Purdue University Project: C.40.11905 GMP3 Schleman Hall - GMP 3
2550 Northwestern Avenue, Suite 1100
West Lafayette, Indiana 47906
P: (765) 494-0580
RFI #150: iGMP3 - SCHL - 4" Waste Main Serving 3106 & 2106 Connection Point
Not Correct Size
Status Open
Linked Drawings
Copies To Jeff Bogle (MSKTD & Associates, Inc.), Rick Dahlstrom (MSKTD & Associates, Inc.), Rustin R Meister (Purdue University),
Purdue PFPMC (Purdue University), Dane Smith (F.A. Wilhelm Construction Co., Inc.), Jim Stanich (F.A. Wilhelm Construction
Co., Inc.), Amogh Swamy (F.A. Wilhelm Construction Co., Inc.), Aaron Tague (F.A. Wilhelm Construction Co., Inc.), Gavin
Wanstreet (F.A. Wilhelm Construction Co., Inc.), Lisa Warren (MSKTD & Associates, Inc.), Joe Wilhelm (F.A. Wilhelm
Construction Co., Inc.)
Activity
Question Question from Dane Smith F.A. Wilhelm Construction Co., Inc. on Tuesday, Mar 7, 2023 at 05:43 PM EST
Drawing P302 shows the new 4" waste main connecting to an existing 4" waste line in room 1100. There is not a 4" waste line
to connect to in room 1100. Wilhelm demolition opened the wall up and have confirmed that there is a 4" galvanized waste
riser inside of the chase on the west side of 1100.
We suggest to open the chase wall and cut a combo into the existing waste main to connect the new 4" waste main from 2106
and 3106. This will have added cost.
Attachments
RFI-150-iGMP3-SCHL- 4 Waste Main Serving 3106 and 2106 Connection Point Not Correct Size.pdf
Awaiting an Official Response
Purdue University Page 1 of 1 Printed On: Mar 8, 2023 09:16 AM EST
RFI
Purdue Schleman Hall QPH Job #: 22773
475 West Stadium Ave GC Job #: XXXXX
West Lafayette,IN 47907
To: F.A. Wilhelm Constuction, INC From: Quality Plumbing & Heating
3914 Prospect Street 3515 North Reed Road
Indianapolis IN 46206 Kokomo, Indiana, 46901
Subject: 4" waste main serviving 3106 and 2106 connection point not correct size
Question:
Drawing P302 shows the new 4" waste main connecting to an existing 4" waste line in room 1100. There is no 4" waste line
to connet to in room 1100. I had Wilhem demo open the wall up, and have confirmed that there is a 4" galvanized waste
riser inside of the chase on the west side of 1100.
Suggestion:
Open the chase wall up, and cut a combo into the existing waste main to connect the new 4" waste main from 2106 and
3106. This will have an added cost
CC: GC
PM - QPH
Jobsite
File
0
1715 Magnavox Way 930 North Meridian
Fort Wayne, IN 46804 Indianapolis, IN 46204
260.432.9337 317.917.1190
www.msktd.com
1" CW
6" ST
COLLABORATION VESTIBULE STORAGE TOILET GROUP WORK 9. 1"HWR FROM ABOVE AND DOWN.
FD-1
1080 1H04 1089 1097 1119B 10. 2"W FROM ABOVE.
13 11
11. HWR BALANCING STATION, SEE DETAIL.
L-2
SKYPE 12. 1"CW DROP INSTALL "WHA-A", 4"W DOWN AND 2"V RISE. P501
S-1 1107 13. 3/4"HW AND 3/4"CW DROP EXTEND TO LAV AND SINK.
14 14. 1/2"W DOWN AND 1 1/2"V RISE.
15. 4"W FROM ABOVE.
1 1/4" CW OFFICE 16. 2"W SERVINIG FD ABOVE.
STAIR 3/4" HW This 4" stub coming 17. EXISTING WALL HYDRANT SHALL REMAIN IN SERVICE.
1119G 1
1S03 18. 2"W DOWN AND TEST TEE CLEANOUT.
CO HALLWAY 3" V EX 4"W out of the wall doesn't 19. EXISTING 2"W SERVING FD ABOVE SHALL REMAIN.
6" ST CO exist.INFORMAL
There is a 2"
3/4" HWR
CO 2" W 1H05B 20. 2"V FROM BELOW CONNECT TO EXISTING V UP.
9 CO stub coming
MEETING off of the
2" W
21. 1 1/4" NON-POPTABLE CW FROM BELOW.
18
1 1/4" CW 4 5
GROUP WORK
1100
vent stack.
1104 16 22. 4"ST FROM DECK DRAIN ABOVE. 8/10/22
VESTIBLE 3/4" HW
STAIR 1H05I
COLLOQUIUM 3" V OFFICE
6"ST FROM CAP 4" W CO 1119H
1069
ABOVE HALLWAY
L-1 L-1 1H05D
11 15
UR-2 19 MEN
1094
UR-1 6
2" W
WAR ROOM
1012 ELEVATOR
BE02 WC-2 STAIR
EWC-2 1S04 VESTIBULE
EAST STAIR 1H03
AV ROOM STORAGE 1 1S02
8 1069B 1069A
RFI 113 10
3
RAMP
1H05G
ELECTRICAL WC-2
EX 3/4"CW
OFFICE
1025G OFFICE SKYPE
1139J 1139D
RFI 125
4" ST
4" ST
SEMINAR ROOM
Purdue University
1004
3
2.3
2
EX 4"ST
7779 08/10/2022
1 REV. DATE
1 Addendum D-2 7/12/2022
2"
F E.5
E.4 E D C B A
1"
SET DESCRIPTION
0
Final Construction
ORIGINAL SHEET SIZE IS 30"x42" (ARCH E1)
Documents
AESI Proj. No:
SHEET TITLE
SHEET NUMBER
P302