1. The number of turns on the primary and secondary windings of a 1-f


transformer are 350 and 35 respectively. If the primary is connected to
a 2.2 kV, 50-Hz supply, determine the secondary voltage on no-load.
[220 V]

GIVEN:
N1 = 350 turns E1 = 2.2 kV / 2200 V
N2 = 35 turns E2 = ?
f = 50 Hz

SOLUTION:
N 1 35 1
K= = =
N 2 350 10

E1
K= ; E =E1 K
E2 2
1
E2=2200 V ( )
10
E2=220 V

2. A 3000/200-V, 50-Hz, 1-phase transformer is built on a core having an


effective cross-sectional area of 150 cm2 and has 80 turns in the low-
voltage winding. Calculate
(a) the value of the maximum flux density in the core
(b) the number of turns in the high-voltage winding.
[(a) 0.75 Wb/m2 (b)
1200]

GIVEN:
E1 = 3000 V a = 150 cm2
E2 = 200 V Bmax = ?
N2 = 80 turns N1 = ?
f = 50 Hz

SOLUTION:
E2=4.44 ∅max f N 2
200 V =4.44 ∅max ( 50 Hz ) (80)

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
∅max =0.0112 Wb

∅max
a. B max=
a
0.0112 Wb
B max=
150 cm2
Wb
B max=0.000075 2
cm
Wb
B max=0.75 2
m

1 E
b. N 1= E x N 2
2
3000V
N 1= (80)
200V
N 1=1200 turns

3. A 3,300/230-V, 50-Hz, 1-phase transformer is to be worked at a


maximum flux density of 1.2 Wb/m2 in the core. The effective cross-
sectional area of the transformer core is 150 cm2. Calculate suitable
values of primary and secondary turns.
[830; 58]

GIVEN:
E1 = 3300 V a = 150 cm2 / 1.5 m2
E2 = 230 V N1 = ?
f = 50 Hz N2 = ?
Bmax = 1.2 Wb/m2

SOLUTION:
∅max
 B max=
a
Wb ∅
1.2 2 = max 2
m 1.5 m
∅max =1.8 Wb

 E1=4.44 ∅max f N 1
3300 V =4.44 (1.8) ( 50 Hz x 10−3 ) (N 1 )
N 1=825.83 turns

 E2=4.44 ∅max f N 2

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
230 V =4.44(1.8) ( 50 Hz x 10−3 ) (N 2)
N 2=57.56 turns

4. A 40-kVA, 3,300/240-V, 50 Hz, 1-phase transformer has 660 turns on


the primary. Determine
(a) the number of turns on the secondary
(b) the maximum value of flux in the core
(c) the approximate value of primary and secondary full-load currents.
Internal drops in the windings are to be ignored.
[(a) 48 (b) 22.5 mWb (c) 12.1 A;
166.7 A]

GIVEN:
V1 = 3300 V N2 = ?
V2 = 240 V ∅ =?
max
f = 50 Hz Ip = ?
VA = 40 Kva Is =?
N1 = 660 turns

SOLUTION:

N1 V1
a. =
N2 V2
660 3300
=
N 2 240
N 2=48turns

b. E2=4.44 ∅max f N 2
240 V =4.44 ∅max ( 50 Hz ) (48)
∅max =22.5 mWb

VA
c. I p = V
1
40 x 103
I p=
3300
I p =12.1 A

VA
I p=
V2
40 x 103
I p=
240
I p =166.7 A

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
5. A double-wound, 1-phase transformer is required to step down from
1900 V to 240 V, 50-Hz. It is to have 1.5 V per turn. Calculate the
required number of turns on the primary and secondary windings
respectively.
The peak value of flux density is required to be not more than 1.2
Wb/m2. Calculate the required cross-sectional area of the steel core. If
the output is 10 kVA, calculate the secondary current.
[1,267; 160; 56.4 cm2;
41.75 A]

GIVEN:

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
6. The no-load voltage ratio in a 1-phase, 50-Hz, core-type transformer is
1,200/440. Find the number of turns in each winding if the maximum
flux is to be 0.075 Wb. [24
and 74 turns]

GIVEN:
E1 = 1200 V ∅ max = 0.075 Wb
E2 = 440 V N1 = ?
f = 50 Hz N2 = ?

SOLUTION:
 E1=4.44 ∅max f N 1
1200V =4.44 ( 0.075 ) (50 Hz ) (N 1)
N 1=72 turns

 E2=4.44 ∅max f N 2
44 0V =4.44 (0.075) (50 Hz ) ( N 2)
N 2=26 turns

7. A 1-phase transformer has 500 primary and 1200 secondary


turns. The net cross-sectional area of the core is 75 cm2. If the primary
winding be connected to a 400-V, 50 Hz supply, calculate.
(i) the peak value of flux density in the core and (ii) voltage induced in
the secondary winding. [0.48
Wb/m2; 60 V]

GIVEN:
N1 = 500 turns a = 75 cm2
N2 = 1200 turns Bmax = ?
f = 50 Hz V2 = ?
V1 = 400 V

SOLUTION:
1 V
i. B max= 4.44 f N a
1
400 V
B max=
4.44(50 x 10−2)(1200)(0.75)
Wb
B max=0.48 2
m

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
N1 V1
ii. =
N2 V2
500 400V
=
1200 V2
V 2=960 V

8. A 10-kVA, 1-phase transformer has a turn ratio of 300/23. The


primary is connected to a 1500-V, 60 Hz supply. Find the secondary
volts on open-circuit and the approximate values of the currents in the
two windings on full-load. Find also the maximum value of the flux.
[115 V; 6.67 A; 87
A; 11.75 mWb]

GIVEN:

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
9. A 100-kVA, 3300/400-V, 50 Hz, 1 phase transformer has 110 turns
on the secondary. Calculate the approximate values of the primary and
secondary full-load currents, the maximum value of flux in the core and
the number of primary turns. [30.3 A; 250 A; 16.4
mWb; 907]

GIVEN:
VA = 100 kVA Ip = ?
V1 = 3300 V Is = ?
V2 = 400 V ∅ =?
max
f = 50 Hz N1 = ?
N2 = 110 turns

SOLUTION:
VA
 I p=
V1
100 x 10 3
I p=
3300 V
I p =30.3 A

VA
 I s=
V2
100 x 103
I s=
4 00 V
I s=250 A

V 1 N1
 =
V 2 N2
3300 N 1
=
400 110
N 2=907 turns

10. The no-load current of a transformer is 5.0 A at 0.3 power factor


when supplied at 230-V, 50-Hz. The number of turns on the primary
winding is 200. Calculate (i) the maximum value of flux in the core (ii)
the core loss (iii) the magnetising current.
[5.18 mWb; 345 W; 4.77 A]

GIVEN:
Io = 5.0 A f = 50 Hz Im = ?

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
cos ∅ o = 0.3 N1 = 200 turns
Ic = ?

= cos-1(0.3) = 72.54o
o ∅ max =?
V = 230 V
SOLUTION:

i. E1=4.44 ∅max f N 1
23 0 V =4.44 ∅max ( 50 x 10−3 ) (200)
∅max =5.18 mWb

ii. I m=I o sin (θo )


I m=5.0 sin(72.54 ° )
I m=4.77 A

θo
iii. ( ¿)
I c =I o cos ¿
72.54 °
(¿)
I c =5.0 cos ¿
I c =1.5002 A

W =I c V
W =(1.5002 A)( 230V )
W =345Watts

11. The no-load current of a transformer is 15 at a power factor of 0.2


when connected to a 460-V, 50-Hz supply. If the primary winding has
550 turns, calculate:
(a) the magnetising component of no-load current
(b) the iron loss
(c) the maximum value of the flux in the core.
[(a) 14.7 A (b) 1,380 W (c)
3.77 mWb]

GIVEN:
Io = 15 A N1 = 550 turns
cos ∅ o = 0.2 Im = ?
∅ o = cos (0.2) = 78.46
-1 o
Ic = ?
V = 460 V ∅ max = ?
f = 50 Hz
Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
SOLUTION:

a. I m=I o sin (θo )


I m=15 sin(78.46 ° )
I m=1 4.7 A
θo
b. (¿)
I c =I o cos ¿
78.46 °
(¿)
I c =15 cos ¿
I c =3 A

W =I c V
W =(3 A)(460 V )
W =1380 Watts

c. E1=4.44 ∅max f N 1
230 V =4.44 ∅max ( 50 x 10−3 ) (550)
∅max =3.77 mWb

Prepared
This study source was downloaded by 100000865285906 from CourseHero.com on by: ENGR.
04-09-2023 22:06:37 Melchor
GMT -05:00 R. BARCENAS

https://www.coursehero.com/file/65094132/AC-DC-LEC-TRANSFORMERdocx/
Powered by TCPDF (www.tcpdf.org)

You might also like