moving contacts which are placed above
two separate rotating posts of sufficient insulation level and the contact
making/breaking will be done at the centre and hence the name
Horizontal Centre Break Disconnector. Horizontal Centre Break
disconnectors are majorly used in outdoor highvoltage sub-stations.

Fig 3.3 Horizontal Centre Break Disconnector

The various parts of a HCB are indicated in the diagram.

(1) Base Frame

(2) The operating mechanism

(3) Two rotatable seated supporting insulators

(4) The current path arms

(5) The rotating Unit. Fig.3.4 parts of HCB

26
The support insulators are mounted on the mounting plate and
support both current path halves (finger and contact side) with the rotary
heads and high-tension terminals. This version offers freedom of
arrangement, since the high tension terminal can be turned within 360
degrees. Thus, the installation of a pipe connection or the straining of a
connection cable is possible from any direction.

The current path consists of a welded aluminium structure with a


minimum of terminal points and therefore no appreciable change of the
contact resistance over many years occurs. Disconnectors for a rated
voltage of 170 kV and above are equipped with an interlocking device,
consisting of a catch hook and an interlocking bolt which prevents the two
halves from separating in longitudinal direction in case of high short
circuit currents.

The optionally available earthing unit consists of a hinged type-


earthing switch fixed at the base frame. When in the open position, the
tubular arm is located along the base frame. In closed position the earthing
switch contact attached to the current path comes to rest between the
contact fingers of the earthing switch, which can be mounted either on the
contact side or the finger side or on both sides of the disconnector. The
universal design permits the earthing switch to be attached at site and it
can be retrofitted without any difficulty. All components are protected
against atmospheric influences; the steel parts liable to rusting being hot
galvanized.

3.3.1.2 Operating Principle

Disconnector and earthing switch are operated separately. The


design of the operating mechanism of the disconnector and earthing switch
is such that a dead centre position is passed through shortly before the end
positions are reached. Due to that, incidental opening or closing of the

27
units due to external influences (e.g. short-circuits, storm, earthquake) is
impossible. The energy is transmitted from the operating mechanism of the
disconnector to a rotary pedestal.

The diagonal rods connect all rotary pedestals of each pole which
ensures simultaneous operation. The live part is very simple in its design
and motion as shown in fig 3.8. From the open position, the arms (1) and
(2) rotate together, synchronized by their linkage bar (3) to join in the
middle of the pole, and to close the main contact (4). (5) represents HV
terminals.

Fig 3.5 Operation Fig 3.6 Skeleton view of HCB

3.3.1.3 Technical Data and Dimensions

VOLTAGE CURRENT STC (KA RMS/1 or MOVING BLADE


(KV) (AMPS) 3SECS) DESIGN

12 to 420KV 400 – 3150 A 12.5 - 40 Copper(12-245KV)


Al (12-420KV)

Table 3.2 HCB Operating limits

28
Short time Dimensions
Voltage Current current(KA RMS A B C D
(KV) (amps) 1/3 sec)
440 2000- 40 4460 4100 3320 3650
3150
Table.3.3 Dimensions and Ratings of HCB

3.3.2 Design of Double Break Disconnector (DBR)

The horizontal double-break disconnector consists of three poles.


Each pole consists of a frame, two supporting insulators at each end and
one rotating insulator in the centre, on which the main blade is mounted.
The contact making/breaking will be done at two ends simultaneously and
hence the name Double Break Disconnector.

Fig 3.7 Double Break Disconnector

3.3.2.1 Basic Constructional Features

The load-carrying constructional element of the disconnector is a


sectional-steel base frame. The middle one of the three insulators is fixed
on a common base frame and mounted on the rotary pedestal protected
against atmospheric influences and running on maintenance-free
assembled ball bearings. The middle insulator bears aluminium current
path.

29
The main contacts of current path are made of silver-plated copper
profiles and the contact head is equipped with silver plated fingers. When
the disconnector is closing, the middle insulator rotates 70° until the main
contacts touch each other.

During final phase of closing the current path makes a rotation


round the longitudinal axis. This movement gives the best connection of
main contacts and makes it possible to break an ice coating.

The main contacts of the disconnector in closed and opened


position are locked via a dead centre system. The HV terminals are made
according to IEC standards. The current path consists of a welded
aluminium structure with a minimum of terminal points and therefore no
appreciable change of the contact resistance over many years occurs.

The optionally available earthing unit consists of a hinged type-


earthing switch fixed at the base frame. When in the open position, the
tubular arm is located along the base frame. In closed position the earthing
switch contact attached to the head of current path comes to rest between
the contact fingers of the earthing switch, which can be mounted on both
sides of the disconnector. The universal design permits the earthing switch
to be attached at site and it can be retrofitted without any difficulty.

30
3.3.2.2 Operating Principle

The double break disconnector is


formed by three poles, operated
simultaneously either by a single operating
mechanism and mechanical linkages between
the poles or by one mechanism for each pole.

The base frame supports two


insulators and a rotating insulating rod (drive
insulator), which supports and operates the
arm.

The live part is very simple in its


design and motion. From the open position,
the arm (1) rotates to enter directly the fixed
contacts (2) at the ends of the disconnector. Fig 3.8 Operation of DBR

3.3.2.3 Technical data and specifications

The operating specifications of a double break disconnector are given


below.

VOLTAGE CURRENT STC (KA RMS/1 MOVING BLADE


or 3SECS)
(KV) (AMPS) DESIGN

Copper(12-245KV)
12 to 420KV 400 – 3150 A 12.5 - 40
Al (12-420KV)

Table No. 3.3 Operating Limits

31
The dimensional or structural
view of a DBR disconnector is
shown in fig. 3.12. The different
dimensions of a DBR
disconnector for different voltage
ratings are given the table in the
next page.

Fig 3.9 skeleton view of DBR

Dimensions
Voltage Current Short time
(KV) (amps) current(KA
A B C D
RMS 1/3 sec)
440 2000-3150 40 4510 4800 4000 3650

Table:3.4 Dimensions and rating of DBR

3.3.3 Design of Pantograph Disconnector

The Pantograph Disconnector is a divided support single column


disconnector with vertical isolating distance used in outdoor high voltage
Sub-stations. This type of disconnectors permits the design of modern
switchgear installations with minimum-space requirement.

In this type of disconnector, the fixed contact is connected to the


top bus and the moving contact is connected to the lower bus. With
pantograph principle the vertical reaching contacts of the moving contact
will make / break the circuit and hence the name Pantograph. Unlike other
disconnectors this will have different support arrangements for fixed
contact and moving contact separately.

32
Fig 3.10 Pantograph Disconnector

The pantograph disconnector helps reach higher bus-bars and


transfers the electrical energy to another set of bus-bars which are at a
lower height. This is particularly helpful because wires cannot be hanged
to connect two bus-bars at different levels. So a pantograph being a rigid
structure which can withstand heavy winds, earthquakes etc. It has arms
which are placed in cross-hair shape. They stretch out to reach the bus-
bars.

33
3.3.3.1 Basic Constructional features:

Fig 3.11 Parts of Pantograph Disconnector

The stable frame carries the constructional element of the disconnector. It


is mounted to the foundation by means of four studs (3) and supports the
support insulator (4) with intermediate piece (6), gear box (7), and the
pantograph (8), as well as the pivot bearing
(9) with the rotary insulator (5) and, if
available, the built-in earthing switch (10)
with its pivot bearing (12). The top
intermediate piece (6) is arranged between
the support insulator (4) and the gearbox (7)
with the pantograph (8). It serves as
mounting point for the bottom conductor. Fig 3.12 Turning Mechanism

34
Adaptation of the top intermediate piece to the respective installation
needs (e.g. equipment with 2 or 4 cable pulleys for straining of the cable
bus bars), helps to reduce the number of structural elements and thus the
work involved in mounting. In the case of disconnectors witch built-on
earthing switches, the earthing switch contact is attached to the top
intermediate piece.

The pantograph has the welded


aluminium construction and together
with the cast aluminium gearbox
forms a mechanical unit.

The construction guarantees the


highest possible degree of mechanical
stability and reliable current transfer
especially in case of the short circuit.
Bolt connections are generally
avoided so that operating reliability is
not impaired with time due to the
bolts working loose or by corrosion in
the joint.

Fig 3.13 housing (gear box)

To balance the weight of the pantograph, the gearbox is mounted a


counterbalance spring. Because gearbox is closed on all sides the installed
components are protected against atmospheric influences, contamination
and animals (e.g. birds, snakes) as well as their nests. On all four sides are
provided flat terminals offering universal connection possibilities. The
entire transmission system has a simple mechanical design.

All gearbox and pantograph bearings are permanently lubricated


and thus maintenance-free. Disconnectors for high short-circuit currents

35
are equipped with a damper. This damper is mounted between the
pantographs joints and is to damp the vibrations caused by the short-circuit
current in the pantograph.

The suspended contact is situated above the disconnector on the


overhead line and is grasped with a high pressure, when the pantograph is
in closed position. Current is transferred through the pantograph joints by
tapered roller contacts and further through the gearbox. These connections
have been proven correct for many years operation under extreme
conditions in wet and cold climate, and their operating durability is
considerably higher than that of the still widely used multi-strand
conductors which are more susceptible to corrosion because of their large
surface area.

3.3.3.2 Operating Principle:

All disconnectors are supplied with manual operating mechanism


or motor-operated mechanism depending on the requirement and sub-
station layout. Each pole of the disconnectors and earthing switches is
actuated by a separate operating mechanism. The base plate supports the
insulator on which the upper frame is bolted. The rotating insulating rod
(driving insulator), which operates the moving contact is directly
connected to the operating mechanism. The torque from the motor of
operating mechanism is transmitted through the operating shaft and rotary
insulator to the top bearing in the gearbox and from there to both
pantograph arms by means of operating rods.

From the open position, the insulating rod (1) rotates to move the
arms through the geared system inside the upper frame (2). The lower
arms (3) raise together and close the jaws of the upper arms (4) on the
fixed contact bar (5). After having reached the final closed position, the

36
moving part is locked by a dead-point passing, preventing any accidental
opening. The flat HV terminals (6) are made according to IEC standards.

During making or breaking, before reaching its final position the


operating lever in the gearbox travels through a dead centre position, thus
preventing the pantograph arms of the
disconnector from opening and closing
incidentally.

The contact strips on the


pantograph arms during making
operation travel through a wide reach
angle and that guarantees reliable
grasping of the suspended contact even
if its position changes considerably
due to the influence of adverse
weather conditions (e.g. strong wind).

Fig 3.14 operation of pantograph


The high contact pressure in closed position does not only assure reliable
current transfer but also reduces contact wear. Due to the scissors’ action
when making and breaking the forces acting on the contacts of the
disconnector are concentrated on a single point so that even thick layers of
ice can be easily broken and removed

The design of the disconnector prevents formation of ice block


between the pantograph and gearbox. The corona protection fittings
attached to the pantograph arms also serve as a catching device in case of
vertical movement of the suspended contact and thus preventing the
suspended contact from slipping out of the pantograph arms.

37
3.3.3.3 Technical Data and Dimensions

The operating values of a pantograph disconnector are given below:

VOLTAGE CURRENT STC (KA RMS/1 or MOVING LADE


(KV) (AMPS) 3SECS) DESIGN

123 to 1600 – 31.5 - 40 Al (12-420KV)


420KV 3150A

Table 3.5. Operating Values of Pantograph Disconnector

The basic structural drawing of a


pantograph disconnector is shown in fig.
3.15.

The dimensions of pantograph


disconnector for various voltage ratings
is shown in table 3.6 below.

Fig 3.15 Structural Diagram of PG

Dimensions (mm)
Rated Rated Short time
voltage current current (KA A B C D E
(kv) (amps) RMS 1/3 sec)
440KV 2000- 40 2760 4738 3650 3150 15600
3150

Table 3.6 Dimensions and Rating of PG disconnector

38
3.4 Earth Switch:

The use of earthing switches ensures absolute de-energisation of


high-voltage components in a circuit or switchgear. The earth switches can
be built as stand-alone or can be attached on other disconnectors.
According to the requirements, built-on earthing switches can be arranged
laterally or in inboard arrangement with respect to the position of the main
current path of the disconnector as needed. Some earthing switches are
designed for switching induced inductive and capacitive currents.

Fig 3.16 Earth Switch

39
4. CONSTRUCTION AND ASSEMBLY

4.1 Introduction

Disconnector is a device used in the transmission and grid


substations for the purpose of disconnecting the power source either for
maintenance purpose or for bus transfer. Disconnector functions as
continuous current carrying device to the other connected equipments such
as Circuit Breaker, CT's, PT's etc from the main busbar in each of the bay
in a sub-station. These are used primarily for the isolating of equipment
and sectionalizing electric circuit or even portion of main feeders for
special purposes, such as testing and maintenance. Generally these devices
are not rated to make or break load.

4.1.1 Major Parts of Disconnectors

• Main-contacts/current path assembly

The disconnectors are provided with current carrying contacts


which are designed and tested for rated currents. The entire contact surface
is silver plated. The design of contacts is such that they are self-aligning
and self-cleaning during the operation.

The material can be either copper/aluminium. To maintain the


constant pressure, springs are used in the design. However these springs do
not carry current and do not loose their characteristics due to heating
effects.

• Base frame/base channel assembly

Each pole of the disconnector shall be provided with a complete


fabrication and galvanized steel base provided with holes and designed for

40
mounting on a supporting structure. The base frame also consists of the
rotating stool base guided by bearings/bushings to mount the insulators.

• Insulators

The insulator unit / stack is designed for sufficient insulation level


and according to the rating of the disconnector. They are installed over the
base frame to support the main contact assembly.

• Operating mechanisms (motor drive / manual drive)

The operating mechanism is used for close / open operation of the


disconnector / earth switch from the ground level. The equipment can be
provided with motor or manual operating mechanism boxes. The down
operating pipe, top operating mechanism (TOM), push pipes are the
mechanical linkages employed in the design to transfer the motion from
the drive mechanism to main contacts.

• Earth switch

The disconnector can also be provided with its associated earth


switch. The earth switch can be placed only on one side of the
disconnector terminals called as with one earth switch, both sides of the
disconnector terminals called as with two earth switches and for some
disconnectors the earth switch need not be provided based on its
application. Independent operating mechanism will be provided for the
operation of earth switch.

The earth switch alone without the association of disconnector is


also required in some cases as bus-earth switch / maintenance earthing
switch.

41
4.2 Construction and Assembly of Horizontal Centre
Break Disconnector

The constructional features of a horizontal centre break disconnector are


explained below.

• Hamper Assembly

• Support Insulator

• Disconnector Base

• Inter Stack Coupling Pipes

• Phase Coupling Pipes

• Support Structure

• Operating Mechanism

• Interlocks

4.2.1 Hamper assembly

The Hamper assembly consists of two moving arms called the


male and female arms, each mounted onto the top of the rotating support
insulators. The arms are made out of tubular or channel sections of
aluminium alloy depending on the current and voltage ratings of the
disconnectors. The male copper contact and female copper contact fingers
are silver plated and mounted onto the arms.

The male and female hamper assemblies are connected to the


terminal stem by using multiple, flexible copper strips for the safe transfer
of current from the moving arm to the fixed terminal stem of the

42
disconnector. The copper flexible is bolted firmly at one end to the rotating
arm and at the other end of the terminal stem.

The contact between the male and female contact is a line contact
and the contacts provided are of the reverse loop type. Each contact finger
is provided with a contact spring which, ensures that the required pressure
of approximately nine kgs. per pair of fingers is maintained.

The terminal stem onto which the terminal connector is fixed is


made of aluminium alloy for 420kV, 2500A disconnectors & 245kV,
2500A disconnectors; and of copper for all 245kV and below
Disconnectors up to 2000A. For 3150A rated disconnectors, only copper
terminal stems are used, and wherever the copper terminals are provided
the terminals are tin plated for connection to aluminium alloy terminal
connectors. Contact corona rings are provided at the male and female
hampers wherever necessary.

4.2.2 Support Insulators

The support insulators in the case of the centre break


disconnectors are used to support metallic hampers of the disconnectors
and to rotate through 90 degrees to open and close the disconnectors, to
provide necessary insulation between live parts and ground. Insulator
corona rings are provided on the insulators wherever necessary.

4.2.3 Disconnector Base

Disconnector base is made out of welded assembly. The base


consists of two flanges at either ends for mounting the support insulators.
These flanges are provided with the necessary holes at the required pitch
circle diameter to match the holes provided on the base flange of the
insulator.

43
The flanges are welded on the bearing shaft and are assembled
with two numbers taper roller bearings, Ball bearings with Al casting.
These taper roller bearings are seated one on the top and one on the bottom
of the base assembly and these ensure free and smooth movement of
disconnector arms. Bearing covers are provided to ensure that water and
dust do not enter the bearings. Provision is made at the two ends of the
bases to mount earth switches if required. Provision is also made on the
base for mounting the mechanical constructional interlock between
disconnector and earth switch wherever required.

The base is provided with mounting arrangement at two points for


fixing the disconnector base with the supporting structure. Earthing pad /
earthing studs are provided at two points at the extreme ends of the base
for connecting to the sub-station earthing system.

4.2.4 Inter Stack Coupling Pipes

Inter stack coupling pipes are provided to couple the two columns
on the same phase of disconnector so as to ensure simultaneous rotation of
the two poles columns driven by the common operating mechanism. The
coupling pipes are linked to the base flange on which the insulator is
mounted by metallic pin to ensure easy assembly / dismantling at site.
Normally the inter pole coupling pipes are assembled on to the base and
set at factory prior to dispatch from works.

4.2.5 Phase Coupling Pipes

Inter Phase coupling pipes are provided to couple the three phases
of the Disconnector and operate all the three phases from a common
operating mechanism in the case of Mechanically Ganged three pole
Disconnectors. These are not required in the case of single pole
Disconnectors where each pole is operated by its own operating

44
mechanism. The coupling pipes are linked to one base flange on each
phase of the three pole disconnector. These are dispatched loose and are to
be assembled at site. Provision is available to do minor adjustments in
length of the coupling pipe to suit site conditions.

4.2.6 Support Structure

Wherever specified, support structure of tubular types for 400kV


disconnector with necessary foundation bolts can be supplied. Plates are
welded on to this tubular support structure fabricated out of welded sheet
steel for 400kV Disconnectors for mounting the operating mechanism
boxes, the operating mechanisms of the disconnectors / earth switches are
mounted on to the structure on plates provided, being bolted with the
angles that are provided on the mechanism box. The height of this support
structure can be varied to accommodate the bus height as required by the
sub-station layout and system.

4.2.7 Operating mechanism

Motor Operating mechanism or manual Operating Mechanisms


are used.

4.2.8 Interlocks

A Mechanical constructional interlock between the disconnector


and earth switch is used to ensure that the Earth Switch can be closed only
when the Disconnector is in the open position and vive versa. An electro-
mechanical bolt coil type interlock is used in each motor operating
mechanism for interlocking between manual and motor operation of
Disconnector / Earth switch. This ensures that the motor circuit is cut off
when the manual operation is under progress. In some cases, only
electrical bolt coils are provided as interlocks solely controlled by
electrical circuits.

45
4.3 Construction and Assembly of Double Break
Disconnector

• Rotating Hamper Assembly

• Fixed Contact Assemblies

• Support Insulators

• Disconnector Base

• Inter Phase Coupling Pipes

• Support Structure

• Operating Mechanism

• Interlocks

4.3.1 Rotating Hamper Assembly

The rotating hamper assembly consists of a tubular section of


aluminium alloy of adequate cross-section clamped at the centre point. It
rotates through 110 º for the closing /opening operation of the
disconnector. The size of the aluminium alloy tube and its thickness is
selected based on the continuous and short time current carrying capacity
of the required disconnector. Silver plated copper contacts are fixed on to
this rotating aluminium alloy blade at either ends.

Double Break Disconnectors are of a special design, having a turn


and twist feature. In this design, the disconnector blade first moves in the
horizontal plane until it touches a stopper on the fixed contact, then the
tubular blade itself rotates giving a twisting motion. Only during this
twisting movement, the contacts mounted on the moving blade actually
make contact with the fingers on the fixed contact assembly. This rotating

46
motion of the blades ensures that adequate contact pressure is built up
between the fixed and moving contacts for carrying the rated currents.

This design also has a further advantage that during the closing
operation of the disconnector, the actual current carrying surfaces do not
come into the contact till the twisting motion occurs, thereby ensuring that
there will not be any damage to the surfaces of the contacts during the
closing of disconnector. The contacts are of the self wiping nature and
clean the contact surfaces while closing and opening of Disconnector.
This type of contact arrangement is called the pressure relieving reverse
loop type.

The moving aluminium alloy blades are clamped onto the turn and
twist mechanism which is housed in an aluminium housing for 420kV and
245kV Disconnectors. The turn and twist mechanism flange is then
mounted on to top flange of the centre insulator of each pole.

4.3.2 Fixed Contact Assemblies

Each pole of the Disconnector consists of two fixed contact


assemblies. The fixed contact assembly consists of a housing onto which
the silver plated copper contact fingers are mounted. Each contact finger is
provided with a compression spring to ensure that the required contact
pressure is maintained. The fixed contact assembly also consists of a
terminal pad. The terminal connector is fixed onto this terminal pad on
four holes provided thereon.

4.3.3 Support Insulators

The Double Break Disconnector consists of three stacks of support


insulators per pole or 9 stacks per 3 pole disconnector. Out of the three
insulators per pole, the outer two insulators are stationary and centre
insulator rotates through 110 degrees for closing / opening of the

47
Disconnector. Due to this reason, this type of Disconnector is also referred
to as the Double Break Centre post Rotating type disconnector.

The fixed contact assemblies are mounted on top of the outer


stacks of insulator which are stationary and the turn and twist mechanism
along with the rotating hamper assembly is mounted on the centre stack of
insulator.

The function of the outer stack of insulator is to keep the fixed


contacts rigid, provide the necessary creepage distance and the insulation
between the live parts and ground. The function of the center stack of the
insulator is to rotate though 110° and provide the necessary creepage
distance and also the insulation between line parts and ground.

4.3.4 Disconnector Base

Disconnector base is made of welded assembly. The base consists


of three flanges, two at either ends or one at the centre for mounting the
support insulators. These flanges are provided with the necessary holes at
the required pitch circle diameter to match with the holes provided on the
insulator base flange. The two end flanges are welded on to the base of the
disconnector adaptors. The center flange is welded to the bearing shaft.
The bearing shaft is assembled with two numbers taper roller bearings,
aluminium bearing housing. These bearings are seated one on top and
another on bottom of the base assembly and these ensure smooth and free
movement of the Centre rotating post of the disconnectors. Bearing caps
are provided to ensure that water and dust do not enter the bearings.
Provision is made on the base for mounting the mechanical constructional
interlock between disconnector and earth switch wherever required. The
base is provided with mounting arrangements at four / eight points for
fixing the disconnector base the supporting structure. Earthing pad /

48
earthing studs are provided at two points at the extreme ends of the base
for connecting to the sub-station earthing systems.

4.3.5 Inter Phase Coupling Pipes

Inter Phase coupling pipes are provided to couple the three phases
of the Disconnector and operate all the three phases from a common
operating mechanism in the case of Mechanically-Ganged three pole
Disconnectors. These are not required in the case of single pole
Disconnectors where each pole is operated by its own operating
mechanism. The coupling pipes are linked to one base flange on each
phase of the three pole disconnector.

4.3.6 Support Structure

Wherever required, support structure of tubular types for 400kV


disconnector with necessary foundation are used. Plates are welded on to
this tubular support structure fabricated out of welded sheet steel for
400kV Disconnectors for mounting the operating mechanism boxes, the
operating mechanisms of the disconnectors / earth switches are mounted
on to the structure on plates provided, being bolted with the angles, that
are provided on the mechanism box. The height of this support structure
can be varied to accommodate the bus height as required by the sub-station
layout and system.

4.3.7 Operating Mechanism

Motor Operating mechanism or manual Operating Mechanisms are used.

4.3.8 Interlocks

A mechanical constructional interlock between the disconnector


and earth switch has been provided to ensure that the Earth Switch can be
closed only when the Disconnector is in the open position and vive versa.

49
An electro-mechanical castle key type interlock is used in each
motor operating mechanism for interlocking between manual and motor
operation of Disconnector / Earth switch. This ensures that the motor
circuit is cut off when the manual operation is under progress. In some
cases, only electrical bolt coils are provided as interlocks solely controlled
by electrical circuits.

4.4 Construction and Assembly of Pantograph Disconnector

• Trapeze contact

• Scissor Assembly

• Main Frame Assembly

• Support Insulator

• Operating Rod Insulator

• Support Structure

• Operating Mechanism

• Interlocks

4.4.1 Trapeze Contact

The trapeze contact consists of a silver plated copper tube


suspended by adjustable dropper rods, quadruple or twin spacers, which
are connected to upper quadruple or twin ACSR conductor bus. The
complete assembly of sets of spacers, two Aluminium dropper rods and
one silver plated copper tube totally form the Trapeze contact of
Pantograph Disconnector.

50
4.4.2 Scissor Assembly

The scissor assembly contains the four point contacts of silver


plated copper which makes contact with the suspended copper tube of this
trapeze assembly. The copper contacts are mounted on the Aluminium
alloy extrusions assembled in the form of a scissor. Current transfer
contacts are provided at the joints to ensure smooth transfer of current
from one moving part to the adjacent part. The scissor arms on one side
have counter balance springs to ensure smooth operations. Current transfer
contact consists of a male copper contact on one side and female contact
finger assembly on the opposite side. Corona rings are provided on the
scissor assembly at the upper contact point and also at the joints in the
scissor assembly.

4.4.3 Main Frame Assembly

Main Frame assembly consists of the main frame of the


Pantograph Disconnector on which the pantograph scissor are mounted.
This assembly also has the terminal pad at either end for connecting the
terminal connectors. The terminal pad is a plate of aluminium alloy with
four holes drilled on it for fixing the terminal connector. The main frame
assembly also has the base plate for mounting it on top of the solid core
support insulator. It also houses the bell Crank and levers connected to the
down operating rod insulator for the operation of the Disconnector.

4.4.4 Support Insulator

The support insulator is a soil core insulator which is primarily


used to support the metallic pole of the Pantograph Disconnector and also
to provide the required insulation between the live parts and ground. An
insulator corona ring is provided on top of the insulator. The lower portion
of the support Insulator is mounted on to the support structure column.

51
4.4.5 Operating Rod Insulator

While the support insulator explained earlier gives the necessary


rigid support for the metallic part (main frame assembly and scissors), the
operating rod insulator is used primarily for operating the pantograph
scissors and for providing insulation for the person operating the
Pantograph. The upper end of the insulator is connected to a bell crank for
operating the disconnector and the lower end is connected to the operating
mechanism through a down operating pipe.

4.4.6 Support Structure

Wherever required, support structure of tubular types with


necessary foundation bolts can be used. Plates are welded on to this
tubular support structure fabricated out of welded sheet steel for mounting
the operating mechanism boxes. Operating mechanism is mounted on to
the structure on three plates being bolted with three angles provided on the
mechanism box.The height of this support structure can be varied to
accommodate the height of Upper and Lower bus heights as required by
the sub-station layout and system.

4.4.7 Operating mechanism

Motor Operating mechanism or manual Operating Mechanisms


are used.

4.4.8 Interlocks

A Mechanical constructional interlock between the Main and


earth switch is used. An electro-mechanical castle key type interlock
between Disconnector and earth switch where earth switch is specified.
Electro mechanical castle Key Interlock is used in between electrical and
manual operation in motor operating mechanism.

52
5. OPERATING MECHANISM AND TESTING

5.1 Introduction

We have seen in earlier chapters that a disconnector is used to


open a circuit and disconnect a sub-station from main power supply. It is
achieved by using a proper operating mechanism to help it move from
close to open or vice-versa. The operating mechanism is installed in a box
of the main disconnector main blade which is connected by means of a
operating down pipe.

Without a properly functioning operating mechanism, a


disconnector cannot disconnect a circuit and it would be a drastic failure
and it will be deemed a big failure. So, the operating mechanism is the
heart of a disconnector. The disconnectors functionality depends on the
operating mechanism.

5.2 Types of operating mechanisms

The Disconnectors and Earthing switches are operated with the following
Operating Mechanisms:

• Manual operating mechanism

• Manual with gear mechanism

• Motor operating mechanism

5.2.1 Manual Operating Mechanism

The manual operating mechanism is provided with a handle to


operate the disconnector / earthing switch. Locking is done in both the
close and open conditions, i.e. to open a disconnector, a person has to go
to the operating mechanism box to manually open the disconnector.

53
Interlocking is done mechanically and auxiliary switches are used
for position indication and interlocking indication. This system is used for
lower voltage systems and is never used for a system of voltage rating
higher than 33KV.

5.2.2 Manual with gear operating mechanism

The manual with gear operating mechanism is provided with


worm and worm gear to achieve smooth operation and self locking of the
mechanism. This gear mechanism helps the operator so that a lesser
physical force is required to move the disconnector. Mechanical
interlocking mechanism is used. Auxiliary contacts for position indication
and interlocking with other equipments are housed in the operating
mechanism.

5.2.3 Motor Operated Mechanism (MOM)

This operating employs a motor to rotate or turn or move a


disconnector. The motor is placed inside the operating mechanism box.

Generally, a motor rotates at 1100 rpm. But a disconnector is


moved at 2 rpm. So in order to step down the rpm, we use a reduction gear
system. Therefore, the motor operating mechanism is provided with
double stage reduction gear system i.e. spur gears at first stage and worm
gear at second stage to achieve smooth operation and self locking of the
mechanism.

The gear can be operated by three phase AC Induction motors or


Permanent Magnet DC motors, though an induction motor is widely used.
Suitable thermal overload relays are provided to protect the motor from
overload.

54
Auxiliary contacts for position indication and interlocking with
other equipments are housed in the operating mechanism. If required make
before break (MBB) contacts can also be fitted with the auxiliary contact.
MBB is a type of contact arrangement of an electrical switch, which
ensures that when a switch transition happens, the new contact is always
made before the old one is broken.

FIG 5.1 MOTOR OPERATING MECHANISM(MOM) BOX

The figure 5.1 shows a typical MOM box. The various parts of MOM is
given below:

1. AC (Induction) motor or DC motor (permanent magnet)

2. Reduction Gear box

3. Auxiliary switch

4. Contactors

55
5. Terminals

6. Start and Stop buttons

7. Selector Switch

8. Castle key interlock

The operating mechanism box conforms to IP 55 standard which


makes it dust and water proof. There is provision for heat sensor and
heater to keep the temperature constant.

The figure 5.2 shows a circuit diagram of motor operating mechanism.

FIG 5.2 CIRCUIT DIAGRAM OF MOM BOX

56
5.2.3.1 Ganging

Ganging is operating a set of disconnectors at the same time, i.e.


in a 3-phase disconnector system, the three disconnectors of three phases
are operated from the motor operating box.

In motor operated disconnectors, ganging is very common. Ganging can be


established in two ways.

• Mechanical Ganging

• Electrical Ganging

Mechanical Ganging:

All poles of the disconnector / earthing switch are coupled together


by means of mechanical linkages and one common operating mechanism
may be motor / manual is employed to operate the whole equipment. This
method of operation is called as mechanical ganging. The linkage device is
a tandem pipe.

Electrical Ganging:

In this case each pole of the disconnector / earth switch is


provided with independent motor operating mechanism. Out of which one
MOM will act like master control and the rest be follower controls. All the
poles of the switch can be operated simultaneously from the master control
cubicle. However, independent operation of each pole is also possible from
their respective motor operated mechanism (MOM) boxes, keeping the
gang selector switch in independent mode.

57
5.2.3.2 Interlocking

Interlocking is the mechanism which prevents the simultaneous operation


of earth switch and the disconnector switch. Similar to ganging, there are
two ways implement interlocking.

• Electrical Interlocking

• Mechanical Interlocking

Electrical Interlocking:

Electrical interlocking is done by connecting the auxiliary contacts


of various equipments in series to the control circuit of the present switch,
to enable the motor / manual operation only when all interlocking
requirements are fulfilling. To operate the disconnector manually, the
selector switch has to be set to manual position and then the solenoid
interlocking is disabled by a key interlock and then a crank handle is used
to operate the disconnector.

Mechanical Interlocking:

Mechanical interlocking is done by interdependent groove-cam


and projected shaft arrangement to block mal-operation of disconnector
and earthing switch simultaneously and also to have safety even in cases of
failure in electrical interlocking. Interlocking cams are fitted with TOM of
main switch and earth switch. Interlocking shaft/rod with threading on
both ends are given to allow the increase and decrease of rod length,
thereby allowing proper and 100% entry in the interlocking groove.

5.3 TESTING:
With so many electrical product safety standards currently in use
and many civil and legal actions pending in various courts around the

58
world, electrical safety testing is more critical than ever to ensure that all
products are safe before they reach the user. Fortunately, the majority of
manufacturers are fully aware of the hazards associated with electrical
equipment and the ramifications of non-compliance with relevant safety
standards or test house agreements.

Electrical safety tests can be roughly divided into two areas:

• Type tests or Conformance tests

• Routine Production tests or Routine tests

Those tests that are carried out during the approvals process by test
houses are known as type tests and those that are carried out at the end of
each production line by the manufacturer are known as routine production
tests.

For type tests, a product is subjected to tests and evaluations in


accordance with a specific product safety standard. For production tests, a
manufacturer can select a few tests, ensuring that each product is subjected
to those tests in accordance with its own procedures. Most manufacturers
choose four primary product safety tests to be routine at the end of the
production line. These include power frequency voltage test, main circuit
resistance, mechanical operation, and visual & dimensional check.

These tests are designed to ensure that the user does not get
electrocuted or otherwise hurt by operating a piece of equipment that has
hazardous voltages or high fault current as a result of electrical fault. This
chapter looks at the fundamentals behind each test and analyzes the
reasoning behind each test, as well as discussing appropriate limits and
equipment.

59
5.4 Type Tests

Conformance testing or type testing is testing to determine


whether a product or system meets some specified standard that has been
developed for efficiency or interoperability.

To aid in this, many test procedures and test setups have been
developed, either by the standard's maintainers or external organizations,
specifically for testing conformance to standards. Conformance testing is
often performed by external organizations, which is sometimes the
standards body itself, to give greater guarantees of compliance. Products
tested in such a manner are then advertised as being certified by that
external organization as complying with the standard. Service providers,
equipment manufacturers, and equipment suppliers rely on this data to
ensure Quality of Service (QoS) through this conformance process.

In electrical engineering, some countries and business


environments require that a product meet certain requirements before it
can be sold. Standards for electrical products written by standards
organizations such as IEEE, IEC, and IS, etc., have certain criteria that a
product must meet before compliance is recognized. In countries such as
Japan, China, Korea, and some parts of Europe, products cannot be sold
unless they are known to meet those requirements specified in the
standards.

Usually, manufacturers set their own requirements to ensure


product quality, sometimes with levels much higher than what the
governing bodies require. Failure levels are usually set depending on what
environment the product will be sold in. For instance, test on a product for
used in an industrial environment will not be as stringent as a product used
in a residential area. A failure can include insulation breakdown, arc
formation, and irregular behavior.

60
There are three main types of compliance test for electrical
services; emissions tests, immunity tests, and safety tests. Emissions tests
ensure that a product will not emit harmful interference by electromagnetic
radiation and/or electrical signals in communication systems. Immunity
tests ensure that a product is immune to common radio signals and
Electromagnetic interference (EMI) that will be found in its operating
environment, such as electromagnetic radiation from a local radio station
or interference from nearby products.

Safety tests ensure that a product will not create a safety risk from
situations such as a failed or shorted power supply, blocked cooling vent,
and power line voltage spikes and dips. A disconnector being an electrical
product is also subjected to many various compliance tests.

The various tests conducted are listed below

• Di-electric tests

- Power Frequency withstand voltage tests

- Lightning Impulse withstand voltage test

- Switching Impulse withstand voltage test

• Radio Interference Voltage test

• Corona inception and extinction test

• Measurement of resistance of main circuit

• Temperature rise test on main contacts

• Short time current and peak withstand current tests

• Mechanical Endurance & Terminal load test

• Verification for protection – IP 55 on ‘MOM/BOM’.

61
6. CONCLUSION

This study project discusses about High Voltage Disconnectors or simply


Disconnectors. Disconnectors are non-load switching devices which
disconnect a sub station from a power source for the sake of maintenance
and repair. When they are in closed position, they act as current carrying
devices and have to withstand heavy currents.

The project also covers the three types of disconnectors. They are
horizontal centre break disconnector, double-break disconnectors,
pantograph disconnector. The design, constructional features, assembly,
operation, testing of 440 kV disconnectors have been discussed in detail,
concentrating heavily on horizontal centre break disconnector, double
break disconnectors, and pantograph disconnectors which are widely used
in 440 kV power system.

During the course of this project, a deep insight into the types of
disconnectors are studied in detail and types of tests conducted on
disconnectors are mentioned.

We sincerely thank Siemens Ltd. (Hyderabad works) for giving us this


opportunity to do a mini-project in their company and we are proud to say
that we have found this industrial oriented mini-project was really useful
to get acquainted with various industrial processes, equipment involved in
manufacturing, different designs and testing techniques.

62
BIBLIOGRAPHY

1. Power Systems by J.B. Gupta.


2. High Voltage Engineering Fundamentals 2nd edition by E. Kuffel,
W.S. Zaengl, J. Kuffel.
3. IEC 600694 Common specifications of High Voltage Switchgear
and Protection.
4. IEC 60060 – 1 High Voltage Dielectric Tests.
5. IEC 62271 – 102 High voltage alternating current circuit breakers.

63

You might also like