UGT CALCULATION-

FIRE FIGHTING
FOR ASSEMBLY BUILDING(ABOVE 15M H EIGHT NOT EXCEEDING 24M)
AMOUNT OF WATER REQUIRED FOR FIRE FIGHTING IN UGT=75000 LIT (AS PER NBC)
FOR BUSINESS BUILDING(LESS THAN 10M IN HEIGHT)
AMOUNT OF WATER REQUIRED FOR FIRE FIGHTING IN UGT=25000 LIT (AS PER NBC)
THEREFORE,
TOTAL AMOUNT OF WATER REQUIRED FOR FIGHTING=1,00,000 LIT

1) AUDITORIUM
CAPACITY OF THEATER =250 PEOPLE
AMOUNT OF WATER REQUIRED =15 LIT/SEAT
TOTAL AMOUNT OF WATER = 3750 LIT/DAY
STAFF-
TOTAL NO.OF STAFF =40 PEOPLE FLANGE
AMOUNT OF WATER REQUIRED =45 LIT/SEAT
TOTAL AMOUNT OF WATER = 1800 LIT/DAY
TOTAL =5550 LIT/DAY
FIREBRIGADE
2) RECEPTION CONNECTIONPOINT
CAPACITY OF THEATER =25 PEOPLE
AMOUNT OF WATER REQUIRED =45 LIT/SEAT
TOTAL AMOUNT OF WATER = 1125 LIT/DAY
3) YOUTH INTERACTION
CAPACITY OF THEATER =50 PEOPLE
AMOUNT OF WATER REQUIRED =70 LIT/SEAT
TOTAL AMOUNT OF WATER = 3500 LIT/DAY
4) MULTIPURPOSE HALL
CAPACITY OF THEATER = 250 PEOPLE
AMOUNT OF WATER REQUIRED =70 LIT/SEAT
TOTAL AMOUNT OF WATER = 17500 LIT/DAY
5) POP-UP MUSEUM
CAPACITY OF THEATER =100 PEOPLE CONCRETEBASE MAINHYDRANTLINE
AMOUNT OF WATER REQUIRED =135 LIT/SEAT
TOTAL AMOUNT OF WATER = 13500 LIT/DAY
6) EXHIBITION HALL
CAPACITY OF THEATER = 60 PEOPLE
AMOUNT OF WATER REQUIRED =135 LIT/SEAT
TOTAL AMOUNT OF WATER = 8100 LIT/DAY
7) VISITOR CENTER
CAPACITY OF THEATER =50 PEOPLE
AMOUNT OF WATER REQUIRED =70 LIT/SEAT
TOTAL AMOUNT OF WATER = 3500 LIT/DAY
TOTAL DOMESTIC WATER REQUIRED IN UGT= 52,775 LIT/DAY
TOTAL AMOUNT OF WATER IN UGT = DOMESTIC +FIRE FIGHTING
= 52,775+1,00,000
= 1,52,775. FLANGE

UGT DIMENSIONS-
CONSIDERING HEIGHT OF UGT= 1.5+0.3(FREE BOARD)= 1.8M
VOLUME= 157.42 CUBIC METER
ASSUMING, RATIO OF BREADTH TO LENGTH IS 1:3 CHAIN
THEREFORE, BREATH= x AND LENGTH= 3x FIREBRIGADE
THEREFORE, VOLUME= LXBXH CONNECTIONPOINT
152.775=3xXxX1.5
THEREFORE, BREATH =x=5.826
LENGTH= 3x= 17.478
THEREFORE,OVERALL SIZE OF TANK= 5.826M X 17.478M X 1.50M
LEGENDS

OHT CALCULATIONS- SUPPLY MAIN

FIRE HYDRANT

CALCULATION THE CAPACITY FOR OHT FOR COMMUNITY CENTER.


CONSIDERING THE TOTEL NO. OF 3 OVERHEAD TANK TO BE PROVIDED. UNDERGROUND TANK

FIRE FIGHTING- SUPPLY LINE FROM UGT


FOR ASSEMBLY BUILDING (ABOVE 15M HEIGHT NOT EXCEEDING 24M ) CONCRETEBASE
AMMOUNT OF WATER REQUIRED FOR FIRE FIGHTING IN OUT
=20000 LIT(AS PER NBC) MAINHYDRANTLINE OVERHEAD TANK
THEREFORE, IN OHT 1= 12000 LIT
IN OHT 2= 8000 LIT
ISOLATION VALVE
DOMESTIC-
ASSSUMING, 50% TOTAL DOMESTIC WATER REQUIRED TO BE IN OHT. PRESSURE GAUGE
THEREFORE, AMOUNT OF WATER REQUIRED= 50% PF 5,550 LIT/DAY
=2,775 LIT/DAY NON-REVERSING VALVE
THEREFORE, IN OHT 1= 6000 LIT/DAY
IN OHT 2= 4000 LIT/DAY
THEREFORE, TOTAL CAPACITY OF OHT 1= 18,000 LIT/DAY
OHT 2= 12,500 LIT/DAY
OTH 1DIMENTION-
CONSIDERING HEIGHT OF OTH= 1.5+0.3(FREE BOARD)= 1.8M
VOLUME= 18,000 CUBIC METER
ASSUMING, RATIO OF BREADTH TO LENGTH IS 1:3 THRUST HYDRANT
THEREFORE, BREATH= x AND LENGTH= 3x BLOCK CONNECTION
THEREFORE, VOLUME= LXBXH AGAINST VALVE
UNDISTURBED
18.0=3xXxX1.5 SOIL
THEREFORE, BREATH =x=2M BLOCK
LENGTH= 3x=12M FLAT STONES OR
HEIGHT= 1.5+0.3=1.8M CONCRETE SLABS
THEREFORE,OVERALL SIZE OF TANK= 2M X 12M X 1.8M
FIRE HYDRANT
OTH 1DIMENTION-
CONSIDERING HEIGHT OF OTH= 1.5+0.3(FREE BOARD)= 1.8M
VOLUME= 12,500 CUBIC METER
ASSUMING, RATIO OF BREADTH TO LENGTH IS 1:3
THEREFORE, BREATH= x AND LENGTH= 3x
THEREFORE, VOLUME= LXBXH
12.5=3xXxX1.5
THEREFORE, BREATH =x=1.6M
LENGTH= 3x=4.8M
HEIGHT= 1.5+0.3=1.8M
THEREFORE,OVERALL SIZE OF TANK= 1.6M X 4.5M X 1.8M